Secop 105N4120 NLV-CN Core Functions Controllers Compressors

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-PRODUCT

Product Usage Instructions

  • Ensure a minimum airflow of 3 m/s for both the compressor and electronic units. Direct airflow for electronics to the heat sink.
  • Fasten the copper shield of the controller cable properly to the clip at the compressor for optimum EMC performance.
  • Connect the compressor and controller to PE (Protective Earth) to avoid electrical hazards.
  • Collect all protective earth lines to one star point to prevent loop currents that could cause electronic component issues.
  • Installation should only be performed by trained personnel.
  • Do not remove the controller cover when the unit is powered on.
  • Disconnect from power and wait 30 seconds before accessing terminals.
  • Ensure the signal connection cable length does not exceed 3 meters.
  • Detailed instructions on thermostatic operation, frequency speed control, DWI serial communication, and defrost control are provided in the manual.
  • Refer to the manual for detailed technical data on the controller and compressors.
  • Dimensions of the product are outlined in the manual for reference.
  • Details on how to order additional units or replacement parts can be found in the manual.

INSTALLATION

WARNING!

  • Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-1To remove a compressor from a system, the tubes must be cut.
  • Never use a torch to remove brazed tubes.

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-2

Brazing on Suction Connectors (Direct Intake)

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-3

  • Refer to Product Bulletin:
  • Brazing on Suction Connectors (Compressors with Direct Suction Intake)

Airflow

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-4

  • Ensure proper airflow of 3 m/s at both compressor and electronic units.
  • The airflow for the electronics must be directed to the heat sink.

Earthing the Compressor and Controller

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-5

  • For optimum EMC performance, the copper shield of the controller cable must be fastened properly in the clip at the compressor.
  • The compressor and controller must be connected to PE (Protective Earth) to avoid risk of electrical hazard.
  • All protective earth lines, PE, in the application must be collected to one star point. This prevents loop currents, which could cause problems concerning the electronic components, communication lines, and sensors. The star-point is normally a screwed terminal on the chassis.

Wiring Diagram

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-6

  • Installation must only be done by trained personnel.
  • Do not remove the cover of the controller when the unit is powered on.
  • Disconnect from power and wait 30 seconds before accessing terminals.
  • The maximum cable length should not exceed 3 meters for signal connections.
  • A cable length of more than 3 m could alter the EMI performance.
  • Signal lines must be separated from power lines.

Connections

  1. 2x Protective Earth
  2. 2x Neutral
  3. 2x Line
  4. Thermostat/AEO
  5. Defrost
  6. Frequency and DWI

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-7

No. Description Type Note
1 Protective Earth FASTON 6.3 mm × 0.8 mm Mandatory, must be connected
2 Neutral FASTON 6.3 mm × 0.8 mm Mandatory, must be connected
3 Line FASTON 6.3 mm × 0.8 mm Mandatory, must be connected
4 Thermostat FASTON 6.3 mm × 0.8 mm For AEO only
5 Defrost FASTON 6.3 mm × 0.8 mm For AEO and defrost only
6 Frequency/DWI JST VH For frequency or DWI only

Wiring for Thermostatic Operation

  • For optimal hot-gas defrost performance, the relay output of the controller should be connected to the DEF input of the controller.
  • This ensures that the compressor operates at full speed when the hot gas valve is activated.

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-9

Wiring for Frequency Operation/DWI Communication

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-10

SPEED CONTROL

The Secop Core Functions controller is equipped with three different inputs for speed control to ensure easy integration.
Almost any temperature controller can be used to control the speed without needing to change the setup.
The Core Functions controller has automatic input detection and will automatically select the input that is active.

  1. Frequency signal.
  2. Thermostatic operation with AEO, Adaptive Energy Optimization.
  3. DWI, Dual Wire Interface with separated RX and TX lines.
    • If more signals are connected, the input with the highest priority (1–3) will be used.
    • DWI input has the lowest priority and can be used for monitoring in combination with the other inputs.
    • If DWI sends an active start command, the DWI input will change priority to 1 and overrule all other input signals.

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-11

Thermostatic Operation with AEO

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-12

  • AEO is the only control mode where there is no direct relation between speed and input signal.
  • The speed is automatically calculated based on the runtime ( time between cut-in and cut-out).
  • The AEO can be interfaced by a normal thermostat or relay.
% Runtime % Speed
100 105
110 110
120 120
140 130
160 140
190 180
220 225

Advantages of the AEO:

  • Easy to interface.
  • Mechanical thermostat.
  • Electronic control with relay output.
  • Perfect for applications with stable conditions, such as freezers, catering equipment.

The AEO operates with a target runtime and will automatically adapt the speed until the target runtime is met.

  • If the compressor runtime is shorter than the target time, the speed in the next cycle will be reduced.
  • If the runtime is longer than the target time, the speed in the current cycle will be increased until the cut-out is reached. The next cycle is calculated as the average speed for the last cycle.

Frequency Speed Control

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-14

The speed can be controlled by applying a low-voltage frequency signal to the frequency input

  • The speed is changed linearly between 66 Hz and 150 Hz.
  • The frequency of 66 Hz corresponds to 2000 rpm, 150 Hz to 4500 rpm (30 rpm/1 Hz by default).
  • If the frequency is between 10-50 Hz, the compressor stops.
  • The frequency signal should have a voltage of 5–12 V and a duty cycle of 50%.

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-15

DWI Serial Communication

  • The DWI, Dual Wire interface, is a bidirectional communication protocol that allows the temperature controller to communicate with the compressor controller.
  • In addition to speed, the temperature controller can get different information from the controller, such as power consumption, actual speed, electronic temperature, and fault status.
  • The communication interface is shared with the frequency interface. A full description of the interface and a list of supported commands may be requested from Secop.
Communication Specification
Baud Rate: 600 Baud
Start Bits: 1
Data Bits: 8
Stop Bits: 1
Parity: No
Frame Size: 5 Bytes
Appliance Controller: Master
Compressor Controller: Client
Start Bit: 1 -> 0 (logic level)
Data Bits: Inverted logic (0V -> “1”)
Stop Bit: 0 -> 1 (logic level)
Control Mode: Half duplex

Defrost Control with AEO

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-17

When variable-speed compressors are used in self-adapting capacity modes, defrosting may not work properly since the compressor speed cannot be controlled during defrost: The compressor lacks capacity for hot gas and the following pull-down.
To improve defrost when AEO is used, the Core Functions controller has an extra input that can be connected to the defrost relay output of the temperature controller.

  • Hot-gas defrosting: When the defrost and AEO inputs are activated simultaneously, the Core Functions controller switches to a defined speed (defrost low speed). After a defined defrost low-speed time, the compressor will increase to defrost high speed until the defrost is completed.
  • The two-speed defrost is a new feature of all next-generation controllers to avoid liquid refrigerant inside the compressor.
  • Electrical defrosting: When only the defrost input is activated, the compressor will remain stopped, but the information is used to trigger pull-down after defrosting.
  • After defrosting, the Core Functions controller will run the first cycle at high speed to ensure that the heat is removed as fast as possible.
  • After the pull-down, it reverts to the speed it had before defrost.

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-18

TECHNICAL DATA

Controller Data

  Electronic Unit 105N4120
 

Power supply

Nominal voltage 220–240 V AC
Minimum operating voltage 187 V AC
Minimum starting voltage 198 V AC
Maximum voltage 264 V AC
Frequency 50–60 Hz
Max power input 1000 W
Power Factor Corrector No
Motor cable length 680±20 mm / 26.0-27.6 in.
 

Environment

IP class IP31
Humidity 30–90% rH
Maximum operating temperature 50°C / 120°F
Minimum operating temperature 0°C / 32°F
Storage temperature -30 to 70°C / -22°F to 158°F
Approvals/ Safety Compressor protection Software protection + internal in the compressor
RoHs Conformity IEC 62321
Speed-Con- trol Frequency input 5–12 V, max. 8 mA, 0–200 Hz
AEO Thermostat input (Lsw) 198 V–264 V AC, non-isolated
AEO Defrost input (Def) 198 V–264 V AC, non-isolated
RX/TX interface (DWI) 5–12 V, max. 8 mA, 600 baud

Compressor Data

  NLV8.0CN / NLV10CN / NLV12.6CN
 

Compressor

Application LBP/MBP
Evaporating temperature             °C (°F) -40 to 0 (-40 to 32)
Voltage range/frequency           V/Hz 198–270/50/60
Speed range                              rpm 2000–4500

Capacity and Performance Data NLV12.6CN

LBP: ASHRAE 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 428.3 488.9 549.5 603.6 657.6 751.0 844.3 937.7 Evaporation pressure -23.3°C -10°F
Capacity [BTU/h] 1463 1670 1877 2061 2246 2565 2884 3202 Condensing pressure 54.4°C 130°F
Power cons. [W] 237.4 265.7 294.0 322.2 350.4 416.0 481.7 547.3 Liquid temperature 32.2°C 90°F
Current cons. [A] 1.59 1.77 1.95 2.13 2.32 2.70 3.09 3.47 Return gas temp. 32.2°C 90°F
COP [W/W] 1.80 1.84 1.87 1.87 1.88 1.81 1.75 1.71  
EER [BTU/Wh] 6.16 6.28 6.38 6.40 6.41 6.16 5.99 5.85
LBP: CECOMAF 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 320.4 366.0 411.7 452.9 494.1 563.3 632.4 701.6 Evaporation pressure -25°C -13°F
Capacity [BTU/h] 1094 1250 1406 1547 1688 1924 2160 2396 Condensing pressure 55°C 131°F
Power cons. [W] 227.7 254.3 280.9 308.0 335.2 398.3 461.5 524.7 Liquid temperature 55°C 131°F
Current cons. [A] 1.53 1.70 1.86 2.04 2.22 2.59 2.96 3.34 Return gas temp. 32°C 90°F
COP [W/W] 1.41 1.44 1.47 1.47 1.47 1.41 1.37 1.34  
EER [BTU/Wh] 4.81 4.92 5.01 5.02 5.04 4.83 4.68 4.57
LBP: EN12900 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 243.4 273.1 302.8 335.4 367.9 424.0 480.1 536.2 Evaporation pressure -35°C -31°F
Capacity [BTU/h] 831 933 1034 1145 1257 1448 1640 1831 Condensing pressure 40°C 104°F
Power cons. [W] 158.6 173.9 189.2 211.9 234.7 277.3 319.8 362.3 Liquid temperature 40°C 104°F
Current cons. [A] 1.09 1.18 1.28 1.42 1.57 1.84 2.11 2.38 Return gas temp. 20°C 68°F
COP [W/W] 1.54 1.57 1.60 1.58 1.57 1.53 1.50 1.48  
EER [BTU/Wh] 5.24 5.36 5.47 5.40 5.35 5.22 5.13 5.05
MBP: ASHRAE 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 764.3 864.3 964.2 1059 1154 1327 1501 1674 Evaporation pressure -6.7°C 20°F
Capacity [BTU/h] 2610 2952 3293 3617 3942 4533 5125 5717 Condensing pressure 54.4°C 130°F
Power cons. [W] 336.5 379.7 423.0 462.2 501.4 601.9 702.5 803.1 Liquid temperature 46.1°C 115°F
Current cons. [A] 2.23 2.51 2.79 3.04 3.29 3.85 4.40 4.95 Return gas temp. 35°C 95°F
COP [W/W] 2.27 2.28 2.28 2.29 2.30 2.21 2.14 2.08  
EER [BTU/Wh] 7.76 7.77 7.79 7.83 7.86 7.53 7.30 7.12
MBP: CECOMAF 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 607.1 688.6 770.1 844.3 918.6 1056 1193 1330 Evaporation pressure -10°C 14°F
Capacity [BTU/h] 2073 2352 2630 2884 3137 3605 4073 4540 Condensing pressure 55°C 131°F
Power cons. [W] 317.7 359.1 400.4 436.6 472.9 566.4 659.9 753.4 Liquid temperature 55°C 131°F
Current cons. [A] 2.11 2.38 2.64 2.88 3.11 3.63 4.15 4.67 Return gas temp. 32°C 90°F
COP [W/W] 1.91 1.92 1.92 1.93 1.94 1.86 1.81 1.77  
EER [BTU/Wh] 6.53 6.55 6.57 6.60 6.63 6.36 6.17 6.03
MBP: EN12900 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 683.4 765.9 848.4 927.6 1007 1170 1334 1497 Evaporation pressure -10°C 14°F
Capacity [BTU/h] 2334 2616 2897 3168 3438 3997 4555 5113 Condensing pressure 45°C 113°F
Power cons. [W] 291.1 326.2 361.2 395.5 429.8 514.5 599.1 683.8 Liquid temperature 45°C 113°F
Current cons. [A] 1.94 2.17 2.40 2.61 2.83 3.31 3.79 4.28 Return gas temp. 20°C 90°F
COP [W/W] 2.35 2.35 2.35 2.35 2.34 2.28 2.23 2.19  
EER [BTU/Wh] 8.02 8.02 8.02 8.01 8.00 7.77 7.60 7.48

Capacity and Performance Data NLV10CN

LBP: ASHRAE 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 340.3 388.2 436.1 479.0 521.9 597.7 673.5 749.3 Evaporation pressure -23.3°C -10°F
Capacity [BTU/h] 1162 1326 1489 1636 1782 2041 2300 2559 Condensing pressure 54.4°C 130°F
Power cons. [W] 186.1 208.7 231.4 253.5 275.7 322.9 370.1 417.3 Liquid temperature 32.2°C 90°F
Current cons. [A] 1.26 1.41 1.55 1.69 1.83 2.13 2.42 2.71 Return gas temp. 32.2°C 90°F
COP [W/W] 1.83 1.86 1.89 1.89 1.89 1.85 1.82 1.80  
EER [BTU/Wh] 6.25 6.35 6.44 6.45 6.46 6.32 6.22 6.13
LBP: CECOMAF 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 254.6 290.7 326.8 359.5 392.2 448.3 504.4 560.5 Evaporation pressure -25°C -13°F
Capacity [BTU/h] 869 993 1116 1228 1339 1531 1723 1914 Condensing pressure 55°C 131°F
Power cons. [W] 178.7 200.0 221.3 242.6 264.0 309.4 354.8 400.2 Liquid temperature 55°C 131°F
Current cons. [A] 1.22 1.35 1.48 1.62 1.76 2.04 2.32 2.61 Return gas temp. 32°C 90°F
COP [W/W] 1.43 1.45 1.48 1.48 1.49 1.45 1.42 1.40  
EER [BTU/Wh] 4.87 4.96 5.04 5.06 5.07 4.95 4.85 4.78
LBP: EN12900 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 192.8 216.5 240.3 266.2 292.0 332.1 372.2 412.3 Evaporation pressure -35°C -31°F
Capacity [BTU/h] 658 740 821 909 997 1134 1271 1408 Condensing pressure 40°C 104°F
Power cons. [W] 125.5 137.6 149.7 168.1 186.4 222.0 257.6 293.2 Liquid temperature 40°C 104°F
Current cons. [A] 0.88 0.96 1.04 1.15 1.26 1.50 1.74 1.98 Return gas temp. 20°C 68°F
COP [W/W] 1.54 1.57 1.61 1.58 1.57 1.50 1.45 1.41  
EER [BTU/Wh] 5.25 5.37 5.48 5.41 5.35 5.11 4.93 4.80
MBP: ASHRAE 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 606.1 685.7 765.3 840.7 916.0 1063 1210 1357 Evaporation pressure -6.7°C 20°F
Capacity [BTU/h] 2070 2342 2614 2871 3128 3631 4133 4635 Condensing pressure 54.4°C 130°F
Power cons. [W] 260.8 295.0 329.1 360.3 391.6 462.2 532.9 603.5 Liquid temperature 46.1°C 115°F
Current cons. [A] 1.74 1.96 2.18 2.38 2.58 2.99 3.39 3.80 Return gas temp. 35°C 95°F
COP [W/W] 2.32 2.33 2.33 2.33 2.34 2.30 2.27 2.25  
EER [BTU/Wh] 7.94 7.94 7.94 7.97 7.99 7.85 7.76 7.68
MBP: CECOMAF 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 481.7 546.4 611.2 670.1 729.0 845.2 961.3 1077 Evaporation pressure -10°C 14°F
Capacity [BTU/h] 1645 1866 2087 2288 2490 2886 3283 3680 Condensing pressure 55°C 131°F
Power cons. [W] 246.7 279.5 312.2 341.0 369.8 436.0 502.2 568.4 Liquid temperature 55°C 131°F
Current cons. [A] 1.65 1.86 2.07 2.26 2.44 2.83 3.21 3.59 Return gas temp. 32°C 90°F
COP [W/W] 1.95 1.96 1.96 1.965 1.97 1.94 1.94 1.90  
EER [BTU/Wh] 6.67 6.68 6.69 6.71 6.73 6.62 6.54 6.47
MBP: EN12900 230 V, 50/60 Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 543.4 608.4 673.3 736.2 799.1 928.6 1058 1188 Evaporation pressure -10°C 14°F
Capacity [BTU/h] 1856 2078 2300 2514 2729 3171 3614 4057 Condensing pressure 45°C 113°F
Power cons. [W] 226.8 254.8 282.7 309.7 336.8 402.0 467.3 532.5 Liquid temperature 45°C 113°F
Current cons. [A] 1.52 1.70 1.88 2.05 2.23 2.61 3.00 3.38 Return gas temp. 20°C 90°F
COP [W/W] 2.40 2.39 2.38 2.38 2.37 2.31 2.27 2.23  
EER [BTU/Wh] 8.18 8.16 8.13 8.12 8.10 7.89 7.73 7.62

Capacity and Performance Data NLV8.0CN

LBP: ASHRAE 230 V, 50/60Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 271.9 310.4 348.9 383.2 417.5 464.3 511.1 557.9 Evaporation pressure -23.3°C -10°F
Capacity [BTU/h] 929 1060 1192 1309 1426 1586 1745 1905 Condensing pressure 54.4°C 130°F
Power cons. [W] 147.7 165.8 184.0 201.7 219.5 252.1 284.7 317.4 Liquid temperature 32.2°C 90°F
Current cons. [A] 1.02 1.13 1.25 1.36 1.47 1.69 1.90 2.12 Return gas temp. 32.2°C 90°F
COP [W/W] 1.84 1.87 1.90 1.90 1.90 1.84 1.80 1.76  
EER [BTU/Wh] 6.29 6.39 6.48 6.49 6.50 6.29 6.13 6.00
LBP: CECOMAF 230 V, 50/60Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 203.4 232.4 261.4 287.6 313.7 347.4 381.0 414.7 Evaporation pressure -25°C -13°F
Capacity [BTU/h] 695 794 893 982 1071 1186 1301 1416 Condensing pressure 55°C 131°F
Power cons. [W] 141.9 159.0 176.0 193.2 210.3 241.9 273.4 305.0 Liquid temperature 55°C 131°F
Current cons. [A] 0.98 1.09 1.20 1.31 1.41 1.62 1.84 2.05 Return gas temp. 32°C 90°F
COP [W/W] 1.43 1.46 1.49 1.49 1.49 1.44 1.39 1.36  
EER [BTU/Wh] 4.89 4.99 5.07 5.08 5.10 4.91 4.76 4.64
LBP: EN12900 230 V, 50/60Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 154.6 173.4 192.2 212.9 233.6 261.2 288.7 316.3 Evaporation pressure -35°C -31°F
Capacity [BTU/h] 528 592 657 727 798 892 986 1080 Condensing pressure 40°C 104°F
Power cons. [W] 100.8 110.3 119.8 135.0 150.2 175.0 199.7 224.5 Liquid temperature 40°C 104°F
Current cons. [A] 0.72 0.79 0.85 0.94 1.03 1.21 1.39 1.57 Return gas temp. 20°C 68°F
COP [W/W] 1.53 1.57 1.61 1.58 1.56 1.49 1.45 1.41  
EER [BTU/Wh] 5.24 5.37 5.48 5.39 5.31 5.10 4.94 4.81
MBP: ASHRAE 230 V, 50/60Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 485.3 548.7 612.2 672.5 732.8 838.1 943.4 1049 Evaporation pressure -6.7°C 20°F
Capacity [BTU/h] 1657 1874 2091 2297 2503 2862 3222 3581 Condensing pressure 54.4°C 130°F
Power cons. [W] 205.5 233.0 260.5 285.3 310.2 356.7 403.3 449.8 Liquid temperature 46.1°C 115°F
Current cons. [A] 1.39 1.56 1.73 1.89 2.06 2.34 2.62 2.90 Return gas temp. 35°C 95°F
COP [W/W] 2.36 2.36 2.35 2.36 2.36 2.35 2.34 2.33  
EER [BTU/Wh] 8.06 8.04 8.03 8.05 8.07 8.02 7.99 7.96
MBP: CECOMAF 230 V, 50/60Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 385.5 437.2 488.9 536.1 583.2 664.4 745.6 826.8 Evaporation pressure -10°C 14°F
Capacity [BTU/h] 1316 1493 1670 1831 1992 2269 2546 2824 Condensing pressure 55°C 131°F
Power cons. [W] 194.7 221.0 247.4 270.3 293.2 337.3 381.4 425.5 Liquid temperature 55°C 131°F
Current cons. [A] 1.32 1.48 1.65 1.80 1.95 2.22 2.49 2.75 Return gas temp. 32°C 90°F
COP [W/W] 1.98 1.98 1.98 1.98 1.99 1.97 1.96 1.94  
EER [BTU/Wh] 6.76 6.75 6.75 6.77 6.79 6.73 6.68 6.64
MBP: EN12900 230 V, 50/60Hz, fan cooling F2  
Speed (rpm) 2000 2250 2500 2750 3000 3500 4000 4500 Test conditions
Capacity [W] 433.9 486.3 538.7 589.0 639.2 739.7 840.2 940.6 Evaporation pressure -10°C 14°F
Capacity [BTU/h] 1482 1661 1840 2011 2183 2526 2869 3212 Condensing pressure 45°C 113°F
Power cons. [W] 179.4 201.9 224.4 245.9 267.4 312.6 357.7 402.8 Liquid temperature 45°C 113°F
Current cons. [A] 1.22 1.36 1.50 1.64 1.78 2.06 2.34 2.62 Return gas temp. 20°C 90°F
COP [W/W] 2.42 2.41 2.40 2.40 2.39 2.37 2.35 2.34  
EER [BTU/Wh] 8.26 8.23 8.20 8.18 8.16 8.08 8.02 7.98

DIMENSIONS

Compressor Dimensions NLV8.0CN | NLV10CN | NLV12.6CN
Height mm (in.) A

B

203

197

Suction connector location/I.D. mm (in.) | angle

material | seal

C 8.2 | 15°

Copper | Rubber plug

Process connector location/I.D. mm (in.) | angle

material | seal

D 6.2 | 25°

Copper | Rubber plug

Discharge connector location/I.D. mm (in.) | angle

material | seal

E 6.2 | 21°

Copper | Rubber plug

Connector tolerance I.D. mm  

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-19

ORDERING

  Item Code No. Comment
Controller Electronic controller (Core Functions), 220–240 V AC 105N4120 single unit
Compressor/Accessories NLV8.0CN compressor 105H7813 compressor w/ metric connectors
NLV10CN compressor 105H7013 compressor w/ metric connectors
NLV12.6CN compressor 105H6313 compressor w/ metric connectors
Cover for the compressor 103N2008  
Bolt joint for one compressor 118-1917  
Bolt joint in quantities 118-1918  
Snap-on in quantities 118-1919  

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-20

SECOP GROUP: AROUND THE WORLD

  • 12 international partners for advanced developments
  • 33 laboratories located in Germany, Slovakia, China, the U.S.A., and Turkey
  • 150+ R&D engineers and technicians
  • 400+ patents globally
  • 50+ countries with customer support

Secop is the expert for advanced hermetic compressor technologies and cooling solutions in commercial refrigeration. We develop high performance stationary and mobile cooling solutions for leading international commercial refrigeration manufacturers and are the first choice when it comes to leading hermetic compressors and electronic controls for refrigeration solutions for light commercial and DC-powered applications.
Secop was formerly known as Danfoss Compressors and is one of the founding fathers of modern compressor technology, with years of experience that go back to the beginning of the 1950s.

Secop-105N4120-NLV-CN-Core-Functions-Controllers-Compressors-FIG-21

CONTACT

  • Secop GmbH · Lise-Meitner-Str. 29 · 24941 Flensburg, Germany · Tel: +49 461 4941 0 · www.secop.com

Secop accepts no responsibility for possible errors in catalogs, brochures, and other printed material. Secop reserves the right to alter its products without notice. This also applies to products already on order, provided that such alterations can be made without subsequent changes being necessary to specifications already agreed. All trademarks in this material are the property of the respective companies. Secop and the Secop logotype are trademarks of Secop GmbH. All rights reserved.

FAQ

  • Q: Can I install the Core Functions Controller myself?
    • A: Installation should only be done by trained personnel to ensure proper setup and avoid any risks.
  • Q: How long should I wait before accessing terminals after disconnecting from power?
    • A: Wait for at least 30 seconds after disconnecting from power before accessing terminals to ensure safety.
  • Q: What is the maximum cable length allowed for signal connections?
    • A: The maximum cable length for signal connections should not exceed 3 meters to maintain proper functionality.