NB1L Residual Current Devices

Assembled with NB1, NB1L can offer leakage current protection for human body,and insulation fault protection for electrical equipment.
Technical data -Standard:IEC/EN 61009-1
-Voltage:230VAC/400VAC
-Frequency:50/60Hz
-Poles:1P+N、2P、3P、3P+N、4P
-Protection Degree:IP20

Operating procedure

  1. Remove the clip of NB1SCHRACK TECHNIK NB1L Residual Current Devices - Operating
  2. Install the axis on NB1SCHRACK TECHNIK NB1L Residual Current Devices - Operating 1
  3. AssemblySCHRACK TECHNIK NB1L Residual Current Devices - Operating 2
  4. Torque=2~2.5N·mSCHRACK TECHNIK NB1L Residual Current Devices - Operating 3

Testing

2.1 Testing of the test button
2.2 Testing of the operating current

Rated  residual operating current(A) Testing range mA)
0.03 >15~30
0.1 >50~100
0.3 >150~300

Wiring

Selection of the wiring cable:

Rated current (A) Nominal section of the copper wiring cable (mm2)
C13 1~2. 5
13~ 16 2. 5″~4
161~25 4″-/6
25~32 64~10
32″~’50 10~16
50″~’63 161~25