Raychem NGC-40-BRIDGE Control and Monitoring Modules User Manual

NGC-40-BRIDGE Control and Monitoring Modules

Specifications:

  • Supply voltage: Not specified
  • Internal power consumption: Not specified
  • Ambient operating temperature: Not specified
  • Ambient storage temperature: Not specified
  • Environment: Hazardous Locations
  • Max. altitude: Not specified
  • Humidity: Not specified
  • Mounting: Not specified

Product Usage Instructions:

Description:

The Raychem NGC-40-BRIDGE module acts as an interface between a
panel’s internal CAN-based network and external devices. It
supports multiple communication ports for serial and Ethernet
connections.

Tools Required:

  • No specific tools specified

Additional Materials:

  • No additional materials specified

Kit Contents:

Item Qty Description
A 1 NGC-40-BRIDGE module
B 2 CAN bus termination block PTM# 10392-043
C 2 No description provided
D 1 NGC-40-BRIDGE serial cable TTC# 10332-005

Special Conditions of Use:

WARNING: This electrical device must be
installed correctly to ensure proper operation and prevent shock or
fire. For technical support, contact Chemelex at (800)
545-6258.

Frequently Asked Questions (FAQ):

Q: What approvals does the NGC-40-BRIDGE module have?

A: The module conforms to FM STD 3600 & 3611, UL STD 121201,
60079-0, 60079-7, 61010-1, 61010-2-201 and is certified to CSA STD
C22.2# 213, 60079-0, 60079-7, 61010-1, 61010-2-201. It also has IEC
Ex and ATEX markings for specific regions.

Q: How many communication ports are supported by the
NGC-40-BRIDGE module?

A: The NGC-40-BRIDGE module supports multiple communication
ports for both serial and Ethernet connections with external
devices.

Q: What is the purpose of the CAN bus termination block
included in the kit?

A: The CAN bus termination block is used for terminating the CAN
bus network to ensure proper signal integrity and communication
within the system.

Q: Is the NGC-40-BRIDGE module suitable for use in hazardous
locations?

A: Yes, the module is approved for use in hazardous locations as
indicated by its certifications and markings.

“`

NGC-40-BRIDGE
Control and Monitoring Modules for use with the Raychem NGC-40 System Installation Instructions

A B C

D
Shown not to scale

APPROVALS

Hazardous Locations

4008 717

Class I, Div. 2, Groups A,B,C,D T4 Class I, Zone 2, AEx ec IIC T4 Gc IP20 Ex ec IIC T4 Gc X ­40°C Ta +65°C

Conforms to: FM STD 3600 & 3611, UL STD 121201, 60079-0, 60079-7, 61010-1, 61010-2-201

Certified to: CSA STD C22.2# 213, 60079-0, 60079-7, 61010-1, 61010-2-201

(Russia, Kazakhstan, Belarus) For other countries contact your local Chemelex representative.

IEC Ex Markings: IECEx ETL 17.0062X Ex ec IIC T4 Gc

ATEX Markings: ITS17ATEX402833X
II 3 G Ex ec IIC T4 Gc

DESCRIPTION
The Raychem NGC-40-BRIDGE module provides the interface between a panel’s internal CAN-based network and upstream devices. Multiple communications ports are supported, allowing serial and Ethernet connections to be used with external devices.

TOOLS REQUIRED
· Small flat-blade screwdriver

ADDITIONAL MATERIALS
· Power supply 24 Vdc @150 mA per NGC-40-BRIDGE · Custom built CAN cables with RJ-45 connections

KIT CONTENTS

Item Qty Description

A

1

NGC-40-BRIDGE module

B

2

CAN bus termination block PTM# 10392-043

C

2

RS-485 termination resistors 120 ­ 1% – 1/4 watt

D

1

NGC-40-BRIDGE serial cable TTC# 10332-005

Special conditions of use:
· The overall equipment is evaluated to type of protection “ec”
· For full connection details see these installation instructions
· The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC/EN 60664-1
· The equipment shall be installed an enclosure that provides a minimum ingress protection of IP54 in accordance with IEC/EN 60079-0
· Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment

WARNING:
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. For technical support, call Chemelex at 800-545-6258.
2 | chemelex.com

GENERAL

Supply voltage Internal power consumption Ambient operating temperature Ambient storage temperature Environment Max. altitude Humidity Mounting

24 Vdc ± 10% <3.6 W per NGC-40-BRIDGE ­40°C to 65°C (­40°F to 149°F) ­55°C to 75°C (­67°F to 167°F) PD2, CAT III 2,000 m (6,562 ft) 5 ­ 90% noncondensing Din Rail ­ 35 mm

ELECTROMAGNETIC COMPATIBILITY

Emissions Immunity

EN 61000-6-3 Emission standard for residential, commercial and light industrial environments EN 61000-6-2 Immunity standard for industrial environments

COMMUNICATIONS COM1, COM2

Type Cable Length Quantity Data rate Data bits Parity Stop bits Tx delay Protocol Connection terminals

2-wire RS-485 One shielded twisted pair 1,200 m (4,000 ft) maximum Up to 255 devices per port 9600, 19.2 K, 38.4 K, 57.6 K, 115.2 K baud 7 or 8 None, even, odd 0, 1, 2 0 ­ 5 sec. Modbus RTU or ASCII Wago cage clamp terminals

COMMUNICATIONS COM3

Type Cable Length Data rate Data bits Parity Stop bits Tx delay Protocol Connection terminals

RS-232 Custom TTC# 10332-005 15 m (50 ft) maximum 9600, 19.2 K, 38.4 K, 57.6 K, 115.2 K baud 7 or 8 None, even, odd 0, 1, 2 0 ­ 5 sec. Modbus RTU or ASCII RJ-11

chemelex.com | 3

CAN NETWORKING PORT

Type Connection Protocol Topology Length Quantity Address

2-wire isolated CAN-based peer-peer network. Isolated to 300 V. Two 8-pin RJ-45 connectors (both may be used for Input or Output connections) Proprietary NGC-40 Daisy chain 10 m (33 ft) maximum Up to 80 CAN nodes per network segment Unique, factory assigned

ETHERNET

Type Length Data rates Protocol Connection terminals

10/100 BaseT Ethernet network 100 m (328 ft) 10 or 100 MB/s Modbus/TCP Shielded 8-pin RJ-45 connector on front of module

PROGRAMMING AND SETTING

LED indicators Alarm conditions Configuration switch

RESET, Configuration lost, CAN communications fail SET/RUN slide switch on front of module

CONNECTION TERMINALS

Wiring terminals CAN networking and module power

Cage clamp, 0.5 to 2.5 mm² (24 to 12 AWG) Two RJ-45s, one each IN and OUT. Provides CAN bus signals and +24 Vdc power.

HOUSING

Size

45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep

4 | chemelex.com

System Components
45.1 mm (1.78 in)
RESET
NGC-40 BRIDGE MODULE

45.1 mm (1.78 in)

45.1 mm (1.78 in)

45.1 mm (1.78 in)

87 mm (3.43 in) 106.4 mm (4.2 in)
87 mm (3.43 in)

Front

Top

A. Wiring Terminals

Terminals 1 2 3 4 5 6 7 8 9 ­ 12

Function COM 1 (485) + in COM 1 (485) + out COM 2 (485) + in COM 2 (485) + out COM 1 (485) ­ in COM 1 (485) ­ out COM 2 (485) ­ in COM 2 (485) ­ out Not used

B. Status LEDs

Status: Indicates status of the module

Off

No power

Green

OK/Normal

Yellow

(flashing) Configuration mode

Red

(flashing) Internal fault

NETWORK: Indicates CAN network activity

Off

No link detected

Green

Link OK, receive data packets

Yellow

Transmit data packets

Red

(flashing) Network error

Bottom

Back

COM: Indicates COM1 & 2 (RS-485) activity

Off

No activity

Green

(flashing) Receipt of data packet

Yellow

(flashing) Transmit of data packet

C. Communication Slide Switch D. RS-232 Port

Status: Indicates status of RS-232 port

Top LED

Off

No activity

Green

(flashing) Receipt of data packet

Bottom LED

Off

No activity

Yellow

(flashing) Transmit of data packet

E. Ethernet Port

Status: Indicates status of the LAN

Top LED

Off

No LAN detected

Green

ON, LAN detectedt

Bottom LED

Off

No LAN activity

Yellow

(flashing) LAN activity (data packet)

F. CAN Bus/Module Power G. Reset Button

chemelex.com | 5

Mounting the NGC-40-BRIDGE Each NGC-40-BRIDGE mounts on a DIN 35 rail. MOUNTING: Insert the rear bottom of the module into the DIN rail, then push up and inwards to engage the clip.
2

REMOVAL: Push the module upwards to disengage the clip, then rotate the module toward you.
2

1

1

RS-485 Connection Diagrams ­ North American Installation Technique

COM 1&2 Connections (In)
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground.

COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 termination resistors (included) at the panel mounted field terminal block as shown.

COM 1 In

159

+

­

Field terminal
block + ­

To upstream device

RESET
NGC-40 BRIDGE MODULE
COM 2 In
3 7 11 +­

To upstream device

RESET
NGC-40 BRIDGE MODULE

COM 1 Out

2 6 10

+

­

Field terminal
block
120 ohm termination
resistor

COM 2 Out
4 8 12 +­
120 ohm termination
resistor

6 | chemelex.com

RS-485 Connection Diagrams ­ European Installation Technique

COM 1&2 Connections (In)
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar.

COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 termination resistors (included) at the panel mounted field terminal block as shown. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar.

RESET
NGC-40 BRIDGE MODULE

COM 1 In Earth grounding
bar located at the bridge module
159

+

­

+

­

Field terminal block

To upstream device

COM 2 In Earth grounding
bar located at the 3 7 11 bridge module

+

­

RESET
NGC-40 BRIDGE MODULE

COM 1 Out Earth grounding
bar located at the bridge module
2 6 10

120 ohm termination
resistor

Field terminal block

COM 2 Out Earth grounding
bar located at the 4 8 12 bridge module

+

­

To upstream device

Local RS-232 (COM 3) & Ethernet
RESET
NGC-40 BRIDGE MODULE

RS-232
Local RS-232 to Laptop
Ethernet
To upstream device

120 ohm termination
resistor

Switch Setting RS-232

User Interface ­ Configuration Switch
A slide switch is provided on the front of the module to allow the user to set the bridge into a known state for configuration of the communication ports, as shown in the following table:

Switch Position

Bridge Module Settings

SET Configuration mode

RUN Normal operating mode

Modbus address Local RS-232
Protocol Data rate Data bits Stop bits Parity

1
RTU 9600 baud 8 2 No parity

Settings based on the user configuration parameters

chemelex.com | 7

RMM2 Connection ­ Optional When using the field mounted RMM2 for RTD input, it must be connected to the COM 2 In as shown below.
RESET
NGC-40 BRIDGE MODULE

Panel
To next RMM2
Field

~~

COM 2 In Earth grounding
bar located at the 3 7 11 bridge module

Panel Terminal Block

+~ ~­
RS-485 Shielded Twisted Pair

+ ­+ ­

8 | chemelex.com

NGC-40 CAN Bus Connections for Up to 10 Modules

Termination Block

CAN / 24 Vdc

CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

CAN/Term CAN / 24 Vdc
Power/ Termination
Module

100-240 Vac In
Primary Supply* 24 Vdc +
20 Modules ­ per Power Supply

100-240 Vac In
Redundant Supply* 24 Vdc +
20 Modules ­ per Power Supply
Optional redundant supply

IN OUT CAN / 24 Vdc
Bridge Module 80 Modules per Bridge
Module 1

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 2

* Power supply shall have a means for disconnect from line voltage

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 3

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 4

Termination Block
IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 10

NGC-40 CAN Bus Connections for Up to 20 Modules

Termination Block

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN/Term CAN / 24 Vdc
Power/ Termination
Module

100-240 Vac In
Primary Supply* 24 Vdc +
20 Modules ­ per Power Supply

100-240 Vac In
Redundant Supply* 24 Vdc +
20 Modules ­ per Power Supply
Optional redundant supply

IN OUT CAN / 24 Vdc
Bridge Module 80 Modules per Bridge
Module 1

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 2

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 3

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 4

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 10
Termination Block

Power/ Termination
Module

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

Module 11

Module 12

* Power supply shall have a means for disconnect from line voltage

Module 13

Module 14

Module 20

chemelex.com | 9

CAN Bus Termination Block
A termination block (included) is required at each end of the CAN/24 Vdc bus. See NGC-40 CAN bus connection wiring diagram for more details.
Termination block

CAN / TERM

CAN / 24 VDC

CAN / TERM CAN / 24 VDC

Termination block

PTM

PTM

HTC/HTC3/IO HTC/HTC3/IO

HTC10

HTC9

Provide Suitable Panel Enclosure and Determine Locations for NGC-40-BRIDGE Assembly in Panel*

1. Provide suitable panel enclosure
The NGC-40-BRIDGE must be mounted in an enclosure to protect its electronic components. For indoor applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). For outdoor applications, use a NEMA 4 or NEMA 4X enclosure depending on the requirements.
Note: The Raychem NGC-40-BRIDGE is designed for operation in ambient temperatures from ­40°C to 65°C (­40°F to 149°F ). If the ambient temperature is outside this range, a space heater and/or cooling fan will be required in the panel.
2. Determine locations for the NGC-40-BRIDGE assembly in the electrical panel.
The NGC-40-BRIDGE should be located in the rear of the panel. The NGC-40-BRIDGE assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or excessive vibration.
*North American panel installation techniques

Panel door
Alarm light

PS4

PS2

C21

PTM4

C1

PTM2

C22

HTC21

C2

HTC1

C23

HTC22

C3

HTC2

C24

HTC23

C4

HTC3

C25

HTC24

C5

HTC4

PS1 PTM1 CBM I/O1 I/O2 I/O3 I/O4 I/O5

C26

HTC25

C6

HTC5

C27

HTC26

C7

HTC6

Panel
TB

C28

HTC27

C8

HTC7

C29

HTC28

C9

HTC8

C10

PS3 PTM3 HTC11 HTC12 HTC13 HTC14 HTC15 HTC16 HTC17 HTC18 HTC19 HTC20

C11 C12 C113 C4 C5 C16 C17 C18 C19 C20

HTC30

HTC29

C30

10 | chemelex.com

NGC-40 CAN Bus Connections for Up to 40 Modules

Termination Block

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN/Term CAN / 24 Vdc
Power/ Termination
Modules

100-240 Vac In

Primary Supply*

24 Vdc

+

20 Modules per Power Supply

­

100-240 Vac In

Redundant Supply*

24 Vdc

+

20 Modules per Power Supply

­

Optional redundant supply

IN OUT
CAN / 24 Vdc
Bridge Module
80 Modules per Bridge Module 1

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 2

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 3

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 4

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN/Term CAN / 24 Vdc
Power/ Termination
Module

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 10
IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O

CAN / 24 Vdc CAN / 24 Vdc

Module 11

Module 12

Module 13

Module 14

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

Module 20

CAN/Term CAN / 24 Vdc
Power/ Termination
Board

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3) or I/O

100-240 Vac In

Primary Supply*

24 Vdc

+

20 Modules per Power Supply

­

100-240 Vac In

Redundant Supply*

24 Vdc

+

20 Modules per Power Supply

­

Optional redundant supply

Module 21

Module 22

Module 23

Module 24

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

* Power supply shall have a means for disconnect from line voltage

CAN/Term CAN / 24 Vdc
Power/ Termination
Module

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

IN OUT
CAN / 24 Vdc
HTC/HTC3 or I/O

Module 31

Module 32

Module 33

Module 34

IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 30
Termination Block
IN OUT CAN / 24 Vdc
HTC/HTC3 or I/O
Module 40

chemelex.com | 11

North America
Tel +1 800 545 6258 info@chemelex.com

Latin America
Tel +1 713 868 4800 info@chemelex.com

Europe, Middle East, Africa, India
Tel +32 16 213 511 Fax +32 16 213 604 info@chemelex.com

Asia Pacific
Tel +86 21 2412 1688 infoAPAC@chemelex.com

©2025 Chemelex. All Chemelex marks and logos are owned or licensed by Chemelex Europe GmbH or its affiliates. All other trademarks are the property of their respective owners. Chemelex reserves the right to change specifications without notice.
RAYCHEM-IM-H58089-NGC40Bridge-EN-2504

chemelex.com