ATV340U15N4E Variable Speed Drive
“
Specifications:
- Model: ATV340U15N4E
- Power: 1.5kW / 2HP
- Voltage: 380/480V
Product Usage Instructions:
1. Download the Manuals
To carry out installation and commissioning, download the
following manuals from www.schneider-electric.com:
- The ATV340 Installation manual (NVE61069)
- The ATV340 Programming manual (NVE61643)
2. Verify the Delivery of the Drive
Follow the safety precautions provided to avoid electric shock,
explosion, or arc flash. Ensure all power sources are disconnected
and labeled properly before proceeding.
3. Verify The Supply Mains Compatibility
Ensure the supply mains are compatible with the product
specifications provided on www.schneider-electric.com.
4. Mount The Drive Vertically
Mount the drive vertically as per the specified dimensions for
your specific model.
5. Connect The Drive: Power
Connect the drive to the power source according to the
specifications provided in the installation manual to prevent
hazards like fire or electric shock.
6. Connect The Drive: Control
Follow the provided steps to connect and start the drive using
SoMove software and a USB to RS485 converter.
7. Simply Start
To access the [Simply Start] menu:
- Download and Install SoMove FDT and Altivar 340 DTM from
www.schneider-electric.com. - Connect to the drive using a USB to RS485 converter.
- Power up the drive and access the [Simply Start] menu through
the DTM based PC software.
Frequently Asked Questions (FAQ):
Q: What should I do if I detect any damage to the product?
A: Contact your local Schneider Electric sales office
immediately if you detect any damage to the product or
accessories.
“`
ENGLISH
Getting Started With ATV340
1 Download the manuals
NVE3764301
You must have detailed information to be able to carry out the installation and commissioning. This information can be found in the following manuals that can be downloaded on www.schneider-electric.com. – The ATV340 Installation manual (NVE61069) – The ATV340 Programming manual (NVE61643)
2 Verify the delivery of the drive
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
· Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment, repair and maintenance must be performed by qualified personnel.
· The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to grounding of all equipment.
· Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use only electrically insulated tools.
· Do not touch unshielded components or terminals with voltage present. · Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system, block the motor
shaft to prevent rotation. · AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of the motor
cable. · Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals. · Before performing work on the drive system:
– Disconnect all power, including external control power that may be present. – Place a “Do Not Turn On” label on all power switches. – Lock all power switches in the open position. – Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the absence of DC bus
voltage that can exceed 800 Vdc. – Measure the voltage on the DC bus between the DC bus terminals (PA/+, PC/-) using a properly rated voltmeter to verify that
the voltage is < 42 Vdc. – If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative. · Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Information below is designed to use single drive connected to single asynchronous motor with a shielded motor cable length less than 20 m (65 ft).
· Unpack the drive and verify that it has not been damaged. Damaged products or accessories may cause electric shock or unanticipated equipment operation.
DANGER
ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION
Do not use damaged products or accessories. Failure to follow these instructions will result in death or serious injury. Contact your local Schneider Electric sales office if you detect any damage whatsoever.
· Verify that the drive catalog number printed on the label is the same as that on the delivery note corresponding to the purchase order.
ATV340U15N4E 8B 1630 4XXXXX
1.5kW-2HP-380/480V
· Write the drive Model: – Catalog number: ____________________ – Serial Number: _______________________
3 Verify The Supply Mains Compatibility
· Verify that the supply mains is compatible with the drive. Drive range: ATV340pppN4p = 380/480 V three-phase
www.schneider-electric.com
1/4
NVE37643 – 09/2016
4 Mount The Drive Vertically
X 1
Catalog Number ATV340U07N4p…ATV340D22N4p
X1
100mm (3.9 in.)
X2
100mm (3.9 in.)
X3
60mm (2.36 in.)
ATV340D30N4E…ATV340D75N4E
100mm (3.9 in.)
100mm (3.9 in.)
10mm (0.39 in.)
X 2
Minimum values corresponding to thermal contrainst for a surrounding air temperature up to 50°C (122°F). For other thermal conditions, or installation use cases (side by side, flush mounting …) see ATV340 Installation Manual (NVE61069) on www.schneider-electric.com.
X3
Example given for ATV340U40N4.
5 Connect The Drive: Power
380/480 V
· Connect the drive to ground · Verify circuit breaker rating or fuse rating. (See SCCR annex
NVE37641) · Verify that the nominal motor voltage is compatible with the
drive voltage. Nominal motor voltage ______volts. · Connect the drive to the motor (U / V / W / PE). · Connect the drive to the supply mains (L1 / L2 / L3 / PE).
OR
OR
OR Asynchronous motor www.schneider-electric.com
… N·m … lb.in
See ATV340 Installation Manual (NVE61069) on www.schneider-electric.com.
DANGER
HAZARD OF FIRE OR ELECTRIC SHOCK Wire cross sections and tightening torques must comply with the specifications provided in the installation manual. Failure to follow these instructions will result in death or serious injury.
2/4
NVE37643 – 09/2016
6 Connect The Drive: Control
· Connect the reference frequency AI1:
ATV340U07N4p…ATV340D22N4p: · Connect the command DI1
· Connect the STO_A and STO_B inputs
ATV340D30N4E…ATV340D75N4E: · Connect the command DI1
+10 v AI 1 COM DI1 STO_A
STO_B DISUP 24V DI1 24V
1…10 k
SK
SRC
EXT
7 [Simply Start]
Steps to follow to access [Simply Start]: 7.1 Download and Install SoMove FDT and Altivar 340 DTM on www.schneider-electric.com.
7.2 Connect to the drive with SoMove using a USB to RS485 converter (TCSMCNAM3M002P) between PC and drive:
OR
R1A R1B R1C R2A R2C R3A R3C
STOA P24
STOB 0V
24V DI 1
10V DI 2
AI 1 DI 3
COM DI 4
AI 2 DI 5
AI 3 DI 6
AQ1 DI 7
AQ2 DI 8
COM 24V
DQDQ+
CN7
Modbus
7.3 Power up the drive: – Verify that digital input is not active (DI1, see step 6 diagram) – Apply power to the drive
7.4 Access [Simply Start] menu: – by clicking on Parameters List tab on DTM based PC software.
– For ATV340pppN4E products, [Simply Start]
OR
menu can also be accessed using the embedded Webserver.
For more information, refer to the ATV340
Programming Manual (NVE61643).
www.schneider-electric.com
3/4
NVE37643 – 09/2016
8 Set motor parameters for asynchronous motor
· Refer to the motor Nameplate to set the following.
Menu
Parameter
Factory setting
[Simply Start] [Motor Standard] bFr: Standard motor frequency (Hz) [Nominal Motor Power] nPr: Nominal motor power on motor nameplate (KW) [Nom Motor Voltage] UnS: Nominal motor voltage on motor nameplate (Vac) [Nom Motor Current] nCr: Nominal motor current on motor nameplate (A) [Nominal Motor Freq] FrS: Nominal motor frequency on motor nameplate (Hz) [Nominal Motor Speed] nSP: Nominal motor speed on motor nameplate (rpm) [2/3-Wire Control] tCC: Command control by 2 wire or 3 wire control [Max Frequency] tfr: Maximum motor frequency (Hz) [Mot. therm. current] ItH: Motor thermal current on motor nameplate (A) [50Hz IEC] 50 drive rating drive rating drive rating 50 drive rating 2C 60 drive ratingFor synchronous or reluctance motor, refer to the ATV340 Programming Manual (NVE61643) on www.schneider-electric.com.
Customer setting
9 Perform a Motor [Autotuning]
WARNING
UNEXPECTED MOVEMENT Autotuning moves the motor in order to tune the control loops. · Only start the system if there are no persons or obstructions in the zone of operation Failure to follow these instructions can result in death, serious injury or equipment damage.
During [Autotuning], the motor makes small movement. Noise development and oscillations of the system are normal.
10 Set Basic Parameters
Menu [Simply Start]
Description [Acceleration] ACC: Acceleration time (s) [Deceleration] dEC: Deceleration time (s) [Low speed] LSP: Motor frequency at minimum reference (Hz) [High speed] HSP: Motor frequency at maximum reference (Hz)
Factory setting 3.0 3.0 0 50
Customer setting
11 Start/Stop The Motor
Set the [Reference frequency] with the potentiometer.
Activate DI1 to start the motor Deactivate DI1 to stop the motor
ATV340···
+10 v AI 1 COM DI1 DISUP 24V
1…10 k
DI1: forward
www.schneider-electric.com
4/4
NVE37643 – 09/2016
Documents / Resources
![]() |