SAVANT 009-2402-01 Power Storage App
Document Number: 009-2402-01
Document Date: June 2025
- This document guides the installer through the process of commissioning a Savant Power Storage System using the Savant Power Storage (SPS) app.
- This document supports the Savant Power Storage (SPS) app version 3.0.5 and higher and Savant Power Storage inverters running firmware version 1.4.8 and higher.
IMPORTANT: As part of initial system deployment, installers must contact Savant Support for assistance with Power Storage Inverter firmware upgrade.
App Setup
Download App
The Savant Power Storage inverter app can be downloaded directly from the Apple App Store or Google Play Store. Search for Savant Power Storage or scan the QR Codes to the right.
Savant Power Storage App (Apple App Store)
Savant Power Storage App (Google Play Store)
Create Account
IMPORTANT: This guide assumes the first person to begin deployment and access the Savant Power Storage Inverter using the Savant Power Storage app is the installer.
Upon downloading the app, new users will need to create an account.
By default, users are given limited permissions within the app. Contact Savant Support to obtain installer level privileges, which enable full configuration capabilities when deploying a system.
NOTES:
- Additional accounts created may not have sufficient permissions to be able to access all settings listed in this guide.
- A maximum of 5 accounts can be associated to a Savant Power Storage system.
HELPFUL TIP: Savant recommends configuring the installer app account before traveling to site to avoid downtime while waiting for account privileges to be granted.
Add Device
Each Savant Power Storage inverter must be added as a device within the Savant Power Storage inverter app.
- WIFI ONLY: Toggle The Cloud icon to Local Area Network
.
- Select Add Device.
- Allow the SPS app camera permissions.
- Scan serial number QR Code on the side of the Power Storage Inverter.
OR
Enter Device Serial Number (S/N) located on the right side and select Submit.
Network Configuration
The Savant Power Storage System requires a connection from the inverter to a local area network with access to the internet to recieve Over-The-Air (OTA) updates.
- Start the Savant Power Storage System according to the system boot sequence in the installation manual.
- Wait until the network indicator on the inverter turns green.
- Follow the Wired section below or the Wireless section on the next page to configure the relevant network connection type.
Wired (Recommended)
- Connect a LAN port of the router to the network port of the Savant Power Storage inverter using an ethernet cable.
- Scan the QR Code on the right side of the Savant Power Storage inverter.
- Select Wired/Other.
Savant Power Storage Inverter
Wireless (Not Recommended)
Press the RESET button on the left side of the system for 5 seconds until indicator flashes red to reset the system before beginning wireless configuration.
- Select Wi-Fi
- Toggle Local for Local Areal Network credentials or Remote for Remote Access network credentials
- Enter network credentials
- Select Save
- Minimize the Savant Power Storage app
- Connect the mobile device’s Wi-Fi to the network titled ICAN-xxxxx
- Reopen the SPS app and select Submit
- The inverter serial number appears on the Associated Devices screen
Associated Devices Overview
Associated Devices displays all Savant Power Storage systems, sorted by inverter, the account has access to. The table below describes the information displayed on this screen.
Setting | Description |
Ⓐ More | Access more information about the Savant Power Storage inverter app, including:
|
Ⓑ Profiles |
|
Ⓒ Connection Mode | Toggle between connection modes:
|
Ⓓ Refresh | Re-discover inverters |
Ⓔ Search Bar | Search through inverters by name or serial number |
Ⓕ Device ID | Inverter Serial Number |
Ⓖ Connection | Inverter connection status |
Ⓗ Battery SOC | Battery State of Charge (SOC) |
Ⓘ Battery Status | Charging, discharging, or standby |
Ⓙ Group | Custom grouping of systems |
Ⓚ Add Device | Add a Savant Power Storage inverter |
Power Overview
The Power Overview screen displays real time power import and export statistics sorted by source.
IMPORTANT: All information and settings listed here are relevant to the individual inverter.
Setting | Description |
Ⓐ Device Name | Name of the inverter |
Ⓑ Solar Production (DC) | Realtime solar production |
Ⓒ Grid Consumption | Total energy consumption of all loads from the grid in kW |
Ⓓ Current Battery State | Charging or Discharging – Whether the battery is currently charging or discharging |
State of Charge – Remaining battery capacity in percentage | |
Time – Approximate time left until battery reaches 0% SOC Note: this may change depending on load conditions |
|
V & A – Battery voltage and amperage | |
Ⓔ Load Consumption | Total energy consumption for all loads in kW |
Ⓕ Settings | Savant Power Storage Inverter Settings![]() |
Ⓖ Generator Input | Realtime generator power production in kW |
Ⓗ Fill Up | Enable to manually force the Savant Power Storage inverter to charge the batteries to 100%![]() Charging the battery using grid power may be prohibited |
System Information
Device Information
To access Device Information, navigate to Settings > System Information > Device Information. Device Information contains important information such as the following:
- Device Name
- Time zone
- Serial number
- IP Address
- Battery Cycles
IMPORTANT: Device Name and Time Zone must both be set before continuing.
Notifications
The Savant Power Storage app monitors the system status and reports changes in behaviors as Notifications. Notifications are divided into Active and History sub menus.
- Toggle to Active to display all active real time notifications.
- Toggle to History to display all changes in behavior in reverse chronological order. Scroll down to see older notifications.
Energy Usage
Energy Usage displays system production and consumption data for all power sources connected to the Savant Power Storage inverter.
Setting | Description |
Ⓐ Energy Usage Graph | All energy sources and consumption over time. Toggle individual power source visibility on the energy usage graph using Power Source icons. |
Ⓑ Max Demand | Highest total load consumption recorded, in kW |
Ⓒ Daily Usage | Average total load consumption per day in kWh |
Ⓓ Summary | Detailed total and energy transactions for all power sources |
Ⓔ Expand | Click the ![]() |
Enabling Parallel System Configuration allows multiple Savant Power Storage Inverters to function in parallel. A parallel system always has one Leader inverter and may have several Follower inverters. Shared Battery configuration allows two inverters to share a single battery stack. To access this menu, navigate to Settings > Parallel & Shared Battery. Then configure according to inverter hierarchy as described below.
IMPORTANT NOTES:
- Parallel & Shared Battery settings are not translated to other inverters automatically. Complete these steps for each inverter in sequence.
- Inverters must be connected to each other using the Parallel System port on the left side with termination connectors at each end.
Leader Inverter
Program the leader inverter first. It is most commonly the first or last inverter in the parallel chain, and is connected to the acral meter. See the relevant Savant Power Storage (20/50) Installation Manual for more details.
- Enable Parallel System.
- Set the Control Mode to Leader. This will set the COMM Address to 1.
- Set the COMM Mode to Wired.
- Set the Total Inverter Quantity to the number of paralleled inverters.
- If two Savant Power Storage inverters share a battery stack, enable Shared Battery Mode. Shared Battery Mode automatically controls the rate at which the inverters will charge the shared battery.
Refer to the table below for charge rates per-inverter:
Power Storage 20 | Power Storage 50 | |
One Inverter per Battery Stack | 6.5kW | 25kW |
Two Inverters per Battery Stack | 3.25kW | 12.5kW |
Once all follower units have been configured, the leader unit will display each configured follower at the bottom of the screen.
Follower Inverters
- Enable Parallel System.
- Set the Control Mode to Follower. This will set the COMM Address to 2 or higher, according to the number of inverters in parallel. Each inverter must have a unique COMM address.
NOTE: When using Shared Battery Mode in parallel, the COMM Address should increment in pairs; i.e. inverters 1&2 share one battery stack, 3&4 share the second battery stack, etc. - Set the COMM Mode to Wired.
- Set the Total Inverter Quantity to the number of paralleled inverters.
- If two Savant Power Storage inverter units share a battery stack, enable Shared Battery Mode. This mode controls the charge rate if the inverter shares the connected battery stack with another inverter.
Power Storage 20 | Power Storage 50 | |
One Inverter per Battery Stack | 6.5kW | 25kW |
Two Inverters per Battery Stack | 3.25kW | 12.5kW |
Once all follower units have been configured, the leader unit will display each configured follower at the bottom of the screen.
Battery Operation
Battery Operation is used to configure system operating parameters according to site usage goals and utility rate plans. From the Power Overview menu, select Settings > Battery Operation.
IMPORTANT: The Power Storage System will use the following priority to power connected loads.
The system will prioritize using solar to offset loads before charging the battery:
Powering Loads
- DC Coupled Solar
- Battery Power (until Backup Reserved is met)
- Utility Power
NOTE: If sufficient solar is available, batteries will charge to 100% before exporting (if applicable), and discharge to the Backup Reserved State of Charge.
Setting | Description |
Ⓐ Power Modes | See Power Modes. |
Ⓑ Backup Reserved SOC | User-configured minimum State of Charge (SOC) the Savant Power Storage System will discharge to when operating on grid. This controls the following behavior:
NOTE: Certain features, such as Storm Watch, disregard the Backup Reserved SOC setting and will prioritize charging the battery to 100%. |
Ⓒ Low Battery Alarm SOC | The battery SOC at which the Power Overview Current Battery State color will change to indicate low battery charge. |
Ⓓ Time of Use Based | Configure system Time of Use (ToU) settings for battery use age. If the desired rate plan is not listed, multiple generic options exist under the OTHER category. Contact Savant Support for assistance if setting a ToU plan. |
Ⓔ Schedules | Configure battery use according to schedules. Schedules override TOU settings. If none of the options meet system requirements, contact Savant Support to build a custom schedule using the Schedules tool. |
IMPORTANT!: Contact Savant Support if the site requires more advanced charging and discharging logic.
Power Modes
Power Modes control inverter and battery behavior while on grid to optimize efficiency and cost savings.
Mode | Description |
Self Sufficiency | Prioritizes powering backed up loads with solar and battery. If battery falls below Back up Reserved SOC, loads are offset by utility power. Battery will charge when solar production is greater than backed up loads. Excess DC coupled solar will not be sold back to grid. NOTE: Self Sufficiency Mode can be used with an Acral meter to power non backed up loads |
Meter Zero | Prioritizes powering backed up and non backed up loads with solar and battery. If battery falls below Back up Reserved SoC, loads are offset by utility power. Battery will charge when solar production is greater than backed up loads. Excess DC coupled solar will not be sold back to grid. AC coupled solar can not be controlled in Meter Zero and may be exported to the grid. IMPORTANT: Requires the use of an Acral AGF-AE-D/200 meter. See the applicable Savant Power Storage 20/50 Installation Manual for further instruction. |
Excess Solar to Grid | Prioritizes powering backed up loads with solar and battery. If battery falls below Back up Reserved SoC, loads are offset by utility power. When DC coupled solar production exceeds demand of loads and battery consumption, excess energy is exported to the grid. |
PARTIAL HOME BACKUP / SINGLE UNIT APPLICATION
WHOLE HOME BACKUP / STACKED APPLICATION
Power Sources
Enable the power sources under the Settings > Connected Power Sources submenu matching the power sources installed onsite.
IMPORTANT: Read and follow all relevant documentation and installation guides before continuing.
DC Coupled Solar
DC Coupled Solar settings are configured under Settings > Connected Power Sources > DC Coupled Solar.
Setting | Description |
Ⓐ MPPT Mode | Choose which MPPTs are used |
Ⓑ AFCI Module | Toggle to indicate whether AFCI Modules are installed NOTE: Refer to relevant installation manual for further information on AFCI operation. |
Ⓒ RUN Indicator Control | When disabled, the inverter RUN indicator will flash when PV is undervoltage or offline. NOTE: It is recommended that this setting remain enabled. |
Generator Port Control
Navigate to Settings > Connected Power Sources > Generator Control to configure generator settings.
IMPORTANT: Refer to the relevant Savant Power Storage 20/50 Installation Guide for instructions on wiring a generator before continuing. All generator manufacturer requirements must be met during the installation process.
Setting | Description |
Ⓐ Maximum Power | The maximum output of the generator based on continuous current draw from generator, up to 100A |
Ⓑ Starting SOC (Automatic Only) | The battery state of charge at which the Savant Power System commands the generator to start |
Ⓒ Stopping SOC (Automatic Only) | The battery state of charge at which the Savant Power System commands the generator to stop |
Ⓓ Generator Start Type (Read Only) | The Savant Power Storage inverter supports 2-wire start generators. See the applicable Savant Power Storage Inverter Installation Guide for more information |
Ⓔ Control | Automatic – (Off Grid Only) Automatically send start and stop commands to the generator based on battery SOC. |
Manual – (Off Grid Only) Manually start the generator. For diagnostic purposes only. |
IMPORTANT NOTES:
- Do not exceed the output power rated for the generator.
- Follow all generator manufacturer’s guidelines.
- Generator operation is only supported for off grid use.
- Adjusting the SOC setting in this menu will impact and automatically adjust the Backup Reserved SOC parameter in the Battery Operation menu – the Backup Reserved SOC must be higher than or equal to the Generator Starting SOC.
AC Coupled Solar Control
IMPORTANT!: Complete all AC solar wiring listed in the applicable Savant Power Storage Installation Guide before enabling AC Coupled Solar Control.
Configure the fields below to control AC solar behavior.
Setting | Description |
Ⓐ Load or Generator | Select Load or Generator port for AC Solar input NOTE: AC coupled solar is only supported on the Load port in single-inverter installations |
Ⓑ Enable | Enable or Disable AC solar input |
Ⓒ Starting SOC | The SOC threshold the battery must reach before the inverter starts charging the battery using AC solar |
Ⓓ Stopping SOC | The SOC threshold the battery must reach before the inverter stops charging the battery using AC solar |
IMPORTANT NOTES:
- The inverter cannot control export of AC coupled solar power to the grid.
- The Starting SOC is always at least 5% lower than the Stopping SOC.
- Both the AC Coupled Solar Control Starting & Stopping SOC and the Generator Starting and Stopping SOC override the Battery Operation Backup Reserved SOC when enabled.
Smart Rectifier Control
For system designs incorporating smart rectifier control, contact Savant Support for assistance before proceeding.
Interconnection Settings
Grid Settings
- Use the left and right arrow to select the appropriate interconnection requirements per guidance from local utility.
- Adjust voltage and frequency ride throughs by selecting the parameter requiring adjustment. Only underlined settings may be configured.
IMPORTANT NOTES:
- Utility grid operators may require interconnection settings unique to the site. Refer to local interconnection guidelines to confirm the appropriate settings.
- Only qualified personnel should edit Interconnection settings.
- Incorrect interconnection settings could void Permission To Operate (PTO) from local utilities.
- The inverter must be restarted after changing any parameter.
- If none of the settings provided match the configuration requested by a utility, contact to Savant Support.
Power Control Systems (PCS) Settings
Setting | Description |
Ⓐ Max Grid Input Power | Maximum load support when on grid. Setting to 24000W is highly recommended. If the system was previously configured with a value of less than 24000W, contact Savant Support.![]() |
Ⓑ Max Grid Output Power | Maximum system export rate to grid in W![]() |
Ⓒ Voltage Drop Ride Through Time | Time the system will wait before switching off grid. In locations with larger voltage fluctuations, it is recommended to increase the Ride Through Time. Check with local utility before making modifications. Recommended setting: 4ms |
Ⓓ Seamless Switching | Optimizes transfer time when switching off grid. Enabling this setting is recommended. |
IMPORTANT: Settings must be uniform across all parallel inverters.
Panel Limit Mode
In Panel Limit Mode, the inverter continuously monitors the amperage on the main breaker bus bar, comparing the PCS import/export with the main breaker. Using this information, the inverter automatically enters Standby mode and ceases exporting power from the grid terminal if one of the following conditions are met:
- The sum of the grid current and inverter discharge current exceeds the Panel Limit setpoint.
The software requires the total current on the load center bus to stay below 75% of the main breaker rating for 5 minutes before the Inverter is allowed to discharge. - The total grid current reaches the Panel Limit setpoint.
- Standby mode reduces the total amount of load on the load center by a factor of the Battery Monitoring System (BMS) minus maximum charge rate. The default is 6.5kW / 26A @240V.
- The upstream power meter must read a current level below 75% of the main breaker size minus BMS Charge Rate for 5 minutes before the inverter will charge from the grid again.
- The inverter loses communication with the power meter – this causes the inverter to enter Standby mode as a failsafe, and generates an alarm condition in the SPS app.
For further details on Panel Limit Mode, refer to the Panel Limit Feature support article.
Setting | Description |
Ⓐ Panel Limit Mode | Toggle Panel Limit mode |
Ⓑ Panel Amperage Rating | Amperage rating of the main breaker panel or the rating of the closest upstream over-protection device feeding the monitored & controlled panel bussing. A 100A Main Breaker Panelboard has a 100A Panel Amperage Rating |
Ⓒ Panel limit setpoint | 80% of the Panel Amperage Rating value and the threshold that triggers the inverter to enter Standby mode |
IMPORTANT: Panel Limit Mode is intended only for installations where no loads are backed up. Contact Savant Support for design assistance, further information, or questions regarding the use of this mode.
Important Notice
Disclaimer
Savant Systems, Inc. reserves the right to change product specifications without notice, therefore, the information presented herein shall not be construed as a commitment or warranty.
Savant Systems, Inc. shall not be liable for any technical or editorial errors or omissions contained herein or for incidental or consequential damages resulting from the performance, furnishing, reliance on, or use of this material.
Patents
Certain equipment and software described in this document is protected by issued and pending U.S. and foreign patents.
All products and services are trademarks or registered trademarks of their respective manufacturer.
Copyright
This document contains confidential and proprietary information protected by copyright. All rights reserved. Copying or other reproduction of all or parts of this document is prohibited without the permission of Savant Systems.
Trademarks
© 2025 Savant Systems, Inc. All rights reserved. Savant, Savant app, Savant Power Storage (SPS) app, Savant Power & Light (SP&L) app, Savant Host, Savant Power Director, Cync, and the Savant logo are trademarks of Savant Systems, Inc.
GE, GE monogram, and C by GE are trademarks of General Electric Company used under license. Air Play, Apple, AirPort Express, AirPort Extreme, Apple TV, Apple Remote Desktop, FireWire, iMac, iTunes, iPad, iPad mini, iPad Air, iPhone, MacBook, Mac and OS X are trademarks or trade names of Apple Inc. iOS is a trademark of Cisco®. Android, Google, Google Play, and other Google marks are trademarks of Google, Inc. Wi-Fi is a registered trademark of the Wi-Fi Alliance®. The WiSA logo is a trademark or registered trademark of WiSA, LLC in the United States and other countries. HDMI® is a trademark of HDMI Licensing, LLC. Luxul is a registered trademark of Luxul Wireless. NETGEAR®, the NETGEAR Logo and Pro SAFE are trademarks of NETGEAR, Inc. Extreme™ is a trademark of Extreme Networks, Inc.
The Lutron logo, and Lutron are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the U.S. and/or other countries.
All other brand names, product names, and trademarks are the property of their respective owners.
Technical and Sales Support
Savant Systems, Inc is dedicated to providing prompt and effective support in a timely and efficient manner.
- To contact Savant Support, access the Savant Customer Community and enter a support Case ticket.
- To contact Savant Sales, visit Savant.com and select Contact Us to locate a local sales representative in your area.
Customer Support
Savant Power Storage App Setup Guide Copyright 2025 Savant Systems, Inc 009-2402-01 | 060425