Product Information

  • Product Name: R-PASS
  • Manufacturer: SENECA srl
  • Weight: 170 g
  • Enclosure: UL94-V0 self-extinguishing PC/ABS material, black
  • Certifications: CE
  • Declaration

Technical Specifications

  •  35mm DIN rail IEC EN60715 assembly
  • Removable 3.5mm pitch terminal block, 1.5mm2 max cable section for connections
  • Communication Ports: 1 USB A connector, 4 RJ45 Ethernet ports (only version with 4 Ethernet ports), 2 RJ45 Ethernet ports (only  version with 2 Ethernet ports), 1 RS485/RS232 serial port  configurable via software, 1 RS485 serial port, 1 micro USB dedicated to debugging
  • Digital Outputs: DO1…DO4
  • Digital Inputs: DI1…DI4
  • Analog Inputs: AI1, AI2
  • Auxiliary Voltage Output: 12Vdc; Max. 50mA
  • Wi-Fi (only R-PASS-W)

Product Usage Instructions
Before starting the installation process, make sure to read and understand all the preliminary warnings mentioned in the user manual. Failure to follow these warnings may result in user safety risks or damage to the instrument or connected equipment. The R-PASS module has a weight of 170 g and is enclosed in a black UL94-V0 self-extinguishing PC/ABS material enclosure. The module layout is as follows: – Width: 106.6 mm – Height: 32.2 mm – Depth: 90.0 mm The front panel of the module contains several LED indicators that provide status information. The LED indicators and their corresponding statuses are as follows: DO1…DO4: Digital Outputs – DI1…DI4: Digital Inputs – DO AUX: Auxiliary Voltage Output – STS (Status): Status Indicator – VPN: VPN Indicator – SRV: Server Indicator – UPS: UPS Indicator – LOG / RUN (only R-PASS-0 / -W): Logging / Running Indicator (for R-PASS-0 / -W models) – LOG / RUN (only R-PASS-S / -E): Logging / Running Indicator (for R-PASS-S / -E models) – WIFI (only R-PASS-W): Wi-Fi Signal Strength

Indicator (for R-PASS-W model) 5. The technical specifications of the R-PASS module are as follows: – Certifications: CE Declaration (refer to the provided link for more information) – Environmental
Conditions: Not specified in the given text – Assembly: 35mm DIN rail IEC EN60715 – Connections: Removable 3.5mm pitch terminal block, 1.5mm2 max cable section – Communication Ports: 1 USB A
connector, Ethernet ports (4 or 2 depending on the model), RS485/RS232 serial port, RS485 serial port, micro USB dedicated to debugging – Insulation: Not specified in the given text – Digital
Outputs: DO1…DO4 – Digital Inputs: DI1…DI4 – Analog Inputs: AI1, AI2 – Auxiliary Voltage Output: 12Vdc; Max. 50mA – Wi-Fi (only R-PASS-W): Wi-Fi capabilities (specific details not provided) 6.

The electrical connections for the R-PASS module are as follows: – Analog Input Voltage: +, AI1, AI2, GND – Analog Input Current: mA When making electrical connections, please observe the following precautions: – Do not exceed the upper power supply limits to avoid serious damage to the module. – Switch off the module before connecting inputs and outputs. – To meet electromagnetic immunity requirements: – Use shielded signal cables. – Connect the shield to a preferential instrumentation earth system. – Separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.). 8. Optional modules can be added through the lateral connection of the R-PASS module. For more information on accessories and optional modules, visit the manufacturer’s website mentioned on page 1 or scan the provided QR-CODE.

PRELIMINARY WARNINGS

The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available using the QR-CODE shown on page 1. The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation. Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection center authorized to recycle electrical and electronic waste. This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorized. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.

MODULE LAYOUT
Weight: 170 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.

SENECA-R-PASS-MI00555-IIoTE-dge-Gateway-FIG-1

SIGNALS VIA LED ON THE FRONT PANEL

LED STATUS LED meaning
DO1.. DO4 On Output enabled
Off Output disabled
DI1…DI4 On Input activated
Off Input deactivated
DO AUX On Auxiliary supply active
Off Fault or wiring error
STS

(Status)

Flashing The module is working correctly
Off Locking system
On Locking system
VPN On VPN connection active
Flashing VPN connection problems
SRV On VPN BOX “SERVICE” connection is working correctly
Flashing VPN BOX “SERVICE” connection in error
UPS On UPS active (only in the presence of the R-COMM accessory)
Off UPS inactive
LOG / RUN (only R-PASS-0 / -W) On Data Logger active and working correctly
Flashing Data Logger in error
Off Data logger not active
LOG / RUN (only R-PASS-S / -E) On PLC up and running
Flashing PLC in STOP
Off PLC not active
WIFI

(only R-PASS-W)

On WiFi enabled in Station mode
Flashing WiFi enabled in access-point mode
 

 

(only R-PASS-W)

On WiFi signal strength in Station mode
PWR On Device powered correctly
RX1 / RX2 On Incorrect RS485 / RS232 connection
Flashing Reception of data packet completed on RS485 / RS232
TX1 / TX2 Flashing Transmission of data packet completed on RS485 / RS232
ETH ACT (Yellow) Flashing Packet transit on Ethernet port
ETH LNK (Green) Flashing Ethernet port connected

TECHNICAL SPECIFICATIONS

Through the lateral connection, it is possible to add optional modules. For more information on accessories and optional modules, visit the website on page 1 or scan the QR-CODE.

 

CERTIFICATIONS

SENECA-R-PASS-MI00555-IIoTE-dge-Gateway-FIG-3

 

https://www.seneca.it/products/r-pass/doc/CE_declaration

 

ENVIRONMENTAL CONDITIONS

Operating temperature: from -25°C to +65 °C Humidity: 10% ÷ 90% noncondensing.

Storage temperature: from -30°C to +80°C Protection rating: IP20

ASSEMBLY 35mm DIN rail IEC EN60715
CONNECTIONS Removable 3.5mm pitch terminal block, 1.5mm2 max cable section
 

COMMUNICATION PORTS

1 USB A connector

4 RJ45 Ethernet ports (only version with 4 Ethernet ports) 2 RJ45 Ethernet ports (only version with 2 Ethernet ports) 1 RS485/RS232 serial port configurable via software

1 RS485 serial port

1 micro USB dedicated to debugging

POWER SUPPLY 10 ÷ 40Vdc; 19 ÷ 28Vac; 8W max
 

 

INSULATION

 

SENECA-R-PASS-MI00555-IIoTE-dge-Gateway-FIG-2

DIGITAL OUTPUTS OptoMOS® 30Vdc, 25mA max

Number of channels: 4

DIGITAL INPUTS Number of channels: 4, Absorbed current: 2.2mA

Input voltage: 0÷30V, Threshold ON > 9V, Threshold OFF < 8V IEC6113-2 Type 1 & 3 compliant

ANALOGUE INPUTS Voltage 0 ÷ 30Vdc, impedance 20kΩ Current 0 ÷ 25mA, impedance ~ 50Ω
AUXILIARY VOLTAGE OUTPUT 12Vdc; Max. 50mA
WI-FI

(only R-PASS-W)

Integrated WiFi 802.11 b/g/n, 2.4 ÷ 2.4835GHz band, max Output Power: 17dBm (50mW)

ELECTRICAL CONNECTIONS
CAUTION VThe upper power supply limits must not be exceeded, as this could cause serious damage to the module. Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirementsThe upper power supply limits must not be exceeded, as this could cause serious damage to the module. Switch the module off before connecting inputs and outputs. To meet the electromagnetic immunity requirements:

  • use shielded signal cables;
  • connect the shield to a preferential instrumentation earth system;
  • separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc…).SENECA-R-PASS-MI00555-IIoTE-dge-Gateway-FIG-SENECA-R-PASS-MI00555-IIoTE-dge-Gateway-FIG-5

DIP-SWITCH
The DIP-SWITCHES on the back of the device have the following functions:

SW1
DIP1 RESERVED DIP3 ON DEFAULT SETTINGS
DIP2 RESERVED DIP4 ON

To access the DIP-SWITCH it is necessary to remove the bottom of the instrument

ETHERNET CONNECTION RULES
For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.

FACTORY IP ADDRESS
The default module IP address is static: 192. 168. 90. 101 (LAN)

WEB SERVER
To access the configuration web server with the factory IP address above, use the following credentials: Username: admin; Password: admin; Port: 8080
Example: To access the web server from LAN.

CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.