Control and Monitoring Modules for use with the Raychem NGC-40 System Installation Instructions

DESCRIPTION

The Raychem NGC-40-BRIDGE module provides the interface between a panel’s internal CAN-based network and upstream devices. Multiple communications ports are supported, allowing serial and Ethernet connections to be used with external devices.

TOOLS REQUIRED

  • Small flat-blade screwdriver

ADDITIONAL MATERIALS

  • Power supply 24 Vdc @150 mA per NGC-40-BRIDGE
  • Custom built CAN cables with RJ-45 connections

KIT CONTENTS

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (1)

Item Qty Description
A 1 NGC-40-BRIDGE module
B 2 CAN bus termination block PTM# 10392-043
C 2 RS-485 termination resistors 120 Ω – 1% – 1/4 watt
D 1 NGC-40-BRIDGE serial cable TTC# 10332-005

Special conditions of use:

  • The overall equipment is evaluated to type of protection “ec”
  • For full connection details see these installation instructions
  • The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC/EN 60664-1
  • The equipment shall be installed an enclosure that provides a minimum ingress protection of IP54 in accordance with IEC/EN 60079-0
  • Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment

WARNING:
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. For technical support, call Chemelex at 800-545-6258.

GENERAL 

Supply voltage 24 Vdc ± 10%
Internal power consumption <3.6 W per NGC-40-BRIDGE
Ambient operating temperature –40°C to 65°C (–40°F to 149°F)
Ambient storage temperature –55°C to 75°C (–67°F to 167°F)
Environment PD2, CAT III
Max. altitude 2,000 m (6,562 ft)
Humidity 5 – 90% noncondensing
Mounting Din Rail – 35 mm

ELECTROMAGNETIC COMPATIBILITY

Emissions EN 61000-6-3 Emission standard for residential, commercial and light industrial environments
Immunity EN 61000-6-2 Immunity standard for industrial environments

COMMUNICATIONS COM1, COM2

Type 2-wire RS-485
Cable One shielded twisted pair
Length 1,200 m (4,000 ft) maximum
Quantity Up to 255 devices per port
Data rate 9600, 19.2 K, 38.4 K, 57.6 K, 115.2 K baud
Data bits 7 or 8
Parity None, even, odd
Stop bits 0, 1, 2
Tx delay 0 – 5 sec.
Protocol Modbus RTU or ASCII
Connection terminals Wago cage clamp terminals

COMMUNICATIONS COM3

Type RS-232
Cable Custom TTC# 10332-005
Length 15 m (50 ft) maximum
Data rate 9600, 19.2 K, 38.4 K, 57.6 K, 115.2 K baud
Data bits 7 or 8
Parity None, even, odd
Stop bits 0, 1, 2
Tx delay 0 – 5 sec.
Protocol Modbus RTU or ASCII
Connection terminals RJ-11

CAN NETWORKING PORT

Type 2-wire isolated CAN-based peer-peer network. Isolated to 300 V.
Connection Two 8-pin RJ-45 connectors (both may be used for Input or Output connections)
Protocol Proprietary NGC-40
Topology Daisy chain
Length 10 m (33 ft) maximum
Quantity Up to 80 CAN nodes per network segment
Address Unique, factory assigned

ETHERNET

Type 10/100 BaseT Ethernet network
Length 100 m (328 ft)
Data rates 10 or 100 MB/s
Protocol Modbus/TCP
Connection terminals Shielded 8-pin RJ-45 connector on front of module

PROGRAMMING AND SETTING

LED indicators
Alarm conditions RESET, Configuration lost, CAN communications fail
Configuration switch SET/RUN slide switch on front of module

CONNECTION TERMINALS

Wiring terminals Cage clamp, 0.5 to 2.5 mm² (24 to 12 AWG)
CAN networking and module power Two RJ-45s, one each IN and OUT. Provides CAN bus signals and +24 Vdc power.

HOUSING

Size 45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep

System Components

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (4)Wiring Terminals

Terminals Function
1 COM 1 (485) + in
2 COM 1 (485) + out
3 COM 2 (485) + in
4 COM 2 (485) + out
5 COM 1 (485) – in
6 COM 1 (485) – out
7 COM 2 (485) – in
8 COM 2 (485) – out
9 – 12 Not used

 Status LEDs

Status: Indicates status of the module
Off No power
Green OK/Normal
Yellow (flashing) Configuration mode
Red (flashing) Internal fault
NETWORK: Indicates CAN network activity
Off No link detected
Green Link OK, receive data packets
Yellow Transmit data packets
Red (flashing) Network error
COM: Indicates COM1 & 2 (RS-485) activity
Off No activity
Green (flashing) Receipt of data packet
Yellow (flashing) Transmit of data packet

Communication Slide Switch

 RS-232 Port

Status: Indicates status of RS-232 port
Top LED
Off No activity
Green (flashing) Receipt of data packet
Bottom LED
Off No activity
Yellow (flashing) Transmit of data packet

E. Ethernet Port

Status: Indicates status of the LAN
Top LED
Off No LAN detected
Green ON, LAN detectedt
Bottom LED
Off No LAN activity
Yellow (flashing) LAN activity (data packet)

CAN Bus/Module Power

 Reset Button

Mounting the NGC-40-BRIDGE

  • Each NGC-40-BRIDGE mounts on a DIN 35 rail.
  • MOUNTING: Insert the rear bottom of the module into the DIN rail, then push up and inwards to engage the clip.
  • REMOVAL: Push the module upwards to disengage the clip, then rotate the module toward you.

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (5)RS-485 Connection Diagrams – North American Installation Technique

COM 1&2 Connections (In)
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground.

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (6)

COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown.

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (7)

RS-485 Connection Diagrams – European Installation Technique

COM 1&2 Connections (In)
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar. Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (8)

COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar.

Local RS-232 (COM 3) & EthernetRaychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (9)

Switch Setting RS-232
User Interface – Configuration Switch
A slide switch is provided on the front of the module to allow the user to set the bridge into a known state for configuration of the communication ports, as shown in the following table:

Switch Position
Bridge Module Settings SET Configuration mode RUN Normal operating mode
Modbus address 1
Local RS-232
Protocol RTU Settings based on the user configuration parameters
Data rate 9600 baud
Data bits 8
Stop bits 2
Parity No parity

RMM2 Connection – Optional
When using the field mounted RMM2 for RTD input, it must be connected to the COM 2 In as shown below.

 

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (11) Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (12)

NGC-40 CAN Bus Connections for Up to 10 Modules

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (13)

NGC-40 CAN Bus Connections for Up to 20 Modules

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (14) Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (15)

CAN Bus Termination Block
A termination block (included) is required at each end of the CAN/24 Vdc bus. See NGC-40 CAN bus connection wiring diagram for more details.

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (16)

Provide Suitable Panel Enclosure and Determine Locations for NGC-40-BRIDGE Assembly in Panel*

  1. Provide suitable panel enclosure
    The NGC-40-BRIDGE must be mounted in an enclosure to protect its electronic components. For indoor applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). For outdoor applications, use a NEMA 4 or NEMA 4X enclosure depending on the requirements.
    Note: The Raychem NGC-40-BRIDGE is designed for operation in ambient temperatures from –40°C to 65°C (–40°F to 149°F ). If the ambient temperature is outside this range, a space heater and/or cooling fan will be required in the panel.
  2. Determine locations for the NGC-40-BRIDGE assembly in the electrical panel.
    The NGC-40-BRIDGE should be located in the rear of the panel. The NGC-40-BRIDGE assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or excessive vibration.
    * North American panel installation techniques

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (17)

NGC-40 CAN Bus Connections for Up to 40 Modules Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (18) Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (19) Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (20)

APPROVALS

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (2)Hazardous Locations
Class I, Div. 2, Groups A,B,C,D T4 Class I, Zone 2, AEx ec IIC T4 Gc IP20 Ex ec IIC T4 Gc X –40°C ≤ Ta ≤ +65°C

Conforms to:
FM STD 3600 & 3611, UL STD 121201, 60079-0, 60079-7, 61010-1, 61010-2-201

Certified to:
CSA STD C22.2# 213, 60079-0, 60079-7, 61010-1, 61010-2-201

Raychem-NGC-40-BRIDGE-Control-and-Monitoring-Modules- (3)(Russia, Kazakhstan, Belarus)
For other countries contact your local Chemelex representative.

  • IEC Ex Markings: IECEx ETL 17.0062X Ex ec IIC T4 Gc
  • ATEX Markings: ITS17ATEX402833X II 3 G Ex ec IIC T4 Gc

North America

Latin America

Europe, Middle East, Africa, India

Asia Pacific

Frequently Asked Questions

What approvals does the NGC-40-BRIDGE module have?

The module conforms to FM STD 3600 & 3611, UL STD 121201, 60079-0, 60079-7, 61010-1, 61010-2-201 and is certified to CSA STD C22.2# 213, 60079-0, 60079-7, 61010-1, 61010-2-201. It also has IEC Ex and ATEX markings for specific regions.

How many communication ports are supported by the NGC-40-BRIDGE module?

The NGC-40-BRIDGE module supports multiple communication ports for both serial and Ethernet connections with external devices.

What is the purpose of the CAN bus termination block included in the kit?

The CAN bus termination block is used for terminating the CAN bus network to ensure proper signal integrity and communication within the system.

Is the NGC-40-BRIDGE module suitable for use in hazardous locations?

Yes, the module is approved for use in hazardous locations as indicated by its certifications and markings.