SENECA logo

INSTALLATION MANUAL
Z-KEY
Z-KEY-P
Z-KEY-E

PRELIMINARY WARNINGS

The word WARNING preceded by the symbolWarning icon indicates conditions or actions that put the user’s safety at risk.
The word ATTENTION preceded by the symbolWarning icon indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

Warning icon WARNING: The full content of this manual must be read before any operation. The module must only be used by
qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
SENECA Z-KEY-E Gateway Ethernet IP - icon The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
WEE-Disposal-icon.png Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling).
The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.
SENECA Z-KEY-E Gateway Ethernet IP - QR 1 www.seneca.it/products/z-key-p
SENECA Z-KEY-E Gateway Ethernet IP - QR 2 www.seneca-it/products/z-key-e
SENECA Z-KEY-E Gateway Ethernet IP - QR 3 www.seneca.it/products/z-key

CONTACT INFORMATION

Technical support support@seneca.it Product information sales@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised.
The content of this document corresponds to the described products and technologies.
Stated data may be modified or supplemented for technical and/or sales purposes.
MI00580-4-EN
INSTALLATION MANUAL

MODULE LAYOUT

SENECA Z-KEY-E Gateway Ethernet IP - LAYOUT

Dimensions: 17.5 x 102.5 x 111 mm, Weight: 100 g; Enclosure: PA6, black

SIGNALS VIA LED ON FRONT PANEL

LED STATUS LED meaning
PWR ON The device is powered correctly
COM
Z-KEY-P/ Z-KEY-E version
Flashing Profinet or Ethernet/IP communication active
Off No Profinet or Ethernet/IP communication
TX1 Flashing Data transmission on port #1 RS485
RX1 Flashing Data receipt on port #1 RS485
TX2 Flashing Data transmission on port #2 RS485/RS232
RX2 Flashing Data reception on port #2 RS485/RS232
ETH ACT Green Flashing Packet transmission on Ethernet port
ETH LNK Yellow ON Ethernet connection present

TECHNICAL SPECIFICATIONS

CERTIFICATIONS SENECA Z-KEY-E Gateway Ethernet IP - QR 3
INSULATION SENECA Z-KEY-E Gateway Ethernet IP - INSULATION
ENVIRONMENTAL CONDITIONS Temperature: -25 °C – + 65 °C; Humidity:;30%– 90% non condensing.
Altitude: Up to 2000 m above sea level; Storage temperature: -30 °C – + 85 °C
Protection rating: IP20 (Not evaluated by UL)
ASSEMBLY IEC EN60715, 35mm DIN rail in vertical position.
POWER SUPPLY Voltage: 11 – 40 Vdc; 19 – 28 Vac 50 – 60 Hz; Absorption: Max. 1,5W
CONNECTIONS 3-way removable screw terminals, pitch 5 mm
Rear connector IDC10 for DIN bar 46277
RJ45 front connector
COMMUNICATION PORTS RS232 or RS485 switchable on terminal 10 – 11 – 12 (serial port 2)
Maximum Baud rate 115 k, maximum cable length RS232 < 3m
RS485 IDC10 rear connector: Maximum Baud rate 115 k. (serial port 1)
RJ45 front Ethernet connector: 100 Mbit/s, maximum distance 100 m
CONFIGURATION Configuration and FW update via webserver; Via DIP – SWITCH
Via EASY SETUP 2 configuration software

Warning icon ATTENTION
The device may only be powered by a power supply unit with a limited energy electric circuit max.
40Vdc / 28Vac output in accordance with CAN/CSA-C22.2 No. 61010-1-12 / UL Std. No. 61010-1 (3rd Edition) chapter 6.3.1/6.3.2 and 9.4 or class 2 according to CSA 223/UL 1310.

FACTORY IP ADDRESS

The default module IP address is static: 192.168.90.101

SETTING THE DIP-SWITCHES

Warning icon WARNING
The DIP-switch settings are read only at boot time. At each change, perform a restart.
SW2 DIP-SWITCH: Through DIP-SWITCH-SW1 it is possible to set the IP configuration of the device:

DESCRIPTION DIP 1 DIP 2 DIP 3 DIP 4
To obtain the configuration from the Flash memory, both SW1
DIP switch selectors must be set to OFF
SENECA Z-KEY-E Gateway Ethernet IP - icon 1 SENECA Z-KEY-E Gateway Ethernet IP - icon 2 RESERVED RESERVED
To reset the device to factory settings both SW1 DIP switches
must be set to ON
SENECA Z-KEY-E Gateway Ethernet IP - icon 3 SENECA Z-KEY-E Gateway Ethernet IP - icon 3 RESERVED RESERVED
To force the device’s IP address to the standard value of
SENECA Ethernet products: 192.168.90.101
SENECA Z-KEY-E Gateway Ethernet IP - icon 10 SENECA Z-KEY-E Gateway Ethernet IP - icon 6 RESERVED RESERVED
Reserved SENECA Z-KEY-E Gateway Ethernet IP - icon 7 SENECA Z-KEY-E Gateway Ethernet IP - icon 10 RESERVED RESERVED

SENECA Z-KEY-E Gateway Ethernet IP - icon 11

Warning icon ATTENTION
DIP3 and DIP4, on models where they are present, must remain OFF.
If set otherwise, the instrument will not operate correctly.
RS232/RS485 SETTING: RS232 or RS485 configuration on terminals 10-11-12 (serial port 2)

SW2
1 ON SENECA Z-KEY-E Gateway Ethernet IP - icon 3 RS232 ACTIVATION
0 OFF SENECA Z-KEY-E Gateway Ethernet IP - icon 1 RS485 ACTIVATION

PROFINET AND WEBSERVER MODE

The device is normally in Profinet mode; in Profinet mode the device can be configured only through the Easy Setup2 software.
In order to access the internal webserver it is necessary to put the device in Webserver mode using the Easy Setup2 or Seneca Device Discovery software. it is also possible to change the operating mode by pressing the side button PS1 following the procedure given in the user manual.

WEB SERVER

To access the maintenance Web Server with 192.168.90.101 factory IP address:
Default user: admin, Default password: admin, http://192.168.90.101
N.B.: For the Z-KEY-P version it is first necessary to activate webserver mode
Warning icon CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.

INSTALLATION REGULATIONS

The module has been designed for vertical installation on a DIN 46277 rail. For optimal operation and long life, adequate ventilation must be provided. Avoid positioning ducting or other objects that obstruct the ventilation slots.
Avoid mounting modules over heat-generating equipment. Installation in the bottom part of the electrical panel is recommended.
Warning icon ATTENTION
These are open-type devices and intended for installation in an end enclosure / panel offering mechanical protection and protection against spread of fire.

ELECTRICAL CONNECTIONS

Warning icon CAUTION
To meet the electromagnetic immunity requirements:
– use shielded signal cables;
– connect the shield to a preferential instrumentation earth system;
– separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc…).

POWER SUPPLY SERIAL PORT 2: RS485 SW2 = OFF SERIAL PORT 2: RS232 SW2 = ON
SENECA Z-KEY-E Gateway Ethernet IP - icon 13 SENECA Z-KEY-E Gateway Ethernet IP - icon 15 SENECA Z-KEY-E Gateway Ethernet IP - icon 12

Warning icon ATTENTION
Use only copper or copper-clad aluminium or AL-CU or CU-AL conductors

IDC10 CONNECTOR

SENECA Z-KEY-E Gateway Ethernet IP - CONNECTOR

The illustration shows the meanings of the various IDC10 connector pins if signals are to be sent via them directly.

MI00580-4-EN
INSTALLATION MANUALSENECA Z-KEY-E Gateway Ethernet IP - icon 5SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY;
Tel. +39.049.8705359
– Fax +39.049.8706287

Documents / Resources

SENECA Z-KEY-E Gateway Ethernet/IP [pdf] Instruction Manual
Z-KEY-E Gateway Ethernet IP, Z-KEY-E, Gateway Ethernet IP, Ethernet IP

References

Leave a comment

Your email address will not be published. Required fields are marked *