RENU WP2 Lite Web Panel User Guide

WP2 Lite Web Panel

WP2 Lite Web Panel

Specifications

  • Power (Base):
    • 4.3: 24VDC(+20%) @250mA, 6W
    • 7.0: 24VDC(+20%) @300mA, 7.2W
    • 10.1: 24VDC(+20%) 350@mA, 8.4W
  • Product Code:
    • WP2043TN: 4.3, 480 x 272 pixels, WQVGA color TFT with 4-wire
      analog resistive touch screen with serial port, 1 Ethernet
      port.
    • WP2070TN: 7, 800 x 480 pixels, WVGA color TFT with 4-wire
      analog resistive touch screen with serial port, 1 Ethernet
      port.
    • WP2101TN: 10.1, 1024 x 600 pixels, WSVGA color TFT with 4-wire
      analog resistive touch screen with serial port, 1 Ethernet
      port.
  • Memory:
    • CPU: 32-bit ARM Cortex-M7
    • RAM: 32MB
  • Dimensions:
    • 89(H) x 120(W) x 31.5(D) mm
    • 138(H)x186(W)x31(D) mm
    • 190(H)x268(W)x33(D) mm
  • Weight: Approx. 200gm, 400gm, 900gm
  • LED: 1
  • Communication: Ethernet 1×10/100MBps
  • OSK: Yes
  • Environment & Approvals:
    • Humidity: 10 to 95% (Noncondensing)
    • Shock: IEC 60068-2-27, 25g, 11ms, 6 shocks per axis, total 18
      shocks (X, Y, Z)
    • Vibration: 5~150Hz, 3g peak, (X, Y, Z)
    • Protection: Front panel-IP66, Rare panel-IP20
    • Approvals Supported Web Server: CE, UL (Class 1 DIV 2), UKCA,
      REACH & RoHS compliant Spider Controls, Codesys2.x,
      Codesys3.x

Product Usage Instructions

Getting Started

  1. Power ON the WP2 Lite panel using a 24VDC power supply.
  2. Plug in the Ethernet cable into the RJ45 port.
  3. After the device boots up, click on Settings Microbrowser and
    Network Settings.
  4. On the new screen enter the Host address and the start page on
    the host Eg: Host: 192.168.1.50 Start Page: start.html
  5. Click Back to go to the main page.
  6. Click Start to load the web page.

Display

The display specifications vary based on the product code
chosen:

  • 480 x 272pixels , 4.3 Color TFT, WQVGA Web Panel Analog
    Resistive Touch Screen
  • 800 x 480pixels , 7 Color TFT, WVGA Web Panel Analog Resistive
    Touch Screen
  • 1024 x 600pixels , 10.1 Color TFT, WSVGA Web Panel Analog
    Resistive Touch Screen

Frequently Asked Questions (FAQ)

What type of power supply does the WP2 Lite Web Panel
require?

The WP2 Lite Web Panel requires a 24VDC power supply with
specific current ratings based on the screen size.


“`

WP2 Lite Web Panel
QUICK START GUIDE

Specification
Power (Base)

4.3″: 24VDC(+20%) @250mA, 6W 7.0″: 24VDC(+20%) @300mA, 7.2W
10.1″: 24VDC(+20%) 350@mA, 8.4W

Product Code
WP2043TN: 4.3″, 480 x 272 pixels, WQVGA color TFT with 4-wire analog resistive touch screen with serial port, 1 Ethernet port. WP2070TN: 7″, 800 x 480 pixels, WVGA color TFT with 4-wire analog resistive touch screen with serial port, 1 Ethernet port. WP2101TN: 10.1″, 1024 x 600 pixels, WSVGA color TFT with 4-wire analog resistive touch screen with serial port, 1 Ethernet port.
WP2 Lite web panel is a Thin Client with an inbuilt Micro browser ready to connect to a remote web server on the network.
Getting Started
To use the WP2 Lite as a browser, follow these steps to connect the device to a Webserver. 1. Power ON the WP2 Lite panel using a 24VDC power
supply. 2. Plug in the Ethernet cable into the RJ45 port. 3. After the device boots up, click on Settings
Microbrowser and Network Settings. 4. On the new screen enter the Host address and the
start page on the host Eg: Host: 192.168.1.50 Start Page: start.html
5. Click Back to go to the main page. 6. Click Start to load the web page.

Display

480 x 272pixels , 4.3″ Color TFT, WQVGA Web Panel Analog Resistive Touch Screen
800 x 480pixels , 7″ Color TFT, WVGA Web Panel Analog Resistive Touch Screen
1024 x 600pixels , 10.1″ Color TFT, WSVGA Web Panel Analog Resistive Touch Screen

Memory

CPU: 32-bit ARM Cortex-M7 RAM: 32MB

Panel Cutout

80(H) x 111(W) mm 127(H)x175(W) mm 178(H)x256(W) mm

Dimensions

89(H) x 120(W) x 31.5(D) mm 138(H)x186(W)x31(D) mm 190(H)x268(W)x33(D) mm

Weight

Approx. 200gm, 400gm, 900gm

LED

1

Communication

Ethernet

1×10/100MBps

OSK

Yes

Environment & Approvals

Operating Temperature 0°C to 50°C

Storage Temperature -30°C to 85°C

Humidity

10 to 95% (Noncondensing)

Shock

IEC 60068-2-27, 25g, 11ms, 6 shocks per axis, total 18 shocks (X, Y, Z)

Vibration

5~150Hz, 3g peak, (X, Y, Z)

Protection

Front panel-IP66, Rare panel-IP20

Approvals Supported Web Server

CE, UL (Class 1 DIV 2) ,UKCA, REACH & RoHS compliant
Spider Controls, Codesys2.x, Codesys3.x

Panel Cutout Dimensions
WP2043TN
WP2070TN
WP2101TN

WP2043TN Panel Cutout Dimensions: 111.00 (W) x 80.00(H) mm Panel Thickness: Maximum 6mm Mounting Clamps: 2
WP2070TN Panel Cutout Dimensions: 127.00(H) x 175.00(W) mm Panel Thickness: Maximum 6mm Mounting Clamps: 4
WP2101TN Panel Cutout Dimensions: 256.00 (W) x 178.00(H) mm Panel Thickness: Maximum 6mm Mounting Clamps: 6
Tighten the mounting screws evenly to a torque between 0.4N/m to maintain water and dust resistance.

Communication

This section provides information regarding communication interfaces supported by this product. RJ45/Ethernet Port
The WP6 Plus series devices come with an in-built RJ45/Ethernet port. The RJ45 port is a shielded female jack with link and activity LEDs.

Pin number

Signal

1

TX+

2

TX-

3

RX+

4

NC

5

NC

6

RX-

7

NC

8

NC

Earthing
The optimum method for earthing electronic equipment is to earth it separately from other high-power systems, to earth more than one unit of electronic equipment with a single-point earth. The earthing marked terminal (see below) is provided on the unit.

CONTROL DRAWING NO# CNTL/DWG/WP2 Lite/001 VER.NO: 1.00

[Note: Do not use an earth that has an unstable impedance, such as painted screws or earth subject to vibration.] WARNING
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-hazardous locations only.
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been removed or the area is known to be non- hazardous.
WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for Class I, Division 2.
The list of materials used in the construction of these devices with name of sealed device – generic name of the material and the supplier’s name and type designation.
It is recommended that the user periodically inspect the sealed devices used, for any degradation of properties and Replace the device if any degradation is found.

Revision History

Rev. Description

Date

1.2 Specification updated

09/06/2025

1.1 Updated Product Image

16/11/2022

1.0 First Draft

07/11/2022

RENU Electronics Pvt. Ltd® reserves the right to change or discontinue specifications and features without prior notice. To view the latest and updated datasheets/manuals, please visit www.renuelectronics.com.

Documents / Resources

RENU WP2 Lite Web Panel [pdf] User Guide
WP2070TN, WP2101TN, WP2 Lite Web Panel, WP2 Lite, Web Panel, Panel

References

Leave a comment