WSXA SSA Dimming Occupancy Wall Switch
“
Product Information:
Specifications:
- Product Name: Dimming Occupancy Wall Switch
- Output Rating:
- 120VAC, 800W, 6.7A
- 277VAC, 1200W, 4.3A
- 347VAC, 1500W, 4.3A
Product Usage Instructions:
Active Configuration Mode:
To enter active configuration mode:
- Locate the PIN hole on the switch.
- Insert the pre-packaged tool into the PIN hole to start active
configuration mode. - Active configuration mode allows for pairing and setting
changes directly from the switch.
Conversion From Ground Only:
If connection to neutral is required by code:
- The unit can be converted in seconds by slipping off the green
sleeve.
Operational Settings:
To perform operations:
- Pairing tool must be inserted.
- Press any button on the front of the switch to enter mode.
- Occupancy Time Detection:
- Maintain the same light level after occupancy was last
detected. - Prolong state is adjustable via the app.
- Maintain the same light level after occupancy was last
Wiring and Pairing:
Based on your wiring situation, follow these steps to pair your
wall switch:
- Power Interrupt Verification: Insert the tool and press any
button for 6 seconds to start auto-pairing. - When using the Clarity+ app, follow the intuitive workflow in
the app. - For 3-way or multi-way applications, refer to the provided
settings.
Frequently Asked Questions (FAQ):
Q: Can I use a different tool for active configuration
mode?
A: No, only use the pre-packaged tool provided. Do not insert
metal into the PIN hole.
Q: How do I reset the PIN of a secure group?
A: Use setting code 9 to reset the PIN of a secure group.
“`
WSXA SSA
Dimming Occupancy Wall Switch
Installation Instructions
Active Configuration Mode Locate the PIN hole as shown below. Insert pairing tool to start active configuration mode, which allows for pairing and setting changes directly from the switch.
WARNING
Only use pre-packaged tool. DO NOT INSERT METAL INTO PIN HOLE!
CONVERSION FROM GROUND ONLY This product is pre-configured for wiring without a neutral; however, if connection to neutral is required by code, the unit easily converts in seconds by slipping off green sleeve. OUTPUT RATING 120VAC, 800W, 6.7A; 277VAC, 1200W, 4.3A; 347VAC, 1500W, 4.3A OPERATIONAL SETTINGS Pairing tool must be inserted to perform any of the below operations. Press any button on the front of the switch to enter mode. 2 = Occupancy Time Detection
Maintain the same light level after occupancy was last detected. When time expires, group will enter prolong state (10% dim and off after 2.5 min). Prolong state is adjustable via app.
Based on your wiring situation, there are multiple ways to pair your wall switch:
1. Power Interrupt Verifcation: When SensorSwitch AIR embedded or components are on the load side of the wall switch, insert the tool as shown, then press and hold any button for 6-seconds to start auto-pairing.
2. When the switch is on a different circuit, it can be accepted into a group via join / accept pairing technique. Here are the steps and LED visual indicators: a) Insert pairing tool to start “active configuration mode”. b) Visually, the LED in active configuration mode will double blink every second. c) Press any button 6-times to place device in join mode. Visually represented by a constanct LED blink. d) On an existing device within the group, place that device in accept mode. Repeat steps a and b as shown above; however, press any button 7-times to start the accept mode. (see setting codes 6 and 7 for more details) e) WARNING: When using jin / accept pairing ensure other spaces are not being paired at the same time; otherwise cross pairing may occur.
3. When pairing the switch using the Clarity+ app, use the intuitive app workflow. For more information, see Clarity+ Quick Start Guide.
3-Way or (Multi-Way Application);
WSXA SSA 1
1 – Test Mode** 2 – 30 sec 3 – 2.5 min 4 – 5.0 min 5 – 7.5 min*
6 – 10.0 min 7 – 12.5 min 8 – 15.0 min 9 – 17.5 min 10 – 20.0 min
11 – 22.5 min 12 – 25.0 min 13 – 27.5 min 14 – 30.0 min
* Defualt Setting **Test mode sets Occupancy Time Delay to 30 seconds and increases photocell transition rate in addition to disabling the microphone on units with Dual Technology
3 = Start Level
Level of light output when occupancy is initially detected. Not applicable in Automatic Dimming Control mode.
1 – 10% 2 – 20% 3 – 30%
4 – 40% 5 – 50% 6 – 60%
7 – 70% 8 – 80% 9 – 90%
10 – 100%*
* DEFAULT SETTING
4 = On Mode 1 – Automatic On*: Sensor automatically turns the light on when it detects occupancy.
2 – Manual On: Sensor requires pressing the button to turn the light on.
5 = High Trim Setting (Maximum Brightness level)
1 – 1% 2 – 10%
3 – 20% 4 – 30%
5 – 40% 6 – 50%
7 – 60% 8 – 70%
10 – 90% 9 – 80%
11 – 100%*
6 = Join
“Join” places an unpaired device to join mode allowing the device to join an existing group or initiate formation of a new group (using Join / Accept pairing method). Join mode may also be used to form 3-way connections as shown in the typical.
7 = Accept
“Accept” places an paired or unpaired device into accept mode allowing the device to accept a join mode device into the group or form a new group. For group formation using Join / Accept pairing method, the accepting device becomes the configurator represented by “GM” within the app.
8 = Add Mobile Device (Clairity Pro)
Allow user to use mobile application of a pre-configured group.
WSXA SSA 2
1 SETTING CODE 6 (Join a Group)
2 SETTING CODE 7 (Accept New Device)
9 = Reset PIN Reset the PIN of a secure group
10= Remove Local Device Only 1 – Do not remove 2 – Remove
See Note * and **
* If device is the pairing device, used to form group, the group will “Restore” all devices group back to factory default. This action will un-pair all devices.
** If device is not the pairing device, it will send a “Delete Node” message to the pairing device for itself and restore itself back to factory defaults. It will no longer be able to communicate with the group.
11 = Restore all Group Devices to Factory Default 1 – Do not remove 2 – Remove
12 = LOW TRIM SETTING (LOWEST DIM VALUE)
1 – 1% 4 – 30% 7 – 60% 10 – 90% 2 – 10% 5 – 40% 8 – 70% 11 – 100% 3 – 20% 6 – 50% 9 – 80%
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com © 2025 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/11/2025 912-00149-004
1 of 2
WSXA SSA
Dimming Occupancy Wall Switch
Installation Instructions
LED RESPONSE
SWITCH SETTING Occupancy Time Detection Maintain the same light level after occupancy was last detected.
Occupancy Start Level Level of light output when occupancy is initially detected.
On Mode Change between Occupancy and Manual On Modes.
High Trim Setting Maximum Brightness
Join Add new wall switch device to an existing group, form; used in 3_way setup.
Accept Accept new switch into an existing group or form a new group; used in 3_way setup.
Add Mobile Device Show app-less formed group and allow mobile device to join group.
Reset PIN If PIN in lost used to create new PIN.
Remove Local Device Only Used to remove local device. Note: Removing switch used to form group will delete entire group.
Delete Group Used to return all devices back to default state.
Low Trim Setting Low Dim Value
ACTION and LED RESPONSE
ACTION: 1) Insert Tool.
2) Press any front button 2-times to enter time delay setting code. LED Observance: LED will blink back current setting if no additional input is given. This is done 3-times. ACTION: 1) At any point, while displaying current setting, press any front button to set value. LED Observance: LED will blink back new setting. This is done 3-times.
ACTION: 1) Insert Tool:
2) Press any front button 3-times to desired occupied brightness start level setting code. LED Observance: LED will blink back current setting if no additional input in given, This is done 3-times. ACTION: 1) At any point, while displaying current setting, press any front button to set value. LED Observance: LED will blink back new setting. This is done 3-times.
ACTION: 1) Insert Tool. 2) Press any front button 4-times to set operation mode setting code. LED Observance: LED will blink back current setting if no additional input in given, This is done 3-times.
ACTION: 1) At any point, while displaying current setting, press any front button to set value. LED Observance: LED will blink back new setting. This is done 3-times.
ACTION: 1) Insert desired settings.
ACTION: 1) While blink back confirmation is occuring from prior action.
2) Press any front button 5 times.
2) Insert desired settings value.
LED will blink back new settings. This is done 3 times.
LED will blink back new settings. This is done 3 times.
ACTION: 1) Insert Tool into the switch that will be joining an app-lessly paired group:
2) Press any front button 6-times to enter setting option. LED Observance: ½ Second On, ½ Second Off, followed by rapid flash. NOTE: TIMEOUT 5-7 minutes.
ACTION: 1) Insert Tool into the switch that pairing app-less group:
2) Press any front button 7-times to enter setting option. LED Observance: LED will blink back setting entry followed by a rapid flash. NOTE: TIMEOUT 5-7 minutes
ACTION: 1) Insert Tool into app-lessly pairing wall switch:
2) Press any front button 8-times to enter setting option. LED Observance: ½ Second On, ½ Second Off, ½ Second On, ½ Second Off. NOTE: TIMEOUT 5-7 minutes.
ACTION: 1) Insert Tool:
2) Press any front button 9-times to enter reset PIN option. LED Observance: ½ Second On, ½ Second Off, ½ Second On, ½ Second Off. NOTE: TIMEOUT 5-7 minutes.
ACTION: 1) Insert Tool.
2) Press any front button 10-times to enter remove local device setting option. (a.) 1-press = do not remove (b.) 2- presses = Remove device. LED Observance: LED will blink back current setting if no additional input is given. This is done 3-times..
ACTION: 1) Insert Tool.
2) Press any front button 11-times to enter delete group setting option. (a.) 1-press = do not remove (b.) 2- presses = Remove device. LED Observance: LED will blink back current setting if no additional input is given. This is done 3-times..
ACTION: 1) Insert desired settings.
ACTION: 1) While blink back confirmation is occuring from prior action.
2) Press any front button 12 times.
2) Insert desired settings value.
LED will blink back new settings. This is done 3 times.
LED will blink back new settings. This is done 3 times.
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com © 2025 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/11/2025 912-00149-004
2 of 2
Documents / Resources
![]() |
sensorswitch WSXA SSA Dimming Occupancy Wall Switch [pdf] Instruction Manual SSA, JOT, WSXA SSA Dimming Occupancy Wall Switch, Dimming Occupancy Wall Switch, Occupancy Wall Switch, Wall Switch |