Answer

Sep 23, 2025 - 02:59 PM
1. **Setting up Temperature Measurements:**
- The SDM-6TE module supports various temperature sensors such as Pt100, Pt500, Pt1000, Ni100, KTY81-110, and different types of thermocouples (J, K, T, N, S, R, B).
- You can connect up to six temperature sensors to the module for measurement.
- The module also allows for voltage measurements and resistance measurements within specified ranges.
2. **Configuring Communication Settings:**
- The module communicates via RS485 using Modbus RTU or Modbus ASCII protocols.
- The baud rate is configurable from 2400 to 115200.
- Default communication settings include a baud rate of 19200, no parity, 8 data bits, 1 stop bit, and RTU Modbus mode.
3. **Setting Module Address in Modbus Network:**
- The module address can be set using switches on the module itself within the range of 0 to 127.
- Addresses from 128 to 255 can be set via RS485 or USB.
- Detailed instructions on how to set the module address using switches are provided in the manual.
4. **Using Configuration Software:**
- The Modbus Configurator software allows you to set the module registers for communication over the Modbus network.
- You can also read and write values to other registers of the module using this software.
- Communication with the module is done via a USB cable, and the module does not require any additional drivers.
By following the guidelines provided in the user manual, you can successfully set up the SDM-6TE module for temperature measurements, configure communication settings, set the module address, and use the configuration software for monitoring and configuration purposes. If you encounter any specific issues during setup, refer to the manual for detailed troubleshooting steps or reach out to the manufacturer for further assistance.