ProCon logo

ProCon® — D750 Series
Conductivity Controller
Quick Start Manual

ProCon D750 Series Conductivity Controller

Read the user’s manual carefully before starting to use the unit.
Producer reserves the right to implement changes without prior notice.

Technical Specifications

Measurement Range 0~2000ms/cm
Measurement Unit ms/cm
Resolution 0.01ms/cm
Basic Error ±3%
Temperature 14 ~ 302ºF | -10 ~ 150.0oC (Depends on the Sensor)
Temperature Resolution 0.1°C
Temperature Accuracy ±0.3°C
Temperature Compensation Manual | Automatic
Stability pH: ≤0.01pH/24h ; ORP: ≤1mV/24h
Current Output Line 2: 4~20mA, 20~4mA, 0~20mA
Communication Output RS485 MODBUS RTU
Three Relay Control Contacts 5A 250VAC, 5A 30VDC
Power Supply 9~36VDC | 85~265VAC | Power Consumption ≤ 3W
Working Conditions No strong magnetic field interference around except the geomagnetic field
Working Temperature 14 ~ 140oF | -10~60°C
Relative Humidity ≤90%
Waterproof Rating IP65
Dimensions 144 x 114 x 118mm
Mounting Panel | Wall Mount

Dimensions

ProCon D750 Series Conductivity Controller - Dimensions

Embedded Installation

ProCon D750 Series Conductivity Controller - Embedded Installation

Wall Mount Installation

ProCon D750 Series Conductivity Controller - Wall Mount Installation

Wiring

ProCon D750 Series Conductivity Controller - Wiring

Terminal Description
V+, V-, A1, B1 Digital Input Channel 1
V+, V-, A2, B2 Digital Input Channel 2
I1, G, I2 Output Current
A3, B3 RS485 Communication Output
G, TX, RX RS232 Communication Output
P+, P- VDC Power Supply
EC1,EC2,EC3,EC4 Conductivity/Resistivity Wiring
RLY3,RLY2,RLY1 Group 3 Relays
L,N, L- Live Wire | N- Neutral |  Ground
Terminal Description
REF1 Digital Input Channel 1
INPUT1 Digital Input Channel 2
TEMP1 Output Current
SEN-,SEN+ RS485 Communication Output
REF2 RS232 Communication Output
INPUT2 VDC Power Supply
TEMP2 Conductivity/Resistivity Wiring
GND Group 3 Relays
CE,RE,WE Constant Voltage for FCL/CLO2/O

The connection between the instrument and the sensor: the power supply, output signal, relay alarm contact and the connection between the sensor and the instrument are all inside the instrument, and the wiring is as shown above. The length of the cable lead fixed by the electrode is usually 5-10 Meters, insert the line with corresponding label or color wire on the sensor into the corresponding terminal inside the instrument and tighten it.

Keypad Description

ProCon D750 Series Conductivity Controller - Keypad Description 1

ProCon D750 Series Conductivity Controller - Keypad Description 2

ProCon D750 Series Conductivity Controller - Symbol 1 Short Press: Short Press means to release the key immediately after pressing. (Default to short presses if not included below)
ProCon D750 Series Conductivity Controller - Symbol 1 Long Press: Long Press is to press the button for 3 seconds and then release it.
ProCon D750 Series Conductivity Controller - Symbol 1 Press & Hold: Press and hold means to press the button, and accelerate after a certain time until the data is adjusted to the user’s required value before releasing the button

Display Descriptions
All pipe connections and electrical connections should be checked before use. After the power is switched on, the meter will display as follows.

ProCon D750 Series Conductivity Controller - Display Descriptions

ProCon D750 Series Conductivity Controller - Display Descriptions 1

Menu Structure

The following is the menu structure of this instrument

Setting Electrode Set Electrode Type Setting ms/cm
NaOH
NaCl
CaCl2
HCl
Units Setup %
ms/cm
Electrode Constant 2.7 (Default, can be modified)
Temperature Coefficient 2.0 (Default, can be modified)
Temperature Temperature Sensor PT1000
Temperature Offset 0.0000
Temperature Input Automatic
Manual
Temperature Unit oC
oF
Calibration Standard Solution Calibration Point 1 0.01 (Default, can be modified)
Point 2 1.0 (Default, can be modified)
Point 3 5.0 (Default, can be modified)
Point 4 10.0 (Default, can be modified)
Point 5 20.0 (Default, can be modified)
Calibration Adjustment Voltage 1
Voltage 2
Voltage 3
Voltage 4
Voltage 5
Field Calibration Field Calibration
Offset Adjustment
Slope Adjustment
Alarm Relay 1 On-Off State ON
OFF
Specify the type High Alarm
Low Alarm
Clean
Limit Setting (Open Time – Cleaning State) Continuous Opening Time
Lag (Off Time – In Cleaning State) The interval between the last opening and closing and the next opening
Relay 2 On-Off State ON
OFF
Specify the type High Alarm
Low Alarm
Clean
Limit Setting (Open Time – Cleaning State) Continuous Opening Time
Lag (Off Time – In Cleaning State) The interval between the last opening and closing and the next opening
Relay 3 On-Off State ON
OFF
Specify the type High Alarm
Low Alarm
Clean
Limit Setting (Open Time – Cleaning State) Continuous Opening Time
Lag (Off Time – In Cleaning State) The interval between the last opening and closing and the next opening
Output Current 1 Channel Main
Temperature
Output Option 4-20mA
0-20mA
20-4mA
Upper Limit
Lower Limit
Current 2 Channel Main
Temperature
Output Option 4-20mA
0-20mA
20-4mA
Upper Limit
Lower Limit
Output RS485 Baud Rate 4800BPS
9600BPS
19200BPS
Parity Check None
Odd
Even
Stop Bit 1 Bit
2 Bit
Network Node 001 +
Data Log Graphic Trend (Trend Chart) Interval/Point Display according to interval settings 480 points/ screen
1h/Point
12h/Point
24h/Point
Data Query Query by number of data Year/Month/Day, Time:Minutes:Seconds Value Unit
Record Interval 7.5s
90s
180s
Memory Information 101600 Point
Data Output
System Language English
Date/Time Year-Month-Day
Hour-Minute-Second
Display Display Speed Low
Standard
Medium
High
Backlight Saving
Bright
Range Set 1
2
3
Automatic
Software version Software Version 1.9-1.0
Password Settings 0000
Serial number
System Factory Default No
Yes
Terminal Current Tuning Current 1 | 4mA The positive and negative ends of the ammeter are connected to the current 1 or current 2 output termi- nals of the instrument respectively, press [Down] key to adjust the current to 4 mA or 20mA , press [ENT] key to confirm.
Current 1 | 20mA
Current 2 | 4mA
Current 2 | 20mA
Relay Test Relay 1 Select three groups of relays and hear the sound of two switches ,the relay is normal.
Relay 2
Relay 3

Calibration

Press [MENU] to enter the setting mode and select the calibration

Calibration Standard Solution Calibration Point 1 Enter given standard liquid value(Example:0.01)
Point 2 Enter given standard liquid value(Example:1.0)
Point 3 Enter given standard liquid value(Example:5.0)
Point 4 Enter given standard liquid value(Example:10.0)
Point 5 Enter given standard liquid value(Example:20.0)
Field Calibration
Offset Adjustment
Slope Adjustment

Standard Solution Calibration
This function is used to calibrate the five calibration points of the sensor. It has been calibrated before delivery and users can use it directly. If calibration is required, prepare 5 suitable standard liquids with known value, press [MENU] to enter the setting mode and select the calibration point.Modify or enter the corresponding calibration value.
After setting the calibration value, press [MENU] key returns to the measurement screen, and press [CAL] key to enter the standard solution calibration mode. Standard solution calibration has five points, and can be calibrated at any point (at least one point)..
If the instrument has been calibrated, press the [CAL] key to check the calibration state, press the [Down] key to switch the calibration state of the calibration point, and if the point shall be re-calibrated in this state, press [ENT] key to enter re-calibration.
If the monitor prompts you to enter the calibration safety password, press [Down] or [Right] key to set the calibration safety password, then press [ENT] to confirm the calibration safety password.

Point 1 Calibration
After entering the calibration mode, the instrument displays as shown in the figure. The main value of the instrument displays the known standard liquid value of point 2024-02-12 12:53:17
1. Place the electrode into the standard solution of the correspond- ing value, and the corresponding voltage mV value and calibration state will be displayed on the left side of the screen.
After completion of calibration, (Done) will be displayed on the right side of the screen.
If the next point is calibrated, press [Down] to switch the calibration point.
If only one point calibration is needed, after the calibration is completed, press [MENU] to exit.
During the calibration process, when the standard solution is wrong, the screen will show Error.

ProCon D750 Series Conductivity Controller - Point 1 Calibration

Field Calibration
Select field calibration methods: [Field calibration], [Offset adjustment], [linear adjustment].

ProCon D750 Series Conductivity Controller - Field Calibration

Offset Adjustment
Compare the data from portable instrument with the data measured by isntrument. if there is any error, the error data can be modified by this function.
Linear adjustment
Linear values after “field calibration” will be saved in this term and the factory data is 1.00.

Graphic Trend (Trend Chart)

Data Log Curve Query (Trend Chart) Interval/Point 400 points per screen, displays the most recent data trend graph according to interval settings
1h/point 400 points per screen, display trend chart of the last 16 days of data
12h/point 400 points per screen, display trend chart of the last 200 days of data
24h/point 400 points per screen, display trend chart of the last 400 days of data
Data Query Year/Month/Day Year/Month/day Time: Minute: Second Value Unit
Interval 7.5s Store Data Every 7.5 Seconds
90s Store Data Every 90 Seconds
180s Store Data Every 180 Seconds

Press the [MENU] button returns to the measurement screen. Press the [ Right/TREND] button in the measurement mode to view the trend chart of the saved data directly. There are 480 sets of data record per screen, and the interval time of each record can be selected [7.5s, 90s, 180s), corresponding to the data displayed in [1h, 12h, 24h] per screen.
Trend Chart Display

ProCon D750 Series Conductivity Controller - Graphic Trend

In the current mode, press the [ENT] key to move the data display line to the left and right (green) and display the data in left and right circles. Long pressing of the [ENT] key can accelerates displacement. (When the bottom Icons is green. [ENT] key is displacement direction, press [ Right/TREND] key to switch the direction of displacement)

MODBUS RTU
The hardware version number of this document is V2.0; the software version number is V5.9 and above. This document describes the MODBUS RTU interface in details and the target object is a software programmer.

MODBUS Command Structure

Data format description in this document;
Binary display, suffix B, for example: 10001B – decimal display, without any prefix or suffix, for example: 256 Hexadecimal display, prefix 0x, for example: 0x2A ASCII character or ASCII string display, for example: “YL0114010022”
Command Structure
The MODBUS application protocol defines the Simple Protocol Data Unit (PDU), which is independent of the underlying communication layer.

ProCon D750 Series Conductivity Controller - MODBUS Protocol Data Unit

MODBUS protocol mapping on a specific bus or network introduces additional fields of protocol data units. The client that initiates the MODBUS exchange creates the MODBUS PDU, and then adds the domain to establish the correct communication PDU.

ProCon D750 Series Conductivity Controller - MODBUS Architecture for Serial Communication

On the MODBUS serial line, the address domain contains only the slave instrument address. Tips: The device address range is 1…247
Set the device address of the slave in the address field of the request frame sent by the host. When the slave instrument responds, it places its instrument address in the address area of the response frame so that the master station knows which slave is responding.
Function codes indicate the type of operation performed by the server.
CRC domain is the result of the “ redundancy check” calculation, which is executed according to the information content.

MODBUS RTU Transmission Mode

When the instrument uses RTU (Remote Terminal Unit) mode for MODBUS serial communication, each 8-bit byte of information contains two 4-bit hexadecimal characters. The main advantages of this mode are greater character density and better data throughput than the ASCII mode with the same baud rate. Each message must be transmitted as a continuous string.

The format of each byte in RTU mode (11 bits):
■ Coding system: 8-bit binary
■ Each 8-bit byte in a message contains two 4-bit hexadecimal characters (0-9, A-F)
■ Bits in each byte: 1 starting bit
■ 8 data bits, the first minimum valid bits without parity check bits
■ 2 stop bits
■ Baud rate: 9600 BPS

How characters are transmitted serially:
Each character or byte is sent in this order (from left to right) the least significant bit (LSB)… Maximum Significant Bit (MSB)

ProCon D750 Series Conductivity Controller - Transmission Mode

Check Domain Structure: Cyclic Redundancy Check (CRC16)

Structure description:

Slave Instrument Address Data CRC
1 byte 1 byte 0…252 byte 2 byte
CRC Low byte | CRC High byte

Fig.4 : RTU Information Structure

The maximum frame size of MODBUS is 256 bytes
MODBUS RTU Information Frame
In RTU mode, message frames are distinguished by idle intervals of at least 3.5 character times, which are called t3.5 in subsequent sections.

ProCon D750 Series Conductivity Controller - RTU Message Frame

The entire message frame must be sent in a continuous character stream. When the pause time interval between two characters exceeds 1.5 characters, the information frame is considered incomplete and the receiver does not receive the information frame.

ProCon D750 Series Conductivity Controller - Frame

MODBUS RTU CRC Check
The RTU mode contains an error-detection domain based on a cyclic redundancy check (CRC) algorithm that performs on all message contents. The CRC domain checks the contents of the entire message and performs this check regardless of whether the message has a random parity check. The CRC domain contains a 16-bit value consisting of two 8-bit bytes. CRC16 check is adopted. Low bytes precede, high bytes precede.

Implementation of MODBUS RTU in Instrument
According to the official MODBUS definition, the command starts with a 3.5 character interval triggering command, and the end of the command is also represented by a 3.5 character interval. The device address and MODBUS function code have 8 bits. The data string contains n*8 bits, and the data string contains the starting address of the register and the number of read/write registers. CRC check is 16 bits.

Value Start Device Address Function Data Summary Check End
No Signal bytes during 3.5 Characters 1-247 1 Function Codes Confirming to MODBUS Specification Data Confirming to MODBUS Specification CRCL CRCL No Signal bytes during 3.5 char- acters
Byte 3.5 1 N 1 1 3.5

Fig.7 : MODBUS definition of Data Transmission

Instrument MODBU RTU Function Code
The instrument only uses two MODBUS function codes:
0x03: Read-and-hold register
0x10: Write multiple registers
MODBUS Function Code 0x03: Read-and-hold Register
This function code is used to read the continuous block content of the holding register of the remote device. Request the PDU to specify the start register address and the number of registers. Address registers from zero. Therefore, the addressing register 1-16 is 0-15. The register data in the response information is packaged in two bytes per register. For each register, the first byte contains high bits and the second byte contains low bits.

Request:

Function Code 1 byte 0x03
Start Address 2 byte 0x0000   0xfffff
Read Register Number 2 byte 1…125

Fig.8 : Read and hold register request frame

Response:

Function Code 1 byte 0x03
Number of bytes 2 bytes 0x0000   0xfffff
Read Register Number 2 bytes 1…125

N = Register Number
Figure 9 : Read and hold register response frame
The following illustrates the request frame and response frame with the read and hold register 108-110 as an example. (The contents of register 108 are read-only, with two byte values of 0X022B, and the contents of register 109-110 are 0X0000 and 0X0064)

Request Frame Response Frame
Number Systems (Hexadecimal) Function Code (Hexadecimal)
Function Code 0x03 Byte Count 0x03
Start Address (High byte) 0x00 Register Value (High Bytes) (108) 0x06
Start Address (Low byte) 0x6B Register Value (Low Bytes) (108) 0x02
Number of Read Registers (High Bytes) 0x00 Register Value (High Bytes) (109) 0x2B
Number of Read Registers (Low Bytes) 0x00 Register Value (Low Bytes) (109) 0x00
Register Value (High Bytes) (110) 0x00
Register Value (Low Bytes) (110) 0x00
Function Code 0x64

Figure 10 : Examples of read and hold register request and response frames

MODBUS Function Code 0x10 : Write Multiple Registers

This function code is used to write continuous registers to remote devices (1… 123 registers) block that specifies the value of the registers written in the request data frame. Data is packaged in two bytes per register. Response frame return function code, start address and number of registers written.

Request:

Function Code 1 byte 0x10
Start Address 2 byte 0x0000   0xfffff
Number of input registers 2 byte 0x0001. 0x0078
Number of bytes 1 byte Nx2
Register Values N x 2 bytes Value

Fig.11 : Write Multiple Register Request Frames

Response:

Function Code 1 byte 0x10
Start Address 2 byte 0x0000   0xffff
Register Number 2 byte 1…123(0x7B)

N = Register Number
Figure 12 : Write Multiple Register Response Frames
The request frame and response frame are illustrated below in two registers that write the values 0x000A and 0x0102 to the start address of 2.

Response Frame (Hexadecimal) Response Frame (Hexadecimal)
Number Systems 0x10 Number Systems 0x10
Function Code 0x00 Function Code 0x00
Start Address (High byte) 0x01 Start Address (High byte) 0x01
Start Address (Low byte) 0x00 Start Address (Low byte) 0x00
Input Register Number (High bytes) 0x02 Input Register Number (High bytes) 0x02
Input Register Number (Low bytes) 0x04 Input Register Number (Low bytes)
Number of bytes 0x00
Register Value (High byte) 0x0A
Register Value (Low byte) 0x01
Register Value (High byte) 0x02
Register Value (Low byte)

Figure 13 : Examples of writing multiple register request and response frames

Data Format in Instrument

Floating Point
Definition: Floating point, conforming to IEEE 754 (single precision)

Description Symbol Index Mantissa SUM
Bit 31 30…23 22…0 22…0
Index Deviation 127

Figure 14 : Floating Point Single Precision Definition (4 bytes, 2 MODBUS Registers)
Example: Compile decimal 17.625 to binary
Step 1:
Converting 17.625 in decimal form to a floating-point number in binary form, first finding the binary representation of the integer part 17decimal= 16 + 1 = 1×24 + 0×23 + 0×22 + 0×21 + 1×20
The binary representation of integer part 17 is 10001B then the binary representation of decimal part is obtained 0.625= 0.5 + 0.125 = 1×2−1 + 0×2−2 + 1×2−3
The binary representation of decimal part 0.625 is 0.101B.
So the binary floating point number of 17.625 in decimal form is 10001.101B

Step 2:
Shift to find the exponent.
Move 10001.101B to the left until there is only one decimal point, resulting in 1.0001101B, and
10001.101B = 1.0001101 B× 24 . So the exponential part is 4, plus 127, it becomes 131, and its binary representation is 10000011B.
Step 3:
Calculate the tail number
After removing 1 before the decimal point of 1.0001101B, the final number is 0001101B (because before the decimal point must be 1, so IEEE stipulates that only the decimal point behind can be recorded). For the important explanation of 23-bit mantissa, the first (i.e. hidden bit) is not compiled. Hidden bits are bits on the left side of the separator, which are usually set to 1 and suppressed.
Step 4:
Symbol bit definition
The sign bit of positive number is 0, and the sign bit of negative number is 1, so the sign bit of 17.625 is 0.

Step 5:
Convert to floating point number
1 bit symbol + 8 bit index + 23-bit mantissa
0 10000011 00011010000000000000000B (the hexadecimal system is shown as 0 x418d0000 )
Reference code:
1. If the compiler used by the user has a library function that implements this function, the library function can be called directly, for example, using C language, then you can directly call the C library function memcpy to obtain an integer representation of the floating-point storage format in memory.
For example: float floatdata; // converted floating point number void* outdata; memcpy(outdata,&floatdata,4);
Suppose floatdata = 17.625
If it is a small-end storage mode, after executing the above statement, the data stored in the address unit outdata is 0x00.
address unit (outdata + 1) stores data as 0x00
address unit (outdata + 2) stores data as 0x8D
address unit (outdata + 3) stores data as 0x41
If it is large-end storage mode, after executing the above statement, the data stored in outdata of address unit is 0x41
address unit (outdata + 1) stores data as 0x8D
address unit (outdata + 2) stores data as 0x00
address unit (outdata + 3) stores data as 0x00
2. If the compiler used by the user does not implement the library function of this function, the following functions can
be used to achieve this function:
void memcpy(void *dest,void *src,int n)
{
char *pd = (char *)dest; char *ps = (char *)src; for (int i=0;i<n;i++) *pd++ = *ps++;
}
And then make a call to the above memcpy(outdata,&floatdata,4);
Example: Compile binary floating-point number 0100 0010 0111 1011 0110 0110 0110 10B to decimal number
Step 1: Divide the binary floating-point number 0100 0010 0111 1011 0110 0110 0110B into symbol bit, exponential bit and mantissa bit.
0
10000100
11110110110011001100110B
1-bit sign + 8-bit index + 23-bit tail sign bit S: 0 denotes positive number
Index position E: 10000100B =1×27+0×26+0×25+0×24 + 0 × 23+1×22+0×21+0×20
=128+0+0+0+0+4+0+0=132
Mantissa bits M: 11110110110011001100110B =8087142
Step 2: Calculate the decimal number
D = (−1)×(1.0 + M/223)×2E−127
= (−1)0×(1.0 + 8087142/223)×2132−127
= 1×1.964062452316284×32
= 62.85

Reference Code:
float floatTOdecimal(long int byte0, long int byte1, long int byte2, long int byte3)
{
long int realbyte0,realbyte1,realbyte2,realbyte3; char S; long int E,M;
float D; realbyte0 = byte3; realbyte1 = byte2; realbyte2 = byte1; realbyte3 = byte0;
if((realbyte0&0x80)==0)
{
S = 0;//positive number
}
else
{
S = 1;//negative number
}
E = ((realbyte0<<1)|(realbyte1&0x80)>>7)-127;
M = ((realbyte1&0x7f) << 16) | (realbyte2<< 8)| realbyte3;
D = pow(-1,S)*(1.0 + M/pow(2,23))* pow(2,E); return D;
}
Function description: parameters byte0, byte1, byte2, byte3 represent 4 bytes of binary floating point number.
The decimal number converted from the return value.
For example, the user sends the command to get the temperature value and dissolved oxygen value to the probe. The4 bytes representing the temperature value in the received response frame are 0x00, 0x00, 0x8d and 0x41. Then the user can get the decimal number of the corresponding temperature value through the following call statement.
That is temperature = 17.625.
float temperature = floatTOdecimal( 0x00, 0x00, 0x8d, 0x41)

Read Instruction Mode

The communication protocol adopts MODBUS (RTU) protocol. The content and address of the communication can be changed according to the needs of customers. The default configuration is network address 01, baud rate 9600, even check, one stop bit, users can set their own changes;
Function code 0x04: This function enables the host to obtain real-time measurements from slaves, which are specified as single-precision floating-point type (i.e. occupying two consecutive register addresses), and to mark the corresponding parameters with different register addresses. Communication address is as follows:
0000-0001: Temperature value | 0002-0003: Main Measured Value | 0004-0005: Temperature and Voltage Value | 0006-0007: Main Voltage Value

Communication examples:
Examples of function code 04 instructions:
Communication address = 1, temperature = 20.0, ion value = 10.0, temperature voltage = 100.0, ion voltage = 200.0
Host Send: 01 04 00 00 08 F1 CC | Slave Response: 01 04 10 00 41 A0 00 41 20 00 42 C8 00 43 48 81 E8
Note:
[01] Represents the instrument communication address;
[04] Represents function code 04;
[10] represents 10H (16) byte data;
[00 00 00 41 A0] = 20.0; / temperature value
[00 00 4120]= 10.0; // Main Measured Value
[00 00 42 C8] = 100.0; / / Temperature and Voltage Value
[00 00 43 48] = 200.0; / / Main measured voltage value
[81 E8] represents CRC16 check code;

Maintenance

According to the requirements of use, the installation position and working condition of the instrument are relatively complex. In order to ensure that the instrument is working normally, maintenance personnel should carry out regular maintenance on the instrument. Please pay attention to the following matters during maintenance:

■ Check the working environment of the instrument. If the temperature exceeds the rated range of the instrument, please take appropriate measures; otherwise, the instrument may be damaged or its service life may be reduced;
■ When cleaning the plastic shell of the instrument, please use a soft cloth and a soft cleaner to clean the shell.
■ Check whether the wiring on the terminal of the instrument is firm. Pay attention to disconnect the AC or DC power before removing the wiring cover.

Warranty, Returns and Limitations

Warranty
Icon Process Controls Ltd warrants to the original purchaser of its products that such products will be free from defects in material and workmanship under normal use and service in accordance with instructions furnished by Icon Process Controls Ltd for a period of one year from the date of sale of such products. Icon Process Controls Ltd obligation under this warranty is solely and exclusively limited to the repair or replacement, at Icon Process Controls Ltd option, of the products or components, which Icon Process Controls Ltd examination determines to its satisfaction to be defective in material or workmanship within the warranty period. Icon Process Controls Ltd must be notified pursuant to the instructions below of any claim under this warranty within thirty (30) days of any claimed lack of conformity of the product. Any product repaired under this warranty will be warranted only for the remainder of the original warranty period. Any product provided as a replacement under this warranty will be warranted for the one year from the date of replacement.

Returns
Products cannot be returned to Icon Process Controls Ltd without prior authorization. To return a product that is thought to be defective, go to www.iconprocon.com, and submit a customer return (MRA) request form and follow the instructions therein. All warranty and non-warranty product returns to Icon Process Controls Ltd must be shipped prepaid and insured. Icon Process Controls Ltd will not be responsible for any products lost or damaged in shipment.

Limitations
This warranty does not apply to products which: 1) are beyond the warranty period or are products for which the original purchaser does not follow the warranty procedures outlined above; 2) have been subjected to electrical, mechanical or chemical damage due to improper, accidental or negligent use; 3) have been modified or altered; 4) anyone other than service personnel authorized by Icon Process Controls Ltd have attempted to repair; 5) have been involved in accidents or natural disasters; or 6) are damaged during return shipment to Icon Process Controls Ltd reserves the right to unilaterally waive this warranty and dispose of any product returned to Icon Process Controls Ltd where: 1) there is evidence of a potentially hazardous material present with the product; or 2) the product has remained unclaimed at Icon Process Controls Ltd for more than 30 days after Icon Process Controls Ltd has dutifully requested disposition. This warranty contains the sole express warranty made by Icon Process Controls Ltd in connection with its products. ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE EXPRESSLY DISCLAIMED. The remedies of repair or replacement as stated above are the exclusive remedies for the breach of this warranty. IN NO EVENT SHALL Icon Process Controls Ltd BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING PERSONAL OR REAL PROPERTY OR FOR INJURY TO ANY PERSON. THIS WARRANTY CONSTITUTES THE FINAL, COMPLETE AND EXCLUSIVE STATEMENT OF WARRANTY TERMS AND NO PERSON IS AUTHORIZED TO MAKE ANY OTHER WARRANTIES OR  REPRESENTATIONS ON BEHALF OF Icon Process Controls Ltd. This warranty will be interpreted pursuant to the laws of the province of Ontario, Canada.
If any portion of this warranty is held to be invalid or unenforceable for any reason, such finding will not invalidate any other provision of this warranty.
For additional product documentation and technical support visit:
www.iconprocon.com | e-mail: sales@iconprocon.com or support@iconprocon.com | Ph: 905.469.9283

ProCon logo 2

https://iconprocon.com

Documents / Resources

ProCon D750 Series Conductivity Controller [pdf] Instruction Manual
D750 Series, D750 Series Conductivity Controller, Conductivity Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *