Protector Three Phase Adjustable V A Instruction Manual

Protector-logo

Protector Three Phase Adjustable V A

Protector-Three-Phase-Adjustable-V-A-product

Overview

The Three Phase Adjustable V/A Protector provides individually adjustable protection functions, including a power-on delay plus overvoltage, undervoltage, and overcurrent protections. Protection action times and recovery times can be set independently, and each protection function can be turned on or off.

Specifications

Rated supply voltage L-N: AC 230V / L-L: 380V
Operating voltage range L-N: AC 80V–300V
Rated frequency 50/60 Hz
Rated insulation voltage AC 450V
Output contact 3NO (Normally Open)
Voltage measurement accuracy ≤ 2% (across the entire spectrum)
Display / indicator L1: Yellow, L2: Green, L3: Red
Voltage display example 22.0V (as shown)
Current display example 63.0A (as shown)
Warning indicators >V (Overvoltage warning), >A (Overcurrent warning)
Controls SET (Settings key), ▲ (Adjusting key Up), ▼ (Adjusting key Down), POWER (Output prompt)

Quick Setup

  1. Use the SET key to enter settings.
  2. Use ▲ and ▼ to adjust protection-related values.
  3. Enable or disable each protection function individually (power-on delay, overvoltage, undervoltage, overcurrent).
  4. Independently set protection action times and recovery times for each enabled function.
  5. Use the indicator lights (L1/L2/L3) and the display/warnings (>V, >A) to monitor the device status.

Functions

  • Adjustable power-on delay
  • Adjustable overvoltage protection
  • Adjustable undervoltage protection
  • Adjustable overcurrent protection
  • All protections can be individually turned on or off
  • All protection action times and recovery times can be set independently

Technical Parameters

Parameter Value / Specification
Rated supply voltage L – N: AC 230V / L – L: 380V
Operating voltage range L – N: AC 80V – 300V
Rated frequency 50/60Hz
Rated insulation voltage AC 450V
Output contact 3NO (Normally Open)
Voltage measurement accuracy ≤2% (Across the entire spectrum)

Display PanelProtector-Three-Phase-Adjustable-V-A-fig- (1)

Indicator Light Status: L1: Yellow | L2: Green | L3: Red

Protector-Three-Phase-Adjustable-V-A-fig- (2)

Parameter Configuration

Code Option / Parameter Description Set Range Default Value
P1 Power-on delay 1 – 999 s 5s
P2 Overvoltage action value 130 – 300V – OFF 265V
P3 Overvoltage action time 0.1 – 30.0s 5s
P4 Overvoltage recovery value 125 – 295V 265V
P5 Overvoltage recovery time 1.0 – 500s 30s
P6 Undervoltage action value 80 – 210V – OFF 170V
P7 Undervoltage action time 0.1 – 60.0s 0.5s
P8 Undervoltage recovery value 85 – 215V 175V
P9 Undervoltage recovery time 1.0 – 500s 30s
P10 Overcurrent action value 1.0 – 63A / 80A / 100A 100A
P11 Overcurrent action time 0.1 – 30s 1.0s
P12 Overcurrent recovery time 1.0 – 500s 30s
P13 Overcurrent automatic closing attempts 1 – 20 – OFF 5
P14 Voltage sampling calibration coefficient -9.9% to +9.9% 0
P15 Current sampling calibration coefficient -9.9% to +9.9% 0
P16 Password settings 1 – 999 112

Product Dimensions

Protector-Three-Phase-Adjustable-V-A-fig- (3)

Wiring DiagramProtector-Three-Phase-Adjustable-V-A-fig- (4)

Troubleshooting

  • Overvoltage warning (>V) appears: Review and adjust the overvoltage protection settings (including whether overvoltage protection is enabled).
  • Overcurrent warning (>A) appears: Review and adjust the overcurrent protection settings (including whether overcurrent protection is enabled).
  • Unexpected protection behavior: Confirm that each protection function is set to the intended on/off state, and verify that the protection action time and recovery time values are set independently as required.