S Plus S REGELTECHNIK PREMASGARD 11D9 Modbus
- Type: WG02
- Model: 11D9 PREMASGARD 11D9-Modbus
- Output: Modbus
- Power Supply: 12V
- Pressure Type: Differential Pressure
- Pressure Connection: M16x1.5
- Measurement Range: 0.01 bar to 1 bar
- Accuracy: ±0.001 bar
Product Usage Instructions
Follow the provided mounting schema (A, B, C, D) in the manual for proper installation.
Setup:
Set the Modbus address using the DIP switches as indicated in the manual.
Calibration:
Perform manual zero point adjustment and offset correction as described in the manual.
Communication Settings:
Configure the baud rate and parity settings using the DIP switches based on your requirements.
Data Read/Write:
Refer to the telegram section in the manual to understand how to read input registers and write data to the device.
- Q: How do I set the Modbus address?
A: Use the DIP switches following the instructions provided in the manual to set the Modbus address. - Q: How can I calibrate the device?
A: Perform manual zero point adjustment and offset correction as detailed in the manual for accurate calibration. - Q: What are the communication settings I need to configure?
A: Configure baud rate and parity settings using the DIP switches according to your communication requirements. - Q: How do I read/write data to the device?
A: Refer to the telegram section in the manual for instructions on reading input registers and writing data to the device.
Operating and Mounting Instructions
Measuring transducers for pressure, differential pressure and volume flow, incl. connection set, calibratable, with Modbus connection
Dimensional drawing
PREMASGARD® 11D9-Modbus
Maintenance-free microprocessor-controlled PREMASGARD® 11D9 – Modbus with Modbus connection, in an impact-resistant plastic housing, for measuring the differential pressure (max. –500…500 Pa) in the air. Incl. connection set ASD-06 (2 m / 78.74 in connecting hose, two pressure port nipples, screws).
The pressure sensor is applied to measure positive, negative or differential pressure in clean air and gaseous media. It is used in clean-room, Medi-Cal and filter technology, ventilation, and air-conditioning ducts, spray booths, large-scale catering facilities, for filter monitoring and level measurement or for triggering frequency converters.
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, LEDs for telegram status display and one a push-in terminal. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
TECHNICAL DATA
Mounting diagram
TYPES OF MONITORING
Negative pressure
- P1 (+) is not connected, but open to the atmosphere
- P2 (–) connection inside of duct
Positive pressure
- P1 (+) connection inside of duct
- P2 (–) is not connected, but open to the atmosphere
Filter
- P1 (+) connection upstream of filter
- P2 (–) connection downstream of filter
Pressure ⁄ volume flow on fan
- P1 (+) connection upstream of fan (vacuum chamber)
- P2 (–) connection of fan nozzle (ring nozzle)
Pressure connections at the pressure-measuring transducer are marked with
- P1 (+) for higher pressure and
- P2 (–) for lower pressure.
Schematic diagram
Manual zero point calibration (Pa):
- The device must be operative for at least 60 minutes before zero point setting is started.
- Connect pressure inputs P (+) and P (–) with a hose (differential pressure between the connections = 0 Pa).
- To set the zero point, press the “auto zero” pushbutton for 10 seconds without interruption.
- The sensors are pre-set and calibrated at the factory.
- Each measuring channel has a separate offset potentiometer for subsequent adjustment of the measurement.
- The adjusting range is ± 10 % of the measuring range (pressure).
Conversion table for | pressure values: | ||||
Unit = | bar | mbar | Pa | kPa | mWs |
1 Pa | 0.00001 bar | 0.01 mbar | 1 Pa | 0.001 kPa | 0.000101971 mWs |
1 kPa | 0.01 bar | 10 mbar | 1000 Pa | 1 kPa | 0.101971 mWs |
1 bar | 1 bar | 1000 mbar | 100000 Pa | 100 kPa | 10.1971 mWs |
1 mbar | 0.001 bar | 1 mbar | 100 Pa | 0.1 kPa | 0.0101971 mWs |
1 mWs | 0.0980665 bar | 98.0665 mbar | 9806.65 Pa | 9.80665 kPa | 1 mWs |
Bus address (binary coded, value selectable from 1 to 247) |
|||||||
DIP 1 | DIP 2 | DIP 3 | DIP 4 | DIP 5 | DIP 6 | DIP 7 | DIP 8 |
128 | 64 | 32 | 16 | 8 | 4 | 2 | 1 |
O N | O N | OFF | OFF | OFF | OFF | OFF | O N |
Example shows 128 + 64 + 1 = 193 as Modbus address. |
The device address in the range of 1 to 247 is set at DIP switch [A]. For switch positions 1 to 8 see the table on the back!
Address 0 is reserved for broadcast messages. Addresses greater than 247 must not be assigned and are ignored by the device. The DIP switches are binary-coded with the following values:
- DIP 1 = 128…………. DIP 1 = ON
- DIP 2 = 64…………. DIP 2 = ON
- DIP 3 = 32…………. DIP 3 = OFF
- DIP 4 = 16…………. DIP 4 = OFF
- DIP 5 = 8…………. DIP 5 = OFF
- DIP 6 = 4…………. DIP 6 = OFF
- DIP 7 = 2…………. DIP 7 = OFF
- DIP 8 = 1…………. DIP 8 = ON
The switch positions shown here result in the Modbus address 128 + 64 + 1 = 193
BUS PARAMETERS
Baud rate
(selectable) |
DIP 1 | DIP 2 |
9600 baud | O N | OFF |
19200 baud | O N | O N |
38400 baud | OFF | O N |
reserved | OFF | OFF |
Parity
(selectable) |
DIP 3 |
EVEN
(numbered) |
O N |
ODD
(numbered) |
OFF |
Parity check
(on / off) |
DIP 4 |
Active
(1 stop bit) |
O N |
Inactive (no parity) (2 stop bits) | OFF |
8N1 mode
(on / off) |
DIP 5 |
Active | O N |
Inactive (default) | OFF |
Busabschluss
(ein/aus) |
DIP 6 |
Active | O N |
Inactive | OFF |
- The baud rate (speed of transmission) is set at DIP switches 1 and 2 of DIP switch block [B].
- Selectable are 9600 baud, 19200 baud, or 38400 baud – see table!
- Parity is set at DIP switch 3 of DIP switch block [B].
- Selectable are EVEN or ODD – see table!
- Parity check is activated via DIP switch 4 of DIP switch block [B].
- Selectable are active (1 stop bit), or inactive (2 stop bits), i.e. no parity check – see table!
- The 8N1 mode is activated via DIP switch 5 of DIP switch block [B].
- The functionality of DIP switch 3 (parity) and DIP switch 4 (parity check) of DIP switch block [B] is therefore deactivated. Selectable are 8N1 active or inactive (default) – see table !.
- Bus termination is activated via DIP switch 6 of DIP switch block [B].
- Selectable are active (bus termination resistance of 120 Ohm), or inactive (no bus termination) – see table!
COMMUNICATION INDICATOR
Communication is indicated via two LEDs. Error-free received telegrams are signalized by the green LED lighting up, regardless of the device address. Faulty telegrams or triggered Modbus exception telegrams are depicted by the red LED lighting up.
DIAGNOSTICS
An error diagnostic function is integrated
TELEGRAMS
Function 04 Read Input Register
Register | Parameter | Data Type | Value | Range | |
3×0001 | Differential pressure | Without filtering | Signed 16 Bit | – 500…+ 500 | – 500…+ 500Pa |
3×0002 | Differential pressure | Filtering 1 s | Signed 16 Bit | – 500…+ 500 | – 500…+ 500Pa |
3×0003 | Differential pressure | Filtering 10 s | Signed 16 Bit | – 500…+ 500 | – 500…+ 500Pa |
3×0010 | Volume flow (high byte) | Computed value | Unsigned 16 Bit | 0…99 | Value* 10000 m3/h |
3×0011 | Volume flow (low byte) | Computed value | Unsigned 16 Bit | 0…9999 | 0…9999 m3/ |
Function 05 Write Single Coil
Register | Parameter | Data Type | Value | Range |
0x0001 | Auto zero (Pa) | Bit 0 | 0 / 1 | OFF – ON |
Function 06 Write Single Register & Function 16 Write Multiple Register
Register | Parameter (Display) | Data Type | Value | Range | |
4×0001 | Physical parameter displayed | Index on display | Unsigned 8 Bit | 0…10 | 0…10 |
Standard display (cyclic):
Differential pressure [Pa] |
– |
0 |
Default setting | ||
Alternative display (static): | |||||
Volume flow [m3/h] | 1 | 1 | |||
Differential pressure [Pa] | 6 | 6 | |||
Freely configurable display | 10 | 10 | |||
4×0002 | 7-segment value | Signed 16 Bit | –999…9999 | –999…9999 | |
4×0003 | 14-segment pattern 1 see graphic | Unsigned 16 Bit | see Binary Pattern | ||
4×0004 | 14-segment pattern 2 see graphic | Unsigned 16 Bit | see Binary Pattern | ||
4×0005 | Segment Pattern | Unsigned 16 Bit | see Binary Pattern | ||
4×0006 | Dot Matrix Character A | Unsigned 8 Bit | 0…255 | ASCII character | |
4×0007 | Dot Matrix Character B | Unsigned 8 Bit | 0…255 | ASCII character | |
4×0008 | Dot Matrix Character C | Unsigned 8 Bit | 0…255 | ASCII character | |
4×0009 | Dot Matrix Character D | Unsigned 8 Bit | 0…255 | ASCII character | |
4×0010 | Dot Matrix Character E | Unsigned 8 Bit | 0…255 | ASCII character | |
4×0011 | Dot Matrix Character F | Unsigned 8 Bit | 0…255 | ASCII character | |
4×0012 | Dot Matrix Character G | Unsigned 8 Bit | 0…255 | ASCII character | |
4×0013 | – | ||||
4×0014 | – | ||||
4×0015 | – |
Register | Parameter | Data Type | Value | Range |
4×0023 * | k value | Unsigned 16 Bit | 1…2000 | 1…2000 |
4×0024 | Function type ** | Unsigned 8 Bit | 1…3 | 1…3 |
Note* (Register 4×0023)
The computed coefficients for the volume flow display are not saved in the permanent memory and are lost at zero voltage. They must be reset when the communication begins. Selection of the function type ** (Register 4×0024) Type 1: Rosenberg, Comefri, Type 2: Ziehl-Abegg,
Type 3 |
Function 08 Diagnostics
The following sub function codes are supported
Sub Function Code | Parameter | Data Type | Answer |
00 | Echo of transmission data (Loopback) | Echo data | |
01 | Restart Modbus
(Reset listen-only mode) |
Echo telegram | |
04 | Activation listen-only mode | No answer | |
10 | Delete counter | Echo telegram | |
11 | Counter bus telegrams | Unsigned 16 Bit | All valid bus telegrams |
12 | Counter communication errors (Parity, CRC, frame errors, etc.) | Unsigned 16 Bit | Faulty bus telegrams |
13 | Counter exception telegrams | Unsigned 16 Bit | Error counter |
14 | Counter slave telegrams | Unsigned 16 Bit | Slave telegrams |
15 | Counter telegrams without answer | Unsigned 16 Bit | Broadcast messages (address 0) |
Function 17 Report Slave ID
Composition of answer telegram
Byte No. | Parameter | Data Type | Answer |
00 | Number of bytes | Unsigned 8 Bit | 6 |
01 | Slave ID (device type) | Unsigned 8 Bit | 23 = PREMASGARD® 11D9 – Modbus |
02 | Slave ID (device class) | Unsigned 8 Bit | 30 = PREMASGARD® / PREMASREG® |
03 | Status | Unsigned 8 Bit | 255 = RUN, 0 = STOP |
04 | Version number (release) | Unsigned 8 Bit | 1…9 |
05 | Version number (version) | Unsigned 8 Bit | 1…99 |
06 | Version number (index) | Unsigned 8 Bit | 1 |
General layout of bus structure
- Terminating resistor may only be installed at the ends of the bus line.
- In networks with repeaters not more than two line terminations are allowed.
- Line termination at the device can be activated via DIP switch 6.
- The bias resistors for bus level definition in the resting state are usually activated at the Modbus master/repeater.
- The maximum number of subscribers per Modbus segment is 32 devices.
- When the number of subscribers is greater, the bus must be subdivided into several segments separated by repeaters. The subscriber address can be set from 1 to 247.
- For the bus line, a twisted-pair cable data line/power supply line and copper mesh wire shield must be used. Therefore, the line capacitance should be less than 100 pF / m (e.g. Profibus cable).
Installation and Commissioning
Notes on installation:
Mounting shall take place while observing all relevant regulations and standards applicable for the place of measurement (e.g. such as welding instructions, etc.). Particularly the following shall be regarded:
- VDE ⁄ VDI directive technical temperature measurements, measurement set-up for temperature measurements.
- The EMC directives must be adhered to.
- It is imperative to avoid parallel laying of current-carrying lines.
- We recommend to use shielded cables with the shielding being attached at one side to the DDC ⁄ PLC.
Before mounting, make sure that the existing thermometer‘s technical parameters comply with the actual conditions at the place of utilization, in particular in respect of:
- Measuring range
- Permissible maximum pressure, flow velocity
- Installation length, tube dimensions
- Oscillations, vibrations, shocks are to be avoided (< 0.5 g)
Attention! In any case, please observe the mechanical and thermal load limits of the protective tubes according to DIN 43763 or according to specific S+S standards!
Notes on commissioning:
This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals. Commissioning is mandatory and may only be performed by qualified personnel!
General notes
Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
In addition, the following points are to be observed:
- Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.
- This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.
- No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
- Consequential damages caused by a fault in this device are excluded from warranty or liability.
- These devices must be installed and commissioned by authorised specialists.
- The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
- In case of any modifications made by the user, all warranty claims are forfeited.
- This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.
Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided. - Operating this device close to other devices that do not comply with EMC directives may influence functionality.
- This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
- Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
- Modifications of these records are not permitted.
- In case of a complaint, only complete devices returned in original packing will be accepted.
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!
Zubehör
Accessories
ASD – 06
Anschluss-Set Connection set
© Copyright by S+S Regeltechnik GmbH
Reprint in full or in parts requires permission from S+S Regeltechnik GmbH. Subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to inform about our products and their application potential, but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user themselves. Existing property rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions.
Bus address, binary coded
S+S REGELTECHNIK GMBH
THURN-UND-TAXIS-STR. 22 90411 NÜRNBERG ⁄ GERMANY
FON +49 (0) 911 ⁄ 519 47- 0 mail@SplusS.de www.SplusS.de