PR Electronics 5333 2-Wire Programmable Transmitter
- Product Name: 2-wire programmable transmitter 5333
- Model Number: 5333V120-UK
- Features: Temperature, I.S. Interfaces, Communication Interfaces, Multifunctional, Isolation, Display
- Patented Technologies: Innovative signal conditioning for smarter operation
- Warranty: 5-year warranty for reliability
Product Information
The 2-wire programmable transmitter 5333 is designed to provide high signal integrity for industrial process temperature signals. It offers fast response time, automatic self-calibration, sensor error detection, low drift, and top EMC performance in any environment. The transmitter can convert temperature signals to analog, bus, or digital communications and is suitable for a wide range of applications in industrial and factory automation.
Product Usage Instructions
Mounting/Installation:
The 5333 transmitter should be mounted securely in a suitable location near the measurement point using appropriate mounting hardware.Ensure proper electrical connections are made according to the specific application requirements.
Applications:
The transmitter is versatile and can be used for converting RTD to 4-20mA or resistance to 4-20mA signals. It can be easily integrated into control room installations for monitoring and control purposes.
- Q: What are the key features of the 5333 transmitter?
A: The key features include fast response time, automatic self-calibration, sensor error detection, low drift, top EMC performance, and compatibility with various communication interfaces. - Q: Can the 5333 transmitter be used in hazardous environments?
A: Yes, the transmitter is suitable for hazardous environments and complies with Zone 2/Div. 2 standards. - Q: How can I configure the communication interfaces of the 5333 transmitter?
A: The interfaces can be configured via push-buttons and offer options for Modbus, Bluetooth communication, and remote access using the PR Process Supervisor application.
Product manual 5333
2-wire programmable transmitter6 Product Pillars to meet your every need
Individually outstanding, unrivalled in combination
With our innovative, patented technologies, we make signal conditioning smarter and simpler. Our portfolio is composed of six product areas, where we offer a wide range of analog and digital devices covering over a thousand applications in industrial and factory automation. All our products comply with or surpass the highest industry standards, ensuring reliability in even the harshest of environments and have a 5-year warranty for greater peace of mind.
Our range of temperature transmitters and sensors provides the highest level of signal integrity from the measurement point to your control system. You can convert industrial process temperature signals to analog, bus or digital communications using a highly reliable point-to-point solution with a fast response time, automatic self-calibration, sensor error detection, low drift, and top EMC performance in any environment.
We deliver the safest signals by validating our products against the toughest safety standards. Through our commitment to innovation, we have made pioneering achievements in developing I.S. interfaces with SIL 2 Full Assessment that are both efficient and cost-effective. Our comprehensive range of analog and digital intrinsically safe isolation barriers offers multifunctional inputs and outputs, making PR an easy-to-implement site standard. Our backplanes further simplify large installations and provide seamless integration to standard DCS systems.
We provide inexpensive, easy-to-use, future-ready communication interfaces that can access your PR installed base of products. All the interfaces are detachable, have a built-in display for readout of process values and diagnostics, and can be configured via push-buttons. Product specific functionality includes communication via Modbus and Bluetooth and remote access using our PR Process Supervisor (PPS) application, available for iOS and Android.
Our unique range of single devices covering multiple applications is easily deployable as your site standard. Having one variant that applies to a broad range of applications can reduce your installation time and training, and greatly simplify spare parts management at your facilities. Our devices are designed for long-term signal accuracy, low power consumption, immunity to electrical noise and simple programming.
Our compact, fast, high-quality 6 mm isolators are based on microprocessor technology to provide exceptional performance and EMC-immunity for dedicated applications at a very low total cost of ownership. They can be stacked both vertically and horizontally with no air gap separation between units required.
Our display range is characterized by its flexibility and stability. The devices meet nearly every demand for display readout of process signals and have universal input and power supply capabilities. They provide a real-time measurement of your process value no matter the industry and are engineered to provide a user-friendly and reliable relay of information, even in demanding environments.
2-wire programmable transmitter 5333
- RTD or Ohm input
- High measurement accuracy
- 3-wire connection
- Programmable sensor error value
- For DIN form B sensor head mountings
Application
- Linearised temperature measurement with Pt100… Pt1000 or Ni100…Ni1000 sensor.
- Conversion of linear resistance variation to a standard analog current signal, for instance from valves or Ohmic level sensors.
Technical characteristics
- Within a few seconds, the user can program PR5333 to measure temperatures within all RTD ranges defined by the norms.
- The RTD and resistance inputs have cable compensation for a 3-wire connection.
Mounting/installation
- For DIN form B sensor head mounting. In non-hazardous areas, the 5333 can be mounted on a DIN rail with the PR fitting type 8421.
Applications
Order
Type | Version |
5333 |
|
Accessories
5909 = Loop Link USB interface and PReset Software
Electrical specifications Environmental conditions:
- Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40°C to +85°C
- Calibration temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20…28°C
- Humidity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond.) Protection degree, enclosure / terminals. . . . . . . . . . . . . . . . . . . . . . IP68 / IP00
Mechanical specifications:
- Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ø 44 x 20.2 mm
- Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 g
- Max. wire size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 x 1.5 mm2 stranded wire Screw terminal torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.4 Nm
- Vibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 60068-2-6
- 2…25 Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1.6 mm
- 25…100 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±4 g
Common specifications:
- Supply voltage, DC
- 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0…35 VDC 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0…30 VDC Internal power dissipation
- 5333A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 mW…0.8 W 5333D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 mW…0.7 W
- Voltage drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0 VDC Warm-up time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 min.
- Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Loop Link
- Signal / noise ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 60 dB
- Response time (programmable) . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.33…60 s
- Signal dynamics, input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 bit
- Signal dynamics, output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 bit
- Effect of supply voltage variation . . . . . . . . . . . . . . . . . . . . . . . . . . < 0.005% of span / VDC
Accuracy, the greater of general and basic values:
General values | ||
Input type | Absolute accuracy | Temperature coefficient |
All | ≤ ±0.1% of span | ≤ ±0.01% of span / °C |
Basic values | ||
Input type | Basic accuracy | Temperature coefficient |
RTD | ≤ ±0.3°C | ≤ ±0.01°C/°C |
Lin. R | ≤ ±0.2 Ω | ≤ ±20 mn / °C |
EMC – immunity influence. . . . . . . . . . . . . . . . . . . . . . . . . < ±0.5% of span
Electrical specifications, input:
RTD and linear resistance input:
RTD
type |
Min. value | Max. value | Min. span |
Standard |
Pt100…Pt1000 | -200°C | +850°C | 25°C | IEC 60751 |
Ni100…Ni1000 | -60°C | +250°C | 25°C | DIN 43760 |
Linear resistance | 0 Ω | 10000 Ω | 30 Ω | —– |
- Max. offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50% of selec. max. value
- Cable resistance per wire (max.) . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Ω
- Sensor current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 0.2 mA, < 0.4 mA
- Cable resistance per wire (max.) . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Ω
- Sensor current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 0.2 mA, < 0.4 mA
Output:
Current output:
- Signal range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4…20 mA
- Min. signal range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 mA
- Updating time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 ms
- Load resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ (Vsupply – 8.0) / 0.023 [Ω]
- Load stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.01% of span / 100 Ω
Sensor error detection:
- Programmable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5…23 mA
- NAMUR NE43 Upscale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 mA
- NAMUR NE43 Downscale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 mA Of span = Of the presently selected range
Observed authority requirements:
- EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/30/EU & UK SI 2016/1091
- ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/34/EU & UK SI 2016/1107
- RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2011/65/EU & UK SI 2012/3032
- EAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TR-CU 020/2011
- EAC Ex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TR-CU 012/2011
Marine approval:
DNV, Ships & Offshore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TAA0000101
Ex / I.S. approvals:
5333A:
- ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEKRA 20ATEX0106X 5333D:
- ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEKRA 20ATEX0105X
- FM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FM17US0013X
- 5333A & 5333D:
- IECEx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEK 20.0062X
- CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1125003
- INMETRO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEKRA 23.0010X
- EAC Ex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RU C-DK.НА65.В.00355/19
Connections
Block diagram
Programming
- Loop Link is a communications interface that is needed for programming 5333.
- For programming please refer to the drawing below and the help functions in PReset.
- Loop link is not approved for communication with modules installed in harzardous (Ex) areas.
ATEX-installation drawing 5333QA02-V3R0
For safe installation of 5333A the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.
ATEX Certificate Marking
DEKRA 20ATEX0106 X
Marking
- II 3 G Ex nA [ic] IIC T6 … T4 Gc
- II 3 G Ex ec [ic] IIC T6 … T4 Gc
- II 3 G Ex ic IIC T6 … T4 Gc
- II 3 D Ex ic IIIC Dc
Standards
- EN 60079-0: 2018, EN 60079-11: 2012,
- EN 60079-15: 2010, EN 60079-7:2015 +A1: 2018
Terminal 3,4,6 | Terminal 1,2 | Terminal 1,2 | Terminal 1,2 |
Ex ic IIC,Ex ic IIIC | Ex ic IIC,Ex ic IIIC | Ex ic IIC,Ex ic IIIC | Ex nA, Ex ec |
Uo: 5 V
Io: 4.0 mA Po: 20 mW Lo: 900 mH Co: 1000 μF |
Ui = 35 V
Ii = 110 mA Ci = 1 nF Li = 10 μH |
Ui = 24 V
Ii = 260 mA Ci = 1 nF Li = 10 μH |
Umax ≤ 35 VDC or
Umax ≤ 24 VDC |
Ex ic IIC, Ex ic IIIC Temperature Class | Ambient temperature range | |
Ui=35 V | Ui=24 V | |
T6 | -40°C to +54°C | -40°C to +63°C |
T5 | -40°C to +69°C | -40°C to +78°C |
T4 | -40°C to +85°C | -40°C to +85°C |
Ex ec, Ex nA Temperature Class | Ambient temperature range | |
Vmax=35 V | Vmax=24 V | |
T6 | -40°C to +43°C | -40°C to +55°C |
T5 | -40°C to +85°C | -40°C to +85°C |
T4 | -40°C to +85°C | -40°C to +85°C |
Installation notes
- If the enclosure is made of non-metallic plastic materials, electrostatic charges on the transmitter enclosure shall be avoided.
If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Gc and applied in type of protection Ex ic, the transmitter shall be mounted in an enclosure that provides a degree of protection of at least IP20 according to EN 60529, and that is suitable for the application and correctly installed. - If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Dc, the transmitter shall be mounted in a separately certified enclosure that provides a degree of protection of at least IP5X according to EN 60079-0, and that is suitable for the application and correctly installed. The surface temperature of the outer enclosure is +20 K above the ambient temperature, determined without a dust layer.
Ambient temperature range: -40°C to +85°C. - If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Gc and applied in type of protection Ex nA or Ex ec, the transmitter shall be mounted in a separately certified enclosure that provides a degree of protection of at least IP54 according to EN 60079-0, and that is suitable for the application and correctly installed.
- If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Gc and applied in type of protection Ex nA or Ex ec, the equipment shall only be used in an area of not more than pollution degree 2, as defined in EN 60664-1.
ATEX-installation drawing 5333QA01-V3R0
For safe installation of 5333D the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.
ATEX Certificate DEKRA 20ATEX0105 X
Marking
- II 1 G Ex ia IIC T6…T4 Ga
- II 2 D Ex ia IIIC Db
- I M1 Ex ia I Ma
Standards EN 60079-0: 2018, EN 60079-11: 2012
Temperature Class | Ambient temperature range | |
Pi: 0.84 W | Pi: 0.75 W | |
T6 | -40°C to +47°C | -40°C to +50°C |
T5 | -40°C to +62°C | -40°C to +65°C |
T4 | -40°C to +85°C | -40°C to +85°C |
Installation notes
- If the enclosure is made of non-metallic plastic materials, electrostatic charges on the transmitter enclosure shall be avoided.
- If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Ga, the transmitter shall be mounted in an enclosure that provides a degree of protection of at least IP20 according to EN 60529, and that is suitable for the application and correctly installed.
- If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Ga or Ma, and if the enclosure is made of aluminum, it must be installed such, that ignition sources due to impact and friction sparks are excluded.
- If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Db, the transmitter shall be mounted in a separately certified enclosure that provides a degree of protection of at least IP5X according to EN 60079-0, and that is suitable for the application and correctly installed. The surface temperature of the outer enclosure is +20 K above the ambient temperature, determined without a dust layer.
- Ambient temperature range: -40°C to +85°C.
- If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Ma, the transmitter shall be mounted in an enclosure that provides a degree of protection of at least IP54 according to EN 60529, and that is suitable for the application and correctly installed. Ambient temperature range: -40°C to +85°C.
- Cable entries and blanking elements shall be used that are suitable for the application and correctly installed.
- For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least 20 K above the ambient temperature.
IECEx-installation drawing 5333QI02-V3R0
For safe installation of 5333A the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.
Certificate IECEx DEK 20.0062X
Marking
- Ex nA [ic] IIC T6 … T4 Gc
- Ex nA [ic] IIC T6 … T4 Gc
- Ex ic IIC T6 … T4 Gc
- Ex ic IIC T6 … T4 Gc
Standards
- IEC 60079-0: 2017, IEC 60079-11: 2011,
- IEC 60079-15: 2010, IEC 60079-7:2017
Terminal 3,4,5,6 | Terminal 1,2 | Terminal 1,2 | Terminal 1,2 |
Ex ic IIC,Ex ic IIIC | Ex ic IIC,Ex ic IIIC | Ex ic IIC,Ex ic IIIC | Ex nA, Ex ec |
Uo: 5 V
Io: 4 mA Po: 20 mW Lo: 900 mH Co: 1000 μF |
Ui = 35 V
Ii = 110 mA Ci = 1 nF Li = 10 μH |
Ui = 24 V
Ii = 260 mA Ci = 1 nF Li = 10 μH |
Umax ≤ 35 VDC or
Umax ≤ 24 VDC |
Ex ic IIC, Ex ic IIIC Temperature Class | Ambient temperature range | |
Ui=35 V | Ui=24 V | |
T6 | -40°C to +54°C | -40°C to +63°C |
T5 | -40°C to +69°C | -40°C to +78°C |
T4 | -40°C to +85°C | -40°C to +85°C |
Ex ec, Ex nA Temperature Class | Ambient temperature range | |
Vmax=35 V | Vmax=24 V | |
T6 | -40°C to +43°C | -40°C to +55°C |
T5 | -40°C to +85°C | -40°C to +85°C |
T4 | -40°C to +85°C | -40°C to +85°C |
Installation notes
If the enclosure is made of non-metallic plastic materials, electrostatic charges on the transmitter enclosure shall be avoided.
If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Gc and applied in type of protection Ex ic, the transmitter shall be mounted in an enclosure that provides a degree of protection of at least IP20 according to IEC 60529, and that is suitable for the application and correctly installed.
If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Dc, the transmitter shall be mounted in a separately certified enclosure that provides a degree of protection of at least IP5X according to IEC 60079-0, and that is suitable for the application and correctly installed. The surface temperature of the outer enclosure is +20 K above the ambient temperature, determined without a dust layer.
Ambient temperature range: -40°C to +85°C.
If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Gc and applied in type of protection Ex nA or Ex ec, the transmitter shall be mounted in a separately certified enclosure that provides a degree of protection of at least IP54 according to IEC 60079-0, and that is suitable for the application and correctly installed. If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Gc and applied in type of protection Ex nA or Ex ec, the equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC 60664-1.
IECEx-installation drawing 5333QI01-V3R0
For safe installation of 5333D the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.
Certificate IECEx DEK 20.0062X
Marking
- Ex ia IIC T6…T4 Ga
- Ex ia IIIC Db
- Ex ia I Ma
Standards IEC 60079-0: 2017, IEC 60079-11: 2011
Temperature Class | Ambient temperature range | |
Pi: 0.84 W | Pi: 0.75 W | |
T6 | -40°C to +47°C | -40°C to +50°C |
T5 | -40°C to +62°C | -40°C to +65°C |
T4 | -40°C to +85°C | -40°C to +85°C |
Installation notes
- If the enclosure is made of non-metallic plastic materials, electrostatic charges on the transmitter enclosure shall be avoided.
- If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Ga, the transmitter shall be mounted in an enclosure that provides a degree of protection of at least IP20 according to IEC 60529, and that is suitable for the application and correctly installed.
- If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Ga or Ma, and if the enclosure is made of aluminum, it must be installed such, that ignition sources due to impact and friction sparks are excluded.
- If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Db, the transmitter shall be mounted in a separately certified enclosure that provides a degree of protection of at least IP5X according to IEC 60079-0, and that is suitable for the application and correctly installed. The surface temperature of the outer enclosure is +20 K above the ambient temperature, determined without a dust layer.
- Ambient temperature range: -40°C to +85°C.
- If the transmitter is installed in an explosive atmosphere requiring the use of equipment protection level Ma, the transmitter shall be mounted in an enclosure that provides a degree of protection of at least IP54 according to IEC 60529, and that is suitable for the application and correctly installed. Ambient temperature range: -40°C to +85°C.
- Cable entries and blanking elements shall be used that are suitable for the application and correctly installed.
- For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of at least 20 K above the ambient temperature.
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
FM Installation Drawing
Model 5331D, 5332D, 5333D and 5343B
Model 5335D, 5337D
The entity concept
The Transmitter must be installed according to National Electrical Code (ANSI-NFPA 70) and shall be installed with the enclosure, mounting, and spacing segregation requirement of the ultimate application.
Equipment that is FM-approved for intrinsic safety may be connected to barriers based on the ENTITY CONCEPT. This concept permits the interconnection of approved transmitters, meters, and other devices in combinations that have not been specifically examined by FM, provided that the agency’s criteria are met. The combination is then intrinsically safe if the entity concept is acceptable to the authority having jurisdiction over the installation.
The entity concept criteria are as follows:
- The intrinsically safe devices, other than barriers, must not be a source of power.
- The maximum voltage Ui(VMAX) and current Ii(IMAX), and maximum power Pi(Pmax), which the device can receive and remain intrinsically safe, must be equal to or greater than the voltage (Uo or VOC or Vt) and current (Io or ISC or It) and the power Po which can be delivered by the barrier.
- The sum of the maximum unprotected capacitance (Ci) for each intrinsic device and the interconnect-ing wiring must be less than the capacitance (Ca) which can be safely connected to the barrier.
- The sum of the maximum unprotected inductance (Li) for each intrinsic device and the interconnecting wiring must be less than the inductance (La) which can be safely connected to the barrier.
- The entity parameters Uo, VOC or Vt and Io, ISC or It, and Ca and La for barriers are provided by the barrier manufacturer.
NI Field Circuit Parameters
Model 5331D, 5332D, 5333D, 5335D, 5337D and 5343B
CSA Installation drawing 5333QC02
For safe installation of the 5333A the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area.
Marking
- Class I, Division 2, Group A,B,C,D T6…T4
- Ex nA[ic] IIC T6…T4
- Class I Zone 2 AEx nA[ic] IIC T6…T4
Hazardous Area
- CL I, Div 2, GP ABCD
- CL I, Zone 2, IIC
- T4: -40ºC to 85 ºC
- T6: -40ºC to 60 ºC
NI Installation instructions
The transmitter must be installed in an enclosure providing a degree of protection of at least IP54 according to IEC60529 that is suitable for the application and is correctly installed. Cable entry devices and blanking elements shall fulfill the same requirements.
If the enclosure is made of non-metallic materials or of painted metal, electrostatic charging shall be avoided.
Use supply wires with a rating of at least 5 K above the ambient temperature.
Supply from a Class 2 Power Supply with Transient protection or equivalent.
WARNING: Substitution of components may impair suitability for Class I, Division 2 AVERTISSEMENT: la substitution de composants peut nuire à l’aptitude à la Classe I, Division 2. WARNING: Do not disconnect equipment unless power has been switched off or the area is known to be safe.
AVERTISSEMENT: Ne débranchez pas l’équipement sauf si l’alimentation a été coupée ou si la zone est connue pour être sûre.
Non Incendive field wiring installation
The non incendive field Wiring Circuit concept allows interconnection of Nonincendive Field wiring Apparatus with Associated Nonincendive Field Wiring Apparatus or Assosicated Intrinsically Safe Apparatus or Associated Apparatus not specially examined in combination as a syatem using any of the wiring methods permitted for unclassified locations, Voc < Vmax, Ca ≥ Ci + Ccable , La ≥ Li + Lcable.
CSA Installation drawing 533XQC03 – V5R0
CLASS 2258 04 – PROCESS CONTROL EQUIPMENT – Intrinsically Safe Entity – For Hazardous Locations
CLASS 2258 84 – PROCESS CONTROL EQUIPMENT – Intrinsically Safe Entity – For Hazardous Locations – Certified to US Standards
- Class I, Division 1, Groups A, B, C and D T6…T4
- Ex ia IIC T6…T4 Ga
- Class I, Zone 0, AEx ia IIC Ga
Warning:
Substitution of components may impair intrinsic safety.
The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in the Canadian Electrical Code (CEC) or for US the National Electrical Code (NEC).
Document history
The following list provides notes concerning revisions of this document.
- Rev. ID Date Notes
- 111 1345 IECEx and INMETRO approvals added.
- 112 1514 PESO/CCOE approval added. GOST approval replaced with EAC approval
- 113 1707 FM installation drawing updated.
- 114 1848 FM installation drawing updated
- 115 1935 CSA approval for 5333A received. Installation drawing added
- 115 1935 CSA approval for 5333A received. Installation drawing added
- 117 2139 ATEX and IECEx approvals updated – Ex na changed to Exec.
- 118 2202 CSA installation drawings updated.
- 119 2245 UKCA added.
- 120 2345 INMETRO approval updated – Ex nA replaced by Exec.
We are near you, all over the world
- Our trusted red boxes are supported wherever you are
- All our devices are backed by expert service and a 5-year warranty. With each product you purchase, you receive personal technical support and guidance, day-to-day delivery, repair without charge within the warranty period and easily accessible documentation.
- We are headquartered in Denmark and have offices and authorized partners the world over. We are a local
- Business with a global reach. This means that we are always nearby and know your local markets well.
- We are committed to your satisfaction and provide PERFORMANCE-MADE SMARTER all around the world.
- For more information on our warranty program, or to meet with a sales representative in your region, visit prelectronics.com.
Benefit today from PERFORMANCE MADE SMARTER
PR Electronics is the leading technology company specializing in making industrial process control safer, more reliable and more efficient. Since 1974, we have been dedicated to perfecting our core competence of innovating high precision technology with low power consumption. This dedication continues to set new standards for products communicating, monitoring and connecting our customers’ process measurement points to their process control systems.
Our innovative, patented technologies are derived from our extensive R&D facilities and from having a great understanding of our customers’ needs and processes. We are guided by principles of simplicity, focus, courage and excellence, enabling some of the world’s greatest companies to achieve PERFORMANCE MADE SMARTER.
Documents / Resources
![]() |
PR electronics 5333 2-Wire Programmable Transmitter [pdf] Instruction Manual 5333, 5333 2-Wire Programmable Transmitter, 2-Wire Programmable Transmitter, Programmable Transmitter, Transmitter |