SENECA R - logo

INSTALLATION MANUAL
R-32DIDO
R-32DIDO-P

PRELIMINARY WARNINGS

The word WARNING preceded by the symbolWarning icon indicates conditions or actions that put the user’s safety at risk.
The word ATTENTION preceded by the symbolWarning icon indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

Warning icon WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - warning The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
Dustbin Icon Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling).
The symbol on the product or its packaging shows the product must be surrendered to a collection center authorized to recycle electrical and electronic waste.
SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - qr codehttp://www.seneca.it/products/r-32dido
DOCUMENTATION R-32DIDO
SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - qr code 1http://www.seneca.it/products/r-32dido-p
DOKUMENTATION R-32DIDO-P
SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - sembly SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - sembly 1

SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 – Fax +39.049.8706287

CONTACT INFORMATION

Technical support support@seneca.it Product information sales@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorized.
The content of this document corresponds to the described products and technologies.
Stated data may be modified or supplemented for technical and/or sales purposes.

INSTALLATION MANUAL

MODULE LAYOUT

SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - MODULE LAYOUT

Weight: 170 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.

SIGNALS VIA LED ON FRONT PANEL

LED STATUS LED meaning
PWR On Device powered
Off Device not powered
101/1032 On Digital input/output active
Off Digital input/output not active
OUT

SUP

On Digital inputs/outputs powered
Off Digital inputs/outputs not powered
STS

(Status)

On IP address set
Flashing Waiting for the IP address from the DHCP
COM (R-32DID0-P version only) Off No Profinet communication
Flashing Profinet communication present
FAIL On Digital output in FAIL
Off Digital output OK
RX (R-32DID0 version only) On RS485 port wiring error
Flashing Reception of data packet completed on RS485
TX (R-32DID0 version only) Flashing Reception of data packet completed on RS485
ETH TRF (Yellow) Flashing Packet transit on Ethernet port
ETH LNK (Green) Flashing The Ethernet port is connected (LINK)

TECHNICAL SPECIFICATIONS

CERTIFICATIONS CE SYMBOL SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - qr code 2

https://www.seneca.it/products/r-32dido/doc/CE_declaration

INSULATION SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - sembly 2SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - sembly 31500vas
POWER SUPPLY Voltage: 10÷40Vdc; 19÷28Vac; 50÷65Hz; Absorption: 3W max; Dissipation: 6.5W max
ENVIRONMENTAL
CONDITIONS
Operating temperature: from -25°C to +65 °C Humidity: 10% ÷ 90% non condensing. Storage temperature: from -30°C to +85 °C Protection rating: IP20
CONFIGURATION With integrated WEB server (only R-32DIDO) / Easy Setup 2
CONNECTIONS /
COMMUNICATION
PORTS
3.5 mm pitch terminal block, 1.5 mm² max cable section
1 micro USB port for programming (only R-32DIDO)
2 Ethernet (with LAN fault-bypass function) 100 base T on RJ45
1 RS485 port on terminals 23-24-25 (only R-32DIDO version)
DIGITAL INPUTS Number of channels: 32; Voltage: Threshold ON: >9V; Threshold OFF: < 4V; Vmax: 24V; Impedance 9kΩ
DIGITAL OUTPUTS Number of channels: 32, MOSFET, PNP; Max voltage/current: 0.2A / 24V

Warning iconCAUTION

Switch the module off before connecting inputs and outputs. To meet the electromagnetic immunity requirements:

  • use shielded signal cables;
  • connect the shield to a preferential instrumentation earth system;
  • separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc…).
POWER SUPPLY

SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - POWER SUPPLY

RS485 SERIAL PORT SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - SERIAL PORT Connection to the RS485 port. Polarity is not standardized; in some devices of other brands, it may be inverted.
         DIGITAL INPUTS (PNP) DIGITAL INPUTS (PNP)

 

DIGITAL OUTPUTS (PNP)

 

 

DIGITAL OUTPUTS (PNP)

 

SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - DIGITAL INPUTS SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - DIGITAL INPUTS 1 SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - DIGITAL INPUTS 2 SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - DIGITAL INPUTS 4

Warning iconCAUTION

The power supply must be sized according to the expected load at the outputs. Terminals 18-64 and 19-65 can be connected together on the same power supply.

Warning iconCAUTION

For correct operation of the instrument, terminals 18-64 and 19-65 must always be connected to the power supply.

DAISY-CHAIN ETHERNET CONNECTION

Warning iconCAUTION

IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES
Using the daisy-chain connection it is not necessary to use switches to connect the devices. The following examples show the correct connections.

SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - ETHERNET CONNECTION

There must be no loops in the Ethernet cabling, otherwise, the communication will not work. The modules and switches must be connected eliminating any loops. The following examples show the incorrect connections.

SENECA R 32DIDO 3 Phase Energy Power Meter with Universal Input - ETHERNET CONNECTION 1

The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of a power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically 4. The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched-off module is less than 100m.

ETHERNET CONNECTION RULES

For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required. CAT6 for industrial environments.

FACTORY IP ADDRESS

The default module IP address is static: 192. 168. 90. 101

WEB SERVER

To access the maintenance Web Server with the factory IP address above, use the following credentials: Account User: admin; Password: admin

Warning iconCAUTION

DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.

SETTING THE DIP-SWITCHES

The DIP-SWITCH on the back of the device has the following function:
SW1 DIP-SWITCH: DEFAULT SETTINGS

SW1

DIP1

ON

DEFAULT SETTINGS

DIP2

ON

To access the DIP-SWITCH it is necessary to remove the bottom of the instrument.

MI00575-0-EN