SPECIFIERS ANCHORING RESOURCE BOOK
EPCON ™ C6 PLUS
SEISMIC ANCHOR STUDS – CHEMICAL INJECTION
GENERAL INFORMATION
AVAILABLE IN NEW ZEALAND ONLY
(Australia refer to ChemSet TM Reo502 TM PLUS range)
Product
EPCON ™ C6 PLUS is a heavy duty pure Epoxy for anchoring threaded studs and reinforcing bar into cracked and uncracked concrete.
Compliance
European Technical Assessment (option 1) – ETA-18/0675 Design according to:
- AS1170.4 – Earthquake Actions
- EN1992-4 (formerly ETAG001 Annex C, E & TR045)
- NZS3101 (A3) Section 17 – Seismic Design C1
- Use enclosed data for simplified calculation method
Use Ramset TM iExpert Anchor Software for optimised calculation or where a greater range of anchor layout detail is needed.
Benefits, Advantages and Features
- 100 year working life Greater productivity:
- Anchors in dry, damp, wet or flooded holes
- Easy dispensing even in cold weather Greater security:
- Strong bond
- Rated for sustained loading Versatile:
- Anchors in carbide drilled and diamond drilled holes*
- Cold and temperate climates Greater safety:
- Low odour
- VOC Compliant
- Suitable for contact with drinking water
Installation
- Drill recommended diameter and depth hole.
- Important: Use Ramset ™ Dustless Drilling System to ensure holes are clean. Alternativly clean dust and debris from hole with stiff wire or nylon brush and blower in the following sequence: blow x 2, brush x 2, blow x 2, brush x 2, blow x 2.
- Dispense adhesive to waste until colour is uniform light grey ( 2-3 trigger pulls ). Insert mixing nozzle to bottom of hole. Fill hole to 3/4 the hole depth slowly, ensuring no air pockets form.
- Insert Ramset ™ ChemSet ™ Anchor Stud/rebar to bottom of hole while turning.
- Allow EPCON ™ C6 PLUS to cure as per setting times.
- Attach fixture.
Principal Applications
- Threaded Studs
- Starter Bars
- Threaded Inserts
- Over-head installation
- Steel Columns
- Hand Rails
- Road Stitching
Recommended Installation Temperatures
Minimum | Maximum | |
Substrate | 5°C | 40°C |
Adhesive | 10°C | 40°C |
Service Temperature Limits
-40°C to 70°C
Setting Times
Temperature of base material | Cartridge Temperature | Gel Time Curing time in dry and wet | concrete |
5°C | Minimum 10°C | 300 min | 24 h |
10°C | 10°C | 150 min | 18 h |
15°C | 15°C | 40 min | 12 h |
20°C | 20°C | 25 min | 8 h |
25°C | 25°C | 18 min | 6 h |
30°C | 30°C | 12 min | 4 h |
40°C | 40°C | 6 min | 2 h |
Note: Cartridge temperature minimum +10°C |
Note
*Performance of cored & oversized holes was not included in the ETAG test program and therefore is based on testing conducted at Ramset™ Product Engineering Laboratory.
Installation and performance details: EPCON ™ C6 Plus and ChemSet ™ Anchor Studs
* For anchor spacings or edge distances less than the minimum, please refer to the simplified strength limit state design process to verify capacity.
** Tension values are based on service temperature limits -40˚C to +70˚C only. If service temperature limits is beyond this range please contact Ramset Engineer.
**Note: Seismic Cracked concrete combined pull-out and concrete cone resistance, tension = N 0 Rd,p,seis = αNseis N 0 Rk,p,seis /γMsp where γMsp = 1.5
***Note: Seismic Cracked Concrete steel resistance, tension = NRd,s,seis = αNseis N 0 Rk,s,seis / γMs (kN) where γMs = 1.5 (Grade 5.8 & 8.8 steel), γMs = 1.87 (A4 316 SS) and γMs = 1.5 (HCR 1.4529 stainless steel)
# Note: HOT-DIP GALVANIZED ANCHORS – for Seismic C1reduced characteristic steel shear capacity the following reduction factors shall apply;
M10 Multiply VRd,seis *0.47
M12 Multiply VRd,seis *0.47
M16 Multiply VRd,seis *0.54
M20 Multiply VRd,seis *0.54
M24 Multiply VRd,seis *0.88
M30 Multiply VRd,seis *0.88
## Note: Shear Data includes annular gap reduction factor of 0.5
For optimised performance data, please use Ramset iExpert Anchoring Software.
DESCRIPTION AND PART NUMBERS
Description | Description | Part No. |
EPCON C6 PLUS | EPCON C6 PLUS | EC6P600 |
ENGINEERING PROPERTIES ChemSet ™ Anchor Studs and Threaded Rod
Refer to “Engineering Properties” for ChemSet ™ Anchor Studs Grade 5.8 and AISI 316 Stainless Steel in the SARB ANZ on page 141.
Select anchor to be evaluated
Table 1a Indicative combined loading – interaction diagram
Notes:
- Shear Limited by Grade 5.8 zinc plated steel capacity
- Tension limited by C1 concrete capacity using nominal depths
- No edge or spacing effects
- f’c = 30 MPa
Table 1b Absolute minimum edge distance and anchor spacing values, em and am (mm)
Anchor size, db MW | MW | M12 | M16 | M20 | M24 | M30 |
Min. Anchor Spacing – am | 40 | 40 | 40 | 50 | 50 | 60 |
Min. Edge Distance – em | 40 | 40 | 40 | 50 | 50 | 60 |
Step 1c Calculate anchor effective depth, h (mm)
Refer to “Description and Part Numbers” table for ChemSet ™ Anchor Studs page in the SARB ANZ on page 141.
Effective depth, h (mm)
Preferred h = hn otherwise, h = Le – t
t = total thickness of material(s) being fastened.
Substrate thickness bm (mm) | ||
Anchor Stud Size (mm) | ||
M10 | M12 | M16 to M24 |
h + 3 Omm ? 10 Omm | h + (2 x dh) |
Checkpoint 1 Anchor size determined, absolute minima compliance achieved, effective depth (h) calculated.
Verify Seismic C1 cracked concrete tensile capacity – per anchor
Table 2a – Seismic (C1) Cracked concrete combinded Pull-out and concrete cone resistance, tension N 0 Rd,p,seis = αseisN 0 Rk,p,seis/γMsp (kN), γMsp = 1.5, αN,seis = 0.85, f’c = 30 MPa where N 0 Rk,p,seis = π * db * h * τRk,cr,seis
Anchor Size, db | CI Seismic Data | |||||
M10 | M12 | M16 | M20 | M24 | M30 | |
Drilled Hole Dia, d„ (mm) | 12 | 14 | 18 | 22 | 26 | 35 |
Effective Depth, h (mm) | ||||||
70 | 11.0 | |||||
80 | 13. | |||||
90 | 14. | 15. | ||||
100 | 16. | 17. | ||||
110 | 17. | 19. | 22. | |||
120 | 19. | 20. | 24. | |||
125 | 20. | 211 | 24. | |||
140 | 22.0 | 24. | 27. | |||
150 | 24. | 25. | 29. | 37.0 | ||
160 | 25. | 27.0 | 31. | 40. | ||
170 | 27. | 29. | 33. | 42. | 44. | |
180 | 28. | 30. | 35. | 44. | 46. | |
190 | 30. | 32. | 371 | 47. | 49. | |
200 | 32. | 34. | 39. | 49. | 51. | |
210 | 36. | 41. | 52. | 54. | 54. | |
240 | 41. | 47. | 59. | 62. | 621 | |
280 | 55. | 69. | 72. | 72. | ||
320 | 63. | 79. | 821 | 83. | ||
350 | 86. | 90. | 91. | |||
400 | 99. | 103. | 103. | |||
450 | 116. | 116. | ||||
480 | 123. | 124. | ||||
550 | 142. | |||||
600 | 1551 |
Bold values are at ChemSet Anchors Stud nominal depths
All data relevant for Dry, Wet and Flooded Holes
For single anchor values: Multiply N 0
Rd,p,seis*1.17
For optimised performance data, please use Ramset iExpert Anchoring Software.
Table 2b-1 Seismic Cracked concrete service temperature limits effect, tension, Xns
Service temperature limits effect, tension, | ||||||
Anchor size, db | MIO | M12 | M16 | M20 | M24 | M30 |
Service temperature (°C) | ||||||
-40 ‘C to +70’ C | 1.00 |
Table 2b-2 Seismic Cracked concrete compressive strength effect, tension, Xnc
f’c (MPa) | 20 | 25 | 30 | 40 | 50 |
Xnc | 0.96 | 0.98 | 1.00 | 1.029 | 1.048 |
Table 2c – Seismic cracked concrete Edge distance effect, tension, Xne
Xne = 0.25 + 0.5*(e/h)
Where em ≤ e ≤ ec
ec = 1.5*h
Note: Tabled values are based on the nominal effective depth, h shown in the installation details.
For other values of Xne, please use equation shown above.
Anchor size, db | M10 | M12 | M16 | M20 | M24 | M30 |
Edge distance, e (mm) | ||||||
40 | 0.47 | 0.43 | 0.41 | |||
45 | 0.50 | 0.45 | 0.43 | |||
50 | 0.53 | 0.48 | 0.45 | 0.40 | 0.37 | |
55 | 0.56 | 0.50 | 47 | 0.41 | 0.38 | |
60 | 0.58 | 0.52 | 0.49 | 0.43 | 0.39 | 0.36 |
65 | 0.61 | 0.55 | 0.51 | 0.44 | 0.40 | 0.37 |
70 | 0.64 | 0.57 | 0.53 | 0.46 | 0.42 | 0.38 |
80 | 0.69 | 0.61 | 0.57 | 0.49 | 0.44 | 0.39 |
100 | 0.81 | 0.70 | 0.65 | 0.54 | 0.49 | 0.43 |
115 | 0.89 | 0.77 | 0.71 | 0.59 | 0.52 | 0.46 |
135 | 1.00 | 0.86 | 0.79 | 0.65 | 0.57 | 0.49 |
165 | 1.00 | 0.91 | 0.74 | 0.64 | 0.54 | |
187 | 1.00 | 0.80 | 0.70 | 0.58 | ||
255 | 1.00 | 0.86 | 0.71 | |||
315 | 1.00 | 0.81 | ||||
420 | 1.00 |
Seismic cracked concrete anchor spacing effect, tension, Xna
Xna = 0.5 + a/(6*h)
Where am ≤ a ≤ ac
ac = 3*h
Note: Tabled values are based on the nominal effective depth, h shown in the installation details.
For other values Xna, please use equation shown above.
Anchor size, db | M10 | M12 | M16 | M20 | M24 | M30 |
Anchor spacing, a (mm) | ||||||
40 | 0.57 | 0.56 | 0.55 | |||
45 | 0.58 | 0.57 | 0.56 | |||
50 | 0.59 | 0.58 | 0.57 | 0.55 | 0.54 | |
55 | 0.60 | 0.58 | 0.57 | 0.55 | 0.54 | |
60 | 0.61 | 0.59 | 0.58 | 0.56 | 0.55 | 0.54 |
65 | 0.62 | 0.60 | 0.59 | 0.56 | 0.55 | 0.54 |
85 | 0.66 | 0.63 | 0.61 | 0.58 | 0.57 | 0.55 |
100 | 0.69 | 0.65 | 0.63 | 0.60 | 0.58 | 0.56 |
125 | 0.73 | 0.69 | 0.67 | 0.62 | 0.60 | 0.57 |
150 | 0.78 | 0.73 | 0.70 | 0.65 | 0.62 | 0.59 |
200 | 0.87 | 0.80 | 0.77 | 0.70 | 0.66 | 0.62 |
270 | 1.00 | 0.91 | 0.86 | 0.76 | 0.71 | 0.66 |
330 | 1.00 | 0.94 | 0.82 | 0.76 | 0.70 | |
375 | 1.00 | 0.87 | 0.80 | 0.72 | ||
510 | 1.00 | 0.90 | 0.80 | |||
630 | 1.00 | 0.88 | ||||
840 | 1.00 |
Checkpoint
Design seismic cracked concrete combined pull-out and concrete cone resistance, NRd,p,seis NRd,p,seis = N 0 Rd,p,seis * Xns * Xnc * Xne * Xna
Verify seismic C1 cracked concrete tensile resistance – per anchor
Table 3a – Seismic C1 Cracked Concrete steel resistance, tensile, NRd,s,seis = αseisNRk,s,seis/γMs (kN), αseis = 1.0
γMs = 1.5 for Grade 5.8 and Grade 8.8 Carbon Steel
γMs = 1.87 for A4 316 Stainless Steel
γMs = 1.5 for HCR Stainless Steel
Anchor size, db | M10 | M12 | M16 | M20 | M24 | M30 |
Grade 5.8 Carbon Steel | 19. | 28.0 | 53. | 82.0 | 118.0 | 1873 |
Grade 8.8 Carbon Steel | 31. | 45. | 84.0 | 131. | 188.0 | 299. |
A4 316 Stainless Steel | 22. | 32. | 59. | 92.0 | 132. | 210. |
NCR 1.4529 Stainless Steel | 273 | 39. | 73. | 115. | 165. | 262. |
Design seismic C1 cracked concrete tensile resistance, NRd,seis
NRd,seis = minimum of NRd,p, seis , NRd,s, seis
Check N*/NRd,seis ≤ 1,
if not satisfied return to step 1
Verify seismic C1 cracked concrete edge shear resistance – per anchor
Table 4a – Seismic (C1) cracked concrete edge resistance, V 0 Rd,c,seis = αseisV 0 Rk,c,seis / γMc (kN), γMc = 1.5, αseis = 0.85, f’c = 30 MPa
Anchor size, db | M10 | M12 | M16 | M20 | M24 | M30 |
Effective depth, h (mm) | 90 | 110 | 125 | 170 | 210 | 280 |
Edge distance, em | ||||||
40 | 1.3 | 1.5. | 1.6 | |||
50 | 2.5 | 2.8 | ||||
60 | 4.2 |
Note: Data includes annular gap reduction factor of 0.5.
For single anchor values: Multiply V 0 Rd,c,seis * 1.17
For optimised performance data, please use Ramset iExpert Anchoring Software.
Table 4b – Seismic cracked concrete compressive strength effect, shear, Xvc
f’c (MPa) | 20 | 25 | 30 | 40 | 50 |
Xvc | 0.82 | 0.91 | 1.00 | 1.15 | 1.29 |
Table 4c – Seismic cracked concrete load direction effect, concrete edge shear, Xvd
Angle, u° | 0-55 | 60 | 70 | 80 | 90-180 |
Xvd | 1 | 1.1 | 1.2 | 1.5 | 2 |
Load direction effect, conc. edge shear, Xvd
Table 4d – Seismic cracked concrete anchor spacing and edge distance effect, concrete edge shear, Xve For single anchor fastening XveXve = e/em *√e/em
&en, | 1.0 | 1. | 1. | 2. | 2. | 2.0 | 2. | 2. | 3. | 3. | 3.0 | 3. |
X | 1.00 | 1. | 2. | 2. | 2. | 3. | 3. | 4. | 4. | 5. | 5.20 | 6. |
For 2 anchors fastening Xve
e/ern | 1.0 | 1. | 1. | 2. | 2. | 2.0 | 2. | 2. | 3. | 3. | 3.0 | 3. |
a/em | ||||||||||||
1.0 | 0.67 | 0.84 | 1. | 1. | 1. | 2. | 2. | 2. | 2. | 3. | 3. | 316 |
2. | 0.75 | 0.93 | 1. | 1. | 2. | 2. | 2.00 | 2. | 2.50 | 3. | 3. | 3. |
2.0 | 0.83 | 1. | 1. | 143 | 2. | 2. | 2. | 2. | 3. | 2.90 | 3. | 346 |
3. | 0.92 | 1. | 1. | 2. | 2. | 2.00 | 2. | 2.50 | 3. | 3. | 3. | 4. |
3.0 | 1.00 | 1.20 | 1. | 2. | 2. | 212 | 2. | 3. | 2.90 | 318 | 3. | 4. |
4. | 1.30 | 2. | 2. | 2. | 2. | 2.50 | 3. | 3. | 3. | 4. | 4. | |
4.0 | 2. | 2. | 210 | 2. | 3. | 3. | 317 | 346 | 4. | 4. | ||
5. | 2. | 2. | 2. | 3. | 3. | 3. | 3.60 | 3.90 | 4.20 | |||
5.0 | 2. | 3. | 3. | 3. | 3. | 4. | 4. | 4. | ||||
6. | 3. | 3. | 3. | 4. | 4. | 4. | 5. | |||||
6.0 | 3. | 311 | 3. | 4. | 4. | 4. | 5. |
For 3 anchors fastening and more
Table 4e – Seismic (C1) Cracked concrete Pryout failure, V 0 Rd,cp,seis = αseisVRk,cp / γMpr (kN), γMpr = 1.5,
αseis = 0.75, f’c = 30 Mpa
Anchor size, db | M10 | M12 | M16 | M20 | M24 | M30 |
Effective depth, h (mm) | 90 | 110 | 125 | 170 | 210 | 280 |
Cl Seismic Data | 13. | 16. | 22. | 370 | 475 | 64. |
Note: Data includes annular gap reduction factor of 0.5
For single anchor values: Multiply V 0 Rd,cp,seis*1.13
Anchor at a corner effect, concrete edge shear, Xvs
Note: For e1/e2 > 1.25, Xvs = 1.0
Checkpoint 4a
Design seismic cracked concrete edge shear resistance, VRd,c,seis = V 0 Rd,c,seis * Xvc * Xvd * Xve * Xvs
Checkpoint 4b
Design seismic cracked concrete Pryout failure, VRd,cp,seis = V 0 Rd,cp,seis * Xnc * Xne * Xna
Table 5a – Seismic (C1) Cracked Concrete steel shear resistance, VRd,s,seis = αseisVRk,s,seis/γMs (kN), αseis = 0.85
γMs = 1.25 for Grade 5.8 and Grade 8.8 Carbon Steel
γMs = 1.56 for A4 316 Stainless Steel
γMs = 1.25 for HCR 1.4529 Stainless Steel
Anchor size, db | C1 Seismic Data | ||||||
M10 | M12 | M16 | M20 | M24 | M30 | ||
Grade 5.8 | Zinc Plated Steel | 3.7 | 5.4 | 8.8 | 13.6 | 11.9 | 19 |
Hot Dip Galv. Steel | 1.8 | 2.6 | 4.8 | 7. 3 | 10.5 | 16.8 | |
Grade 8.8 | Zinc Plated Steel | 5.8 | 8.5 | 13.9 | 21.8 | 19 | 30.6 |
Hot Dip Galv. Steel | 2.7 | 4 | 7. 5 | 11.8 | 16.8 | 26.9 | |
A4 316 | Stainless Steel | 4.1 | 6 | 9.8 | 15.3 | 13.3 | 21.5 |
HCR 1.4529 | Stainless Steel | 5.1 | 7. 5 | 12.2 | 19 | 16.7 | 26.9 |
Note: Data includes annular gap reduction factor of 0.5
For single anchor values: Multiply VRd,s,seis*1.17
Checkpoint 5
Design seismic C1 cracked concrete shear resistance, VRd, seis
VRd, seis = minimum of VRd,c, seis , VRd,cp, seis ,VRd,s, seis
Check V*/VRd, seis ≤ 1,
if not satisfied return to step 1
STEP 6 Combined Loading
Check
N*/NRd,seis + V*/VRd,seis ≤ 1.0,
if not satisfied return to step 1
Specifiy – Threaded Stud Anchors Ramset ™ EPCON ™ C6 PLUS with (Anchor Size) grade 5.8 ChemSet ™ Anchor Stud (Anchor Stud Part Number) Drilled Hole Depth to be (h) mm.
Example Ramset ™ EPCON ™ C6 PLUS Injection with M16 grade 5.8 ChemSet ™ Anchor Stud (CS16190GH). Drilled hole depth to be 125mm. To be installed according to Ramset ™ Installation Instructions.
Use Ramset™ iExpert Anchor Software for optimised calculation or where a greater range of anchor layout detail is needed.
www.ramset.com.au – 1300 780 063
www.ramset.co.nz – 0800 RAMSET
Documents / Resources
![]() |
Ramset EPCON C6 PLUS Seismic Anchor Stud with Chemical Injection [pdf] Owner's Manual SARB-ANZ-Ed.3-EPCON-C6-PLUS-SEISMIC-ANCHOR-STUD, EPCON C6 PLUS, EPCON C6 PLUS Seismic Anchor Stud with Chemical Injection, Seismic Anchor Stud with Chemical Injection, Anchor Stud with Chemical Injection, Chemical Injection |