RENOGY RNG-SET-ANLX0 ANL Fuse Set

Product Usage Instructions
- Before using the RENOGY ANL Fuse set, familiarize yourself with the safety guidelines provided in the user manual.
- Ensure to follow all safety instructions to prevent electrical shock or damage to the product.
- Understand the components of the ANL Fuse set, including the ANL fuses and the fuse cover.
- Familiarize yourself with the different ampere ratings available to select the appropriate fuse for your application.
- Disconnect power source: Before installation, ensure that the power source is disconnected to avoid any electrical mishaps.
- Select appropriate ampere rating: Choose the correct ampere rating ANL fuse based on your system requirements.
- Insert the fuse: Insert the ANL fuse into the designated slot, ensuring it fits securely.
- Install the fuse cover: Place the fuse cover over the fuse for added protection and safety.
- Test functionality: After installation, test the system to ensure proper functionality.
Before Getting Started
The user manual provides important operation and maintenance instructions for RENOGY ANL Fuse Set w/ Fuse, RENOGY ANL Fuse Cover, and RENOGY ANL Fuse.
Read the user manual carefully before operation and save it for future reference. Failure to observe the instructions or precautions in the user manual can result in electrical shock, serious injury, or death, or can damage the ANL fuse or fuse set, potentially rendering it inoperable.
- Renogy ensures the accuracy, sufficiency, and applicability of information in the user manual at the time of printing due to continual production. Safety First improvements that may occur.
- Renogy assumes no responsibility or liability for personal and property losses, whether directly or indirectly, caused by the user’s failure to install and use the product in compliance with the user manual.
- Renogy is not responsible or liable for any failure, damage, or injury resulting from repair attempts by unqualified personnel, improper installation, or inappropriate operation.
- The illustrations in the user manual are for demonstration purposes only. Details may appear slightly different depending on product revision and market region.
- Renogy reserves the right to change the information in the user manual without notice. For the latest user manual, visit renogy.com.
Safety First
Renogy accepts no liability for any damage caused by:
- Force majeure includes fire, typhoon, flood, earthquake, war, and terrorism.
- Intentional or accidental misuse, abuse, neglect, or improper maintenance, and use under abnormal conditions.
- Improper installation, improper operation, and malfunction of a peripheral device.
- Contamination with hazardous substances or radiation.
- Alterations to the product without express written consent from Renogy.
Symbols Used
The following symbols are used throughout the user manual to highlight important information.
WARNING: Indicates a potentially hazardous condition that could result in personal injury or death.
CAUTION: Indicates a critical procedure for safe and proper installation and operation.
NOTE: Indicates an important step or tip for optimal performance.
Important Safety Instructions
- The ANL fuses or fuse sets listed in this manual shall only be deployed in DC systems operating at lower than 72V. Installation in higher-voltage systems violates safety standards and voids product warranties.
- Only use ANL fuses or fuse sets with current ratings that exactly match the system’s rated current. Never install mismatched fuses. Substitution with non-identical fuses is prohibited under safety standards.
- Prior to installation, verify that the ANL fuse and fuse set terminals exhibit no corrosion (white/green oxidation), pitting, or deformation. DO NOT use any damaged ANL fuses or fuse sets showing signs of erosion or wear.
- Verify the ANL fuse is intact with no signs of tripping, loose connections, or corrosion. DO NOT use any fuse exhibiting these defects.
- To guarantee your safety, wear insulating gloves during the fuse or fuse set installation.
- Risk of electric shock! Fuse or fuse set replacement requires full power disconnection. Never perform fuse or fuse set replacement on live circuits to eliminate shock hazards.
- Inspect and clean all fuse terminals and contact surfaces thoroughly before installation to ensure proper contact alignment.
- Handle fuses or fuse sets with care to avoid impact/dropping during installation. Never install damaged fuses that may cause premature tripping at rated current and other thermal runaway risks.
- Inspect and verify the ANL fuse and set terminals exhibit no corrosion (white/green oxidation), pitting, or deformation regularly.
- Always replace blown ANL fuses or fuse sets with identical models. Never use substitutes like copper wires to prevent hazardous failures.
- Troubleshooting your system is required before fuse or fuse set replacement. Use a multimeter to verify overload conditions or short-circuit faults.
General Information
Introduction
- A RENOGY ANL Fuse Set w/ Fuse contains a Renogy ANL fuse and an ANL Fuse Cover.
- The fuse set offers complete protection to your system, protects your charge controller, battery, inverter, and connecting wires from over-current, and ensures you get the longevity out of your system as expected.
- The ANL fuse is composed of high-quality alloy and brass copper materials, and the clear protective non-conductive resistant cover is ideal for custom installation.
Key Features
Safeguard Your System
- Ignition protection guarantees the safe use of the fuse in RVs, boats, or any other closed environments.
Multiple Specifications are Available
- Offers multiple specifications of the ANL fuses to meet the requirements of different-sized systems. Optional specifications including 20A/30A/40A/60A/80A/100A/200A/300A/400A. The protective cover is compatible with all
- specifications.
High Quality and Easy to Use Design
- The ANL fuse is composed of high-quality alloy and brass copper materials and works with a clear protective non-conductive resistant cover which is ideal for custom installation and can be easily added to your solar system.
Environment Friendly
- The ANL fuse is RoHS compliant, which confirms that it’s free from environmentally hazardous, difficult-to-dispose substances.
SKU
A Renogy ANL Fuse Set includes one ANL fuse and a fuse cover. For stocked sets, you may replace blown fuses or covers separately. Refer to the tables below for the specific model number.
ANL Fuse Set w/ Fuse
| 20A ANL Fuse Set w/ Fuse | RNG-SET-ANL20 |
| 30A ANL Fuse Set w/ Fuse | RNG-SET-ANL30 |
| 40A ANL Fuse Set w/ Fuse | RNG-SET-ANL40 |
| 50A ANL Fuse Set w/ Fuse | RPD50ANL-SET |
| 60A ANL Fuse Set w/ Fuse | RNG-SET-ANL60 |
| 80A ANL Fuse Set w/ Fuse | RPD80ANL-SET |
| 100A ANL Fuse Set w/ Fuse | RNG-SET-ANL100 |
| 200A ANL Fuse Set w/ Fuse | RPD200ANL-SET |
| 300A ANL Fuse Set w/ Fuse | RPD300ANL-SET |
| 400A ANL Fuse Set w/ Fuse | RPD400ANL-SET |
ANL Fuse
| 20A ANL Fuse | RNG-ANL-FUSE20 |
| 30A ANL Fuse | RNG-ANL-FUSE30 |
| 40A ANL Fuse | RNG-ANL-FUSE40 |
| 50A ANL Fuse | RPD50ANL |
| 60A ANL Fuse | RNG-ANL-FUSE60 |
| 80A ANL Fuse | RPD80ANL |
| 100A ANL Fuse | RNG-ANL-FUSE100 |
ANL Fuse Cover
| ANL Fuse Cover | RNG-ANL-FUSE-COVER |
Technical Specifications
Electrical Parameters
| Product | Current Rating | Voltage Rating | Interrupt Capacity |
| RNG-SET-ANL20 RNG-ANL-FUSE20 | ≤ 20A | ≤ 72V | 40A |
| RNG-SET-ANL30 RNG-ANL-FUSE30 | ≤ 30A | ≤ 72V | 60A |
| RNG-SET-ANL40 RNG-ANL-FUSE40 | ≤ 40A | ≤ 72V | 80A |
| RPD50ANL-SET RPD50ANL | ≤ 50A | ≤ 72V | 100A |
| RNG-SET-ANL60 RNG-ANL-FUSE60 | ≤ 60A | ≤ 72V | 120A |
| RPD80ANL-SET RPD80ANL | ≤ 80A | ≤ 72V | 160A |
| RNG-SET-ANL100 RNG-ANL-FUSE100 | ≤ 100A | ≤ 72V | 200A |
| RPD200ANL-SET | ≤ 200A | ≤ 72V | 400A |
| RPD300ANL-SET | ≤ 300A | ≤ 72V | 600A |
| RPD400ANL-SET | ≤ 400A | ≤ 72V | 800A |
Dimensions
Dimension tolerance: ±0.2 in (0.5 mm)
ANL Fuse Set w/ Fuse & ANL Fuse Cover

ANL Fuse

Get to Know ANL Fuse
This manual takes an ANL Fuse Set with/ Fuse as an example. A Renogy ANL Fuse Set includes one ANL fuse and a fuse cover.


Installation
Required Tools
Before installing and configuring the ANL fuse, prepare the recommended tools.

Inspection
Prior to installation, verify that the ANL fuse and set terminals exhibit no corrosion (white/green oxidation), pitting, or deformation. Verify the ANL fuse is intact with no signs of tripping, loose connections, or corrosion. DO NOT use any fuse or fuse set exhibiting these defects.

Inspect and verify the ANL fuse and set terminals exhibit no corrosion (white/green oxidation), pitting, or deformation regularly.
Wear Insulating Gloves
To guarantee your safety, wear insulating gloves during the fuse installation.

Installation Instructions
Install all components in the exact order shown in the illustration below. Ring terminals sized for M8 studs (M8-M10 acceptable).

Tighten the nuts to 70.8 in•lbs (8 N•m).
Components
Time-current curves – average melt:
Functional Characteristics
A fuse does not blow when the current reaches its rated current. It is designed to pass its rated current without opening. A fuse will take varying times to blow under different conditions. A fuse will pass significantly more than its rated current for a very short time. The periods for other fuses will be slightly different.
| Testing Current (% of amp rating) | Blow the Time Limit |
| 150% (Rating < 225A) | 1 hour at a minimum |
| 160% (Rating > 225A) | 6 seconds at minimum |
| 220% | 60 seconds at maximum |
| 250% | 0.8s to 10s |
| 400% | 0.2s to 2s |
Renogy Empowered
- Renogy aims to empower people around the world through education and the distribution of DIY-friendly renewable energy solutions.
- We intend to be a driving force for sustainable living and energy independence.
- In support of this effort, our range of solar products makes it possible for you to minimize your carbon footprint by reducing the need for grid power.
Live Sustainably with Renogy
Did you know? In a given month, a 1 kW solar energy system will…
- Save 170 pounds of coal from being burned
- Save 300 pounds of CO2 from being released into the atmosphere
- Save 105 gallons of water from being consumed
Renogy Power PLUS
Renogy Power Plus allows you to stay in the loop with upcoming solar energy innovations, share your experiences with your solar energy journey, and connect with like-minded people who are changing the world in the Renogy Power Plus community.
Renogy reserves the right to change the contents of this manual without notice.
Disclaimer
RENOGY ANL Fuse Set w/ Fuse, ANL Fuse Cover, and ANL Fuse User Manual © 2025 Renogy. All rights reserved.
RENOGY and RENOGY are registered trademarks of Renogy.
- All information in the user manual is subject to copyright and other intellectual property rights of Renogy and its licensors. The user manual may not be modified, reproduced, or copied, in whole or in part, without the prior written permission of Renogy and its licensors.
- The registered trademarks in the user manual are the property of Renogy. The unauthorized use of the trademarks is strictly prohibited.
Online Manual
User Manual
The above values are from the NEC Table 310.16 for copper cables rated at 194°F (90°C), operating at an ambient temperature of no more than 86°F (30°C). Please note that wire gauge standards may vary due to factors such as temperature and installation conditions. In actual applications, it is recommended to refer to the latest NEC standards.
CONTACT
Renogy Support
To discuss inaccuracies or omissions in this quick guide or user manual, visit or contact us at:
Questionnaire Investigation
To explore more possibilities of solar systems, visit the Renogy Learning Center at:
For technical questions about your product in the U.S., contact the Renogy technical support team through:
- renogy.com/contact-us
- 1(909)2877111
For technical support outside the U.S., visit the local website below:
Canada
China
Australia
Japan
Other Europe
Germany
United Kingdom
- uk.renogy.com
- Manufacturer: RENOGY New Energy Co., Ltd
- Address: No.66, East Ningbo Road, Room 624-625, Taicang German Overseas Students Pioneer Park, Jiangsu 215000 CN
eVatmaster Consulting GmbH Raiffeisen Street2 B11, 63110 Rodgau, Hessen, Germany contact@evatmaster.com
EVATOST CONSULTING LTD- Office 101 32 Threadneedle Street, London, United Kingdom, EC2R 8AY contact@evatost.com
- RENOCY.COM

FAQ
How do you size an ANL fuse?
- Always prioritize the recommended fuse size in the manual of your charge controller, battery charger, or inverter.
- Alternatively, you can size a fuse based on the current going through the fuse. For details, see Size Fuses or Circuit Breakers for a Solar Power System at Renogy Learning Center
Can the fuse be replaced individually, or does the entire fuse set require replacement?
The fuse alone is replaceable (no full device replacement needed). Replace the fuse set only when the fuse holder/terminals are damaged.
What size are the posts on this fuse set holder?
The posts are 5/16“ studs (metric equivalent: M8). Ring lugs sized for M8-M10 are recommended.
Does the fuse or fuse set come with a fuse cable?
No. You need to purchase a fuse cable separately.
How to size a fuse cable for the ANL fuse or fuse set?
Always prioritize the recommended cable size in the manual of your charge controller, battery charger, or inverter. Alternatively, you can refer to the table below for copper cable ampacities with different gauge sizes for up to 13 feet (4 m) cables. Cables longer than 13 feet (4 m) may require thicker gauge wires to prevent excessive voltage drop in undersized wiring.
| Cable Gauge Size | Ampacity | Cable Gauge Size | Ampacity |
| 14 AWG (2.08 mm²) | 25A | 1 AWG (42.41 mm²) | 145A |
| 12 AWG (3.33 mm²) | 30A | 1/0 AWG (53.49 mm²) | 170A |
| 10 AWG (5.26 mm²) | 40A | 2/0 AWG (67.43 mm²) | 195A |
| 8 AWG (8.37 mm²) | 55A | 3/0 AWG (85.01 mm²) | 225A |
| 6 AWG (13.3 mm²) | 75A | 4/0 AWG (107.22 mm²) | 260A |
| 4 AWG (21.15 mm²) | 95A | 300 kcmil (152.1 mm²) | 320A |
| 3 AWG (26.67 mm²) | 115A | 400 kcmil (202.8 mm²) | 380A |
| 2 AWG (33.62 mm²) | 130A | 500 kcmil (253.5 mm²) | 430A |