PPI Zenex Pro Digital Temperature Controller User Manual
I / O CONFIGURATION PARAMETERS
Parameters | Settings (Default Value) |
Input Type![]() |
Refer Table 1 (Default : Type K) |
Temperature Display Units![]() |
![]() °C °F (Default : °C) |
Temperature Range![]() |
Min. to Max. specified for the selected Input Type (Refer Table 1)
(Default : 1376) |
Control Output Type![]() |
Refer Table 2 (Default : Relay) |
Control Mode![]() |
![]() On-Off PID (Default : PID) |
Control Logic![]() |
![]() Direct Reverse (Default : Reverse) |
Hysteresis![]() |
1 to 999°C or
0.1 to 99.9°C (Default : 2 or 0.2) |
Setpoint Low Limit![]() |
Min. Range to Setpoint High for the selected Input Type (Default : -200) |
Setpoint High Limit![]() |
Setpoint Low to Max. Range for the selected Input Type (Default : 1376) |
SUPERVISORY PARAMETERS
Parameters | Settings (Default Value) |
Tune / Optimize Command![]() |
![]() No Yes (Default : No) |
Tune / Optimize Abort Command![]() |
![]() No Yes (Default : No) |
Overshoot Inhibit![]() |
![]() Disable Enable (Default : Disable) |
Overshoot Inhibit Factor![]() |
1.0 to 2.0 (Default : 1.2) |
Self-tune on Setpoint Change![]() |
![]() Disable Enable (Default : Disable) |
Offset for PV![]() |
-1999 to 9999 or
-199.9 to 999.9 (Default : 0) |
Digital Filter for PV![]() |
0.5 to 25.0 Seconds in steps of 0.5 Seconds
(Default : 1.0) |
Permission for OP2/OP3 Setpoint Editing on Operator Page![]() |
![]() Disable Enable (Default : Enable) |
Soak Abort Command on Operator Page![]() |
![]() Disable Enable (Default : Enable) |
Soak Time Adjustment on Operator Page![]() |
![]() Disable Enable (Default : Enable) |
Parameters | Settings (Default Value) |
Utility Option![]() |
![]() None Soak Start Water Level Low Detection (Default : None) |
Water Level-Low Detection Logic![]() |
![]() Open Close (Default : Open) |
Slave ID![]() |
1 to 127 (Default : 1) |
Baud Rate![]() |
4800, 9600, 19200 (Default : 9600) |
Parity![]() |
![]() None Even Odd (Default : Even) |
Communication Write Enable![]() |
![]() No Yes (Default : Yes) |
PID CONTROL PARAMETERS
Parameters | Settings (Default Value) |
% Output Power![]() |
Not Applicable (Default : Not Applicable) |
Cycle Time![]() |
0.5 to 120.0 Seconds (in steps of 0.5 secs.) (Default : 0.5) |
Proportional Band![]() |
0.1 to 999.9 (Default : 10.0) |
Integral Time![]() |
0 to 1000 Seconds (Default : 100) |
Derivative Time![]() |
0 to 250 Seconds (Default : 25) |
OP2 FUNCTION PARAMETERS
Parameters | Settings (Default Value) |
Output-2 Function Selection![]() |
![]() None Alarm Control Blower (Default : None) |
OP2 Function : Alarm-1 | |
Type![]() |
![]() Process Low Process High Deviation Band Window Band End of Soak (Default : Process Low) |
Setpoint![]() |
Min. to Max. Range for the selected Input type (Default : 0) |
Deviation Band![]() |
-199 to 999 or -199.9 to 999.9 (Default : 0) |
Window Band![]() |
3 to 999 or 0.3 to 999.9 (Default : 3) |
Parameters | Settings (Default Value) |
Logic![]() |
![]() Normal Reverse (Default : Normal) |
Inhibit![]() |
![]() Yes No (Default : Yes) |
Alarm Timer![]() |
5 to 250 Seconds
(Default : 10) |
OP2 Function : Auxiliary Control | |
Parameters | Settings (Default Value) |
Offset Value![]() |
(Min. Range – SP) to (Max. Range – SP) specified for the selected Input Type
(Default : 0) |
Hysteresis![]() |
1 to 999 or
0.1 to 999.9 (Default : 2 or 0.2) |
Control Logic![]() |
![]() Normal Reverse (Default : Normal) |
OP2 Function : Blower / Compressor Control | |
Offset Value![]() |
0 to 250 or 0.0 to 25.0
(Default : 0) |
Hysteresis![]() |
1 to 250 or 0.1 to 250.0
(Default : 2 or 0.2) |
Time Delay![]() |
00.00 to 10.00 Min. Sec (in steps of 5 Seconds)
(Default : 00.00) |
OP3 FUNCTION PARAMETERS
Parameters | Settings (Default Value) |
Output-3 Function Selection![]() |
Alarm Control Water Level Low Alarm (Default : None) |
OP3 Function : Alarm-2 | |
Type![]() |
![]() Process Low Process High Deviation Band Window Band End of Soak (Default : Process Low) |
Setpoint![]() |
Min. to Max. Range for the selected Input type (Default : 0) |
Deviation Band![]() |
-199 to 999 or
-199.9 to 999.9 (Default : 0) |
Window Band![]() |
3 to 999 or 0.3 to 999.9
(Default : 3) |
Logic![]() |
![]() Normal Reverse (Default : Normal) |
Inhibit![]() |
![]() Yes No (Default : Yes) |
Alarm Timer![]() |
5 to 250 Seconds
(Default : 10) |
OP3 Function : Auxiliary Control | |
Offset Value![]() |
(Min. Range – SP) to (Max. Range – SP) specified for the selected Input Type (Default : 0) |
Hysteresis![]() |
1 to 999 or 0.1 to 999.9 (Default : 2 or 0.2) |
Control Logic![]() |
![]() Normal Reverse (Default : Normal) |
SOAK TIMER PARAMETERS
Parameters | Settings (Default Value) |
Timer Enable![]() |
![]() No Yes (Default : No) |
Time Units![]() |
![]() Min:Sec Hours:Min Hours (Default : Min:Sec) |
Time Duration![]() |
00.05 to 60:00 Min:Sec 00.05 to 99:55 Hrs:Min 1 to 999 Hours (Default : 00.10 Min:Sec) |
Timer-Start Band![]() |
0 to 9999 or 0.0 to 999.9 (Default : 5 or 0.5) |
Holdback Strategy![]() |
![]() None Up Down Both (Default : None) |
Hold Band![]() |
1 to 9999 or 0.1 to 999.9 (Default : 5 or 0.5) |
Switch-Off Control Output at Timer End![]() |
![]() No Yes (Default : No) |
![]() Power-fail Recovery Method |
![]() Abort (Re)Start Continue (Default : Continue) |
OPERATOR PAGE AND PARAMETERS
Parameters | Settings |
Timer Start Command![]() |
![]() No Yes |
Timer Abort Command![]() |
![]() No Yes |
Time Duration![]() |
00.05 to 60.00 M:S or 00.05 to 99.55 H:M or 1 to 999 Hours |
OP2 Function : Alarm-1 | |
Alarm-1 Setpoint![]() |
Min. to Max. Range for the Input Type |
Alarm-1 Deviation Band![]() |
-199 to 999 or -199.9 to 999.9 |
Alarm-1 Window Band![]() |
3 to 999 or 0.3 to 999.9 |
Parameters | Settings |
OP2 Function : Auxiliary Control | |
Auxiliary Control Setpoint![]() |
(Min. Range – SP) to (Max. Range – SP) for selected Input |
OP2 Function : Blower / Compressor Control | |
Blower / Compressor Setpoint![]() |
0 to 250 or 0.0 to 25.0 |
OP3 Function : Alarm-2 | |
Alarm-2 Setpoint![]() |
Min. to Max. Range for the Input Type |
Alarm-2 Deviation Band![]() |
-1999 to 9999 or -199.9 to 999.9 |
Alarm-2 Window Band![]() |
3 to 999 or 0.3 to 99.9 |
OP3 Function : Auxiliary Control | |
Auxiliary Control Setpoint![]() |
(Min. Range SP) to (Max. Range SP) for selected Input |
Control Setpoint (SP) Locking | |
Setpoint Locking![]() |
![]() No Yes |
TABLE- 1 | ||
Option | Range (Min. to Max.) | Resolution |
![]() |
0 to +960°C / +32 to +1760°F | Fixed 1°C / 1°F |
![]() |
-200 to +1376°C / -328 to +2508°F | |
![]() |
-200 to +385°C / -328 to +725°F | |
![]() |
0 to +1770°C / +32 to +3218°F | |
![]() |
0 to +1765°C / +32 to +3209°F | |
![]() |
0 to +1825°C / +32 to +3092°F | |
![]() |
0 to +1300°C / +32 to +2372°F | |
![]() |
-199 to +600°C / -328 to +1112°F | |
![]() |
-199.9 to 600.0°C / -199.9 to 999.9°F | 0.1°C / 0.1°F |
TABLE- 2 | ||
Option | What it means | Remarks |
![]() |
Relay SSR (Solid State Relay) |
Applicable for OP1 as Relay / SSR |
NOTE : Applicable Only For Zenex DC Linear Version | ||
Option | What it means | Remarks |
![]() |
0 to 20mA current 4 to 20mA current | Applicable for OP1 as DC Linear Current |
![]() |
0 to 5 Volts 0 to 10 Volts | Applicable for OP1 as DC Linear Voltage |
FRONT PANEL LAYOUT
Symbol | Key | Function |
![]() |
PAGE |
Press to enter or exit set-up mode. |
![]() |
DOWN |
Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change. |
![]() |
UP |
Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change. |
![]() |
ENTER |
Press to store the set parameter value and to scroll to the next parameter on the PAGE. |
PV Error Indications
Message | PV Error Type |
![]() |
Over-range
(PV above Max. Range) |
![]() |
Under-range
(PV below Min. Range) |
![]() |
Open
(Sensor open / broken) |
ELECTRICAL CONNECTIONS
Relay / SSR Control Output Version
DC mA/V Control Output Version
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net