SANHUA logo

SEC series EEV Controller
Manual/Installation Instructions

SANHUA SEC Series EEV Controller

SEC Series EEV Controller

CAUTIONS

  1. This product may cause an electric shock in handling. Please do not attempt to open it with power turned on.
  2. This product should be installed in a place fixed secured by a rack or panel.
  3. This product can be used under the following environmental conditions:
    • Indoor
    • Pollution Degree 2
    • At an altitude of 2000m or below
  4.  Power input must be within the designated ranges.
  5. To turn on or turn off power supply for this product, please use the circuit breaker or switch of a standard product of IEC 60947-1 or IEC 60947-3 product and install it within a close distance allowing convenient operation by user provided.
  6. An output wire to be used for this product should be inflammable grade FV1(v-1 grade or above). The thickness of the wire should 0.08mm²~1.3 mm²
  7. In order to prevent it from an inductive noise, please maintain the high-voltage wire and power wire separated.
  8. Please avoid installing the product in a place where a strong magnetism, noise, severe vibration and impact exist.
  9. When extending the sensor wire, use a shield wire and do not extend it unnecessary long.
  10. The sensor wire and signal wire should be away from the power and load wires using conduits separately installed.
  11. Please avoid using the product near a device generating strong high frequency noise (high frequency welding machine, high-frequency sewing machine, high-frequency radiotelegraph, high capacity SCR controller)

Basic specifications

Items Description
Dimension 87(W)mm x 114(H)mm x 30 (D)mm
Power supply 24Vac +10%/-15%, 50/60Hz (SEC611)
24Vdc+10%/-15% (SEC611 & SEC612)
Class II
Power consumption 15VA with Sanhua EEV at 24VDC
Connection Pluggable terminal: Screw M2 Min/Max wire diameter: 0.08²~1.3 mm² XHP terminal
Input Pressure sensor
Temperature sensor
RUN signal Passive switch signal
Output Relay output 30Vdc/5A
EEV (uni-polar) output
Communication RS 485
Operation -30~55 oC, Humidity≤95%RH
Storage -30~55 oC, Humidity≤95%RH
Protection level IP20

SANHUA SEC Series EEV Controller - a

Installation Notes

a. DIN slide rail mounting
Mount the controller on the DIN rail by the snap on the back of the controller.
Installed in the electric control cabinet to avoid moisture and dust.

SANHUA SEC Series EEV Controller - b

b. Sensors installation
Pressure transmitter / temperature sensor installed on the tube of evapora tor outlet. If the system is divided into several eva porators, install pressure transmitter / temperature sensor at each evaporator outlet.

SANHUA SEC Series EEV Controller - c

We recommend to install the temperature and pressure sensors within 0.5m from the evaporator to prevent ambient temperature and pressure drop interference for the superheat calculation.

Wire Connections

SANHUA SEC Series EEV Controller - d

Type Function Label Description
Pluggable
terminal
Power supply 24Vac/Vdc +24V AC24V / DC24V+
-24V AC24V / DC24V-
Compressor signal
and comm port
RUN GND Passive swithcing signal, open or close synchronously with the compressor, close when using manual mode
S/W
RS485 GND GND
B- TRX-(B)
A+ TRX+(A)
Auxiliary relay output AUX-RLY N.O. Normally Open contact
COM Common
N.C. Normally Open contact
XIIP
terminal
Pressure sensor P-SENS Vcc Power: YCQB: +5V
(RED) YCQC: 10-30Vdc
Si Si YCQB: 0.5-3.5V
(White) YCQC: 4-20mA
GND GND YCQB: GND
(Black) YCQC: N/A
Temp. sensor T-SENS S2 NTCSK/B3970
GND
EEV output EEV MOTOR A
B
A
B
COM

SANHUA SEC Series EEV Controller - e

Safety Tips:

  1. Do not turn on the power before completing the wiring, cut off the power before changing the wiring.
  2. The RUN port (compressor signal) is a passive port. If add a voltage it may cause the controller burn out.
  3. Ultracapacitor please series connected to the power supply wire. (Coming soon)
  4. If you use a transformer, please ensure the minimum power is 15 VA (for 1 controller + 1 EEV).
  5. Min/max wire diameter: 0.2 ~1.3 mm²
  6. 24Vdc or 24Vac for SEC611, 24Vdc only for SEC612.

DIP SW Setting

All DIP switches are OFF in default mode (suitable for most applications). There are 4 DIP switches, 2, 3 used as a group for selecting EEV type, 1, 4 used as a group for selecting controller operating mode.

SANHUA SEC Series EEV Controller - f

a. EEV type selecting
EEV total steps, excitation speed and excitation mode is determined by the DIP SW2, 3

SANHUA SEC Series EEV Controller - g

(Default mode)
DIP SW2: OFF, DIP SW3: OFF
1-2 phase, 500 steps, 30pps

SANHUA SEC Series EEV Controller - h

DIP SW2: OFF, DIP SW3: ON
2phase, 2000 steps, 100PPS

SANHUA SEC Series EEV Controller - m

DIP SW2: ON, DIP SW3: ON
Custom mode, set by parameter table 3

b. Control method selecting
Control method determined by the DIP SW1, 4

DIP SW position Description Schematic
SANHUA SEC Series EEV Controller - n – DIP SW1: OFF, DIP SW4: OFF
– Superheat control (Default mode)
–  Temp./pressure signal ensures system SH stable
SANHUA SEC Series EEV Controller - r
SANHUA SEC Series EEV Controller - o –  DIP SW1: ON, DIP SW4: OFF
–  Manual operation
–  Use SANHUA SEC Series EEV Controller - icon 14 Button directly controls the valve opening ratio
SANHUA SEC Series EEV Controller - s
SANHUA SEC Series EEV Controller - p –  DIP SW1: ON, DIP SW4: ON
–  Drive mode
–  Use 4-20mA or 1-5Vanalog signal control
SANHUA SEC Series EEV Controller - t
SANHUA SEC Series EEV Controller - q –  DIP SW1: OFF, DIP SW4: ON
– Hot gas bypass (temperature control)
SANHUA SEC Series EEV Controller - u

Note:

  1. While using the manual /drive mode, keep the compressor RUN signal always ON.
  2. n drive mode, external 4-20mA or 1-5V analog signal is input through the pressure sensor port.

SANHUA SEC Series EEV Controller - v

Buttons and operation

a. Screen introduction

SANHUA SEC Series EEV Controller - x

LED Description
SH Display current superheat
PRESS Display pressure sensor value
OPEN Display current EEV opening
TEMP Display temperature sensor value
oC /bar Unit of temp./pressure

Warning

Lighting when alarming
SANHUA SEC Series EEV Controller - y Flickering at communication mode
POWER Lighting at power up
TX,RX Flickering at communication

Use SANHUA SEC Series EEV Controller - icon 14 button can switch the display on screen among superheat/ pressure/valve opening/temperature (current display is indicated by the cursor pointer)

b. Buttons introduction

SANHUA SEC Series EEV Controller - icon 15  Enter the parameter setting interface / return parameter list
SANHUA SEC Series EEV Controller - icon 14  Switch screen display parameters, increase/decrease parameters
SANHUA SEC Series EEV Controller - icon 46  Confirm key, parameter switch in parameter table, long press save parameter

c. Set/change parameters

SANHUA SEC Series EEV Controller - FIGURE 1

  1. During operating status, long press SANHUA SEC Series EEV Controller - icon 15 for more than 3s, enter parameter setting mode
  2. When screen show SANHUA SEC Series EEV Controller - icon 16 , press SANHUA SEC Series EEV Controller - icon 17 until screen display 5 (original password), then press enter parameters table list
  3. SANHUA SEC Series EEV Controller - icon 18 means parameters table1, press can select SANHUA SEC Series EEV Controller - icon 19 or SANHUA SEC Series EEV Controller - icon 20 (switching parameter table)
  4. After selected parameters table, press SANHUA SEC Series EEV Controller - icon 46 enter the table, if you want to switch other parameter tables, press SANHUA SEC Series EEV Controller - icon 15 return to the parameter table select list
  5. In parameters table, screen will directly display the parameter code, press SANHUA SEC Series EEV Controller - icon 46 can switch the code in parameters table
  6. When the screen displays the parameter code which you want to modify, press SANHUA SEC Series EEV Controller - icon 14 can modify parameters directly, and press SANHUA SEC Series EEV Controller - icon 46 will turn to next parameter or press SANHUA SEC Series EEV Controller - icon 15 return to the parameter table select list
  7. After finish modifying, long press SANHUA SEC Series EEV Controller - icon 46 for 3s will save all settings and return to the operating interface.

d. Main parameter setting
1. Refrigerant selection
Refrigerant data is in SANHUA SEC Series EEV Controller - icon 29

Add. Code Description Default
40062 SANHUA SEC Series EEV Controller - icon 31 Refrigerant 0(R22)

Now 26 kinds refrigerants is available in controller as below:

0 R22 7 R1234YF 14 R744(CO2) 21 R124
1 R404A 8 R290 15 R744(N2O) 22 R717
2 R410A 9 R450A 16 R32 23 R407H
3 R134A 10 R513A 17 R245FA 24 R454C
4 R407C 11 R448A 18 R23 25 R455A
5 R507 12 R449A 19 R407A
6 R1234ZE 13 R452A 20 R407F

2. Target superheat setting
Target superheat is in SANHUA SEC Series EEV Controller - icon

Add.

Code Description

Default

40001 SANHUA SEC Series EEV Controller - icon 1 Target superheat 6

If the target SH is too small, may cause liquid hammer in compressor; if the target value is too large, the evaporator energy efficiency will be very low.
3. Start open ratio and duration time
You can find it in SANHUA SEC Series EEV Controller - icon

Add. Code Description Default
40003 SANHUA SEC Series EEV Controller - icon 3 Start open ratio 0
40004 SANHUA SEC Series EEV Controller - icon 2 Start open ratio duration time 0

When controller receives compressor RUN signal, EEV will keep the start opening ratio for the duration time.
4. Pump down function

Add. Code Description Default
40025

SANHUA SEC Series EEV Controller - icon 23

Select pump down function and delay time -1(OFF)
40026 SANHUA SEC Series EEV Controller - icon 24 Pressure set-point for stopping pump down 0.5

If 40025 value is not -1, pump down function is ON RUN signal = ON => Compressor is ON
RUN signal = OFF (need main controller to cut off) => EEV will close
when low pressure = 40026 bar or delay time = 40025 seconds, the Output Relay changes its position and will inform to cut Off the compressor
5. Reset to factory settings

Add. Code Description Default
SANHUA SEC Series EEV Controller - icon 45 Reset 0

 Reset is inSANHUA SEC Series EEV Controller - icon 29 menu, useSANHUA SEC Series EEV Controller - icon 14 to find the parameter SANHUA SEC Series EEV Controller - icon 45 , input backup-password 913 and long pressSANHUA SEC Series EEV Controller - icon 46 , all parameters reset to the default from factory

Alarm mode

Code

Description Code

Description

RUN signal disconnected MOP high pressure alarm
Pressure transmitter disconnected LOP Low pressure alarm
Pressure transmitter short circuit High superheat alarm
Temperature sensor disconnected Low superheat alarm
Temperature sensor short circuit Low temperature freezing alarm
SANHUA SEC Series EEV Controller - icon 13 Supply voltage out of tolerance

Note StP is not alarm, just reminding the compressor RUN signal is disconnected. Alarm manual reset button is on side face of SEC (EEV driver) shell. SANHUA SEC Series EEV Controller - fig 1

Parameters Table

1. SANHUA SEC Series EEV Controller - iconRefrigerant data is in

Add. Description Code Unit Step Min. Max. Default
40001 Superheat set point SANHUA SEC Series EEV Controller - icon 1 K 0.1 0.5 30 6
40003 Start open ratio SANHUA SEC Series EEV Controller - icon 2 % 1 0 100 0
40004 Start open ratio duration time SANHUA SEC Series EEV Controller - icon 3 Sec 1 0 600 0
40005 P: Proportional gain SANHUA SEC Series EEV Controller - icon 4 % 0.1 0.1 99.9 3
40006 I: Integral time SANHUA SEC Series EEV Controller - icon 5 Sec 1 0 999 20
40007 D: Derivative time SANHUA SEC Series EEV Controller - icon 6 Sec 1 0 999 4
40008 Low SH alarm mode SANHUA SEC Series EEV Controller - icon 7 0=No use 1=automatic return 2=manual return 1
40009 Low SH alarm value SANHUA SEC Series EEV Controller - icon 53 K 0.1 0.5 30 0.5
40010 Low SH alarm delay time SANHUA SEC Series EEV Controller - icon 8 Sec 1 1 300 15
40011 Clear low SH alarm SANHUA SEC Series EEV Controller - icon 10 K 0.1 1 30.5 3
40012 MOP alarm mode SANHUA SEC Series EEV Controller - icon 11 0=No use 1=automatic return 2=manual return 1
40013 MOP alarm pressure SANHUA SEC Series EEV Controller - icon 12 bar 0.1 -1 50 9
40014 MOP alarm delay time SANHUA SEC Series EEV Controller - icon 13 Min 1 1 15 1
40015 Clear MOP alarm        SANHUA SEC Series EEV Controller - icon 14 bar 0.1 -1 50 8
40016 High SH alarm mode SANHUA SEC Series EEV Controller - icon 15 0=No use 1=automatic return 2=manual return 0
40017 High SH alarm value SANHUA SEC Series EEV Controller - icon 16 K 1 10 40 30
40018 High SH alarm delay time SANHUA SEC Series EEV Controller - icon 17 Min 1 1 600 3
40019 Clear high SH alarm SANHUA SEC Series EEV Controller - icon 18 K 0.1 7 37 27
40021 Freeze prevention alarm mode SANHUA SEC Series EEV Controller - icon 19 0=No use 1=automatic return 2=manual return 0
40022 Freeze prevention alarm value SANHUA SEC Series EEV Controller - icon 20 oC 1 -40 40 0
40023 Freeze prevention alarm delay time SANHUA SEC Series EEV Controller - icon 21 Sec 1 5 200 30
40024 Clear freeze prevention alarm SANHUA SEC Series EEV Controller - icon 22 oC 1 -37 43 3
40025 Select pump down function and delay time SANHUA SEC Series EEV Controller - icon 23 Sec 1 0 180 -1(OFF)
40026 Pressure set-point for stopping pump down SANHUA SEC Series EEV Controller - icon 24 bar 0.1 -0.5 18 0.5
40027 Pressure low limit alarm mode SANHUA SEC Series EEV Controller - icon 25 0=No use 1=automatic return 2=manual return 0
40028 Pressure low limit alarm value SANHUA SEC Series EEV Controller - icon 26 bar 0.1 -0.8 17.7 0
40029 Low limit pressure alarm delay time SANHUA SEC Series EEV Controller - icon 27 Sec 1 5 200 5
40030 Clear low limit pressure alarm SANHUA SEC Series EEV Controller - icon 28 bar 0.1 -0.5 18 0.3

1) Alarm setting
When alarm setting is ON, if system pressure/temperature exceeds/below the set alarm value and keep more than the delay time, the controller will generate an alarm and act accordingly
2.SANHUA SEC Series EEV Controller - icon 29(Parameters Table2)

Add. Description Code Unit Step Min. Max. Default
40061 Password / 1 0 999 5
40062 Refrigerant SANHUA SEC Series EEV Controller - icon 31 0=R22   1=R404A   2=R410A   3=R134a   4=R407C
40062 Refrigerant SANHUA SEC Series EEV Controller - icon 31 5=R507 6=R1234ze 7=R1234yf   8=R290   9=R450A
40062 Refrigerant SANHUA SEC Series EEV Controller - icon 31 10=R513A   11=R448A   12=R449A   13=R452A
14=R744(CO2)   15=R744(N20)   16=R32   17=R245fa
0
40062 Refrigerant SANHUA SEC Series EEV Controller - icon 31 18=R23   19=R407A   20=R407F   21=R124   22=R717
40062 Refrigerant SANHUA SEC Series EEV Controller - icon 31 23=R407H   24=R454C   25=R455A
40063 Pressure sensor MAX. range SANHUA SEC Series EEV Controller - icon 32 bar 1 0 99 12(Current) 20(Voltage)
40064 Pressure sensor MIN. range SANHUA SEC Series EEV Controller - icon 33 bar 1 -1 99 -1(Current) 0(S Voltage)
40065 Pressure sensor offset correction SANHUA SEC Series EEV Controller - icon 34 K 0.1 -9.9 9.9 0
40066 Temp. sensor offset correction SANHUA SEC Series EEV Controller - icon 35 K 0.1 -20 19.9 0
40069 Jerk control ratio SANHUA SEC Series EEV Controller - icon 36 0.1 0.1 100 100
40070 EEV open ratio upper limit SANHUA SEC Series EEV Controller - icon 37 % 1 0 100 100
40071 EEV open ratio lower limit SANHUA SEC Series EEV Controller - icon 38 % 1 0 100 0
40072 Sensor input filter time SANHUA SEC Series EEV Controller - icon 39 / 0.1 1 99.9 1
40073 EEV compulsory open ratio SANHUA SEC Series EEV Controller - icon 40 % 0.1 0 100 OFF(-1)
40076 Display mode SANHUA SEC Series EEV Controller - icon 41 0=1~4 rotation / 1= Superheat
2=Evaporator outlet pressure / 3= Expansion valve open ratio
4= Evaporator outlet temperature / 5= Saturation temperature
1
40077 Run/stop method SANHUA SEC Series EEV Controller - icon 45 0= Always run / 1= Digital input 2= Communication Run 1
40078 CommunicationID setup SANHUA SEC Series EEV Controller - icon 43 / 1 1 254 1
40079 Communication speed setup SANHUA SEC Series EEV Controller - icon 44 48(0)=4800 96(1)=9600   192(2)=19200   384(3)=38400 96
Reset SANHUA SEC Series EEV Controller - icon 42 / 1 0 999 0

1) set SANHUA SEC Series EEV Controller - icon 45 to password value (default 5), and then long pressSANHUA SEC Series EEV Controller - icon 46 the controller will factory reset.

3. SANHUA SEC Series EEV Controller - icon 52(Parameters Table3)

Add. Description Code Unit Step Min. Max. Default
40041 Hold current SANHUA SEC Series EEV Controller - icon 47 0=OFF 1=ON 0
40042 Expansion valve excitation type SANHUA SEC Series EEV Controller - icon 48 1-2(0)=1-2 phase excitation 2(1)=2 phase excitation 1-2
40043 Expansion valve total pulse SANHUA SEC Series EEV Controller - icon 49 pulse 1 10 999 50
40044 Expansion valve open pulse SANHUA SEC Series EEV Controller - icon 50 pulse 1 0 999 30
40045 EEV drive speed (PPS) SANHUA SEC Series EEV Controller - icon 51 10(0)=10PPS   20(1)=20PPS   30(2)=30PPS
50(3)=50PPS   80(4)=80PPS   100(5)=100PPS
200(6)=200PPS   250(7)=250PPS   500(8)=500PPS
 

30(2)

  1.  Parameter Table 3 is usually not use, SANHUA standard EEV can directly set by the DIP SW.
    If you want modify parameters table 3, please change DIP SW first. (See page 5)
  2. Because the controller screen display maximum value is 999, so 40043 EEV total steps pulse 50 means 500 steps.

Communication Protocol

a. Specification

Item Description
Transmission line connection Multiple line
Communication method RS485 (2-wire, half-duplex)
Baud-rate Default 9600BPS
Parity, Data, Stop bit None, 8 data, 1 stop
Protocol Type Modbus RTU Mode
Function Code Read Hold Registers (0×03) /Preset Single Register (0×06)
Max. Read Word 32word
Media Type Belden 9841/9842, LG LIREV-AMESB
Poll interval 100ms

b. Status of Communication table

Add. Function Unit Type S SEC601 MMI
40073 EEV compulsory open ratio Analog INT 16 0.0-100.0 ×10
40099 Reset command Analog INT 16 0:OFF 1:ON
40101 Run/Stop input Analog INT 16 0:Stop 1:Run
40102 Operation status Analog INT 16 Refer to below bit
Bit0 Operation status of EEV Digital bit 0:OFF 1:ON
Bit1 Aux. relay output Digital bit 0:OFF 1:ON
40110 Alarm status Analog INT 16 Refer to below bit
Bit0 Press. sensor disconnection Digital bit 0:OFF 1:ON
Bit1 Press. sensor short circuit Digital bit 0:OFF 1:ON
Bit2 Temp. sensor disconnection Digital bit 0:OFF 1:ON
Bit3 Temp. sensor short circuit Digital bit 0:OFF 1:ON
Bit6 MOP alarm Digital bit 0:OFF 1:ON
Bit7 Low limit pressure alarm Digital bit 0:OFF 1:ON
Bit8 High superheat alarm Digital bit 0:OFF 1:ON
Bit9 Low superheat alarm Digital bit 0:OFF 1:ON
Bit10 Freezing Protection alarm Digital bit 0:OFF 1:ON
40111 Present Superheat K Analog INT 16 ×10
40112 Present saturation temperature C Analog INT 16 ×10
40113 Present pressure bar Analog INT 16 -1.0~1.0 ×10
40114 Present temperature C Analog INT 16 -100.0~100.0 ×10
40116 EEV open ratio % Analog INT 16 0.0~100.0 ×10

SANHUA logo

Copyright © SANHUA 2022
II-SEC61-EN-R2201
Subject to change without notice