NB1L Residual Current Devices
Instructions
NB1L Residual Current Devices
Assembled with NB1, NB1L can offer leakage current protection for human body,and insulation fault protection for electrical equipment.
Technical data -Standard:IEC/EN 61009-1
-Voltage:230VAC/400VAC
-Frequency:50/60Hz
-Poles:1P+N、2P、3P、3P+N、4P
-Protection Degree:IP20
Operating procedure
- Remove the clip of NB1
- Install the axis on NB1
- Assembly
- Torque=2~2.5N·m
Testing
2.1 Testing of the test button
2.2 Testing of the operating current
Rated residual operating current(A) | Testing range mA) |
0.03 | >15~30 |
0.1 | >50~100 |
0.3 | >150~300 |
Wiring
Selection of the wiring cable:
Rated current (A) | Nominal section of the copper wiring cable (mm2) |
C13 | 1~2. 5 |
13~ 16 | 2. 5″~4 |
161~25 | 4″-/6 |
25~32 | 64~10 |
32″~’50 | 10~16 |
50″~’63 | 161~25 |
SCHRACK TEC HN IK GM BH
Seybelgasse 13,A – 123 0 Wien, TELEFON +43 1/86 6 85-0
E-MAIL info@schrack.com,
INTERNET www.schrack.at