PPI logoUnclogs Pro / Unclogs Pro Plus with AIS
Universal Process Data Recorder PC Software Version
Operation Manual

UniLog Pro Universal Process Data Recorder PC

OPERATOR PARAMETERS
Parameters Settings (Default Value)
‘Start’ Command for Batch Recording (Available if Batch Recording is selected)
PPI UniLog Pro Universal Process Data Recorder PC - icon
No
Yes
‘Stop’ Command for Batch Recording (Available if Batch Recording is selected)
PPI UniLog Pro Universal Process Data Recorder PC - icon 2
No
Yes

SUPERVISORY CONFIGURATION

PPI UniLog Pro Universal Process Data Recorder PC - fig

Note: AII the other Parameters are under SUPERVISORY CONFIGURATION

ALARM SETTING
Parameters Settings(Default Value)
Channel Name for Alarm Settings
PPI UniLog Pro Universal Process Data Recorder PC - icon 3
User defined or default names for channel-1 to channel-8 /  16 (Default : NA)
Select Alarm
PPI UniLog Pro Universal Process Data Recorder PC - icon 4
AU , AL2, AL3, AL4
(The actual available options depends on the numbers of  Alarms set per channel on Alarm configuration page)
Alarm Type
PPI UniLog Pro Universal Process Data Recorder PC - icon 5
None
Process Low
Process High
(Default : None)
Alarm Setpoint
PPI UniLog Pro Universal Process Data Recorder PC - icon 6
Min. to Max. of selected input type range (Default : 0)
Alarm Hysteresis
PPI UniLog Pro Universal Process Data Recorder PC - icon 7
1 to 3000 or 0.1 to 3000.0
(Default : 2 or 2.0)
Alarm Inhibit
PPI UniLog Pro Universal Process Data Recorder PC - icon 8
No
Yes
(Default : No)
DEVICE CONFIGURATION
Parameters Settings (Default Value)
Channel Update Time in Auto Scan Mode
PPI UniLog Pro Universal Process Data Recorder PC - icon 9
1 Sec. to 99 Sec. (Default: 3 Sec.)
Device Identification Number
PPI UniLog Pro Universal Process Data Recorder PC - icon 10
1 to127 (Default : 1)
Select Total Numbers of Channels
PPI UniLog Pro Universal Process Data Recorder PC - icon 11
8
16
(Default : 16)
Erase All Stored Records
PPI UniLog Pro Universal Process Data Recorder PC - icon 12
No
Yes
(Default : No)
CHANNEL CONFIGURATION
Parameters Settings (Default Value)
Select Channel Name
PPI UniLog Pro Universal Process Data Recorder PC - icon 13
User defined or default names for channel-1 to channel – 8 /  16 (Default : NA)
Skip Channel for Display
PPI UniLog Pro Universal Process Data Recorder PC - icon 14
No
Yes
(Default : Yes)
Signal Input Type
PPI UniLog Pro Universal Process Data Recorder PC - icon 15
Refer Table 2
(Default : Type K (Cr-Al)
Display Resolution for Measured PV
PPI UniLog Pro Universal Process Data Recorder PC - icon 16
1 Unit
0.1 Unit
0.01 Unit
0.001 Unit
(Default : 0.1 Unit)
Display Units for Measured PV
PPI UniLog Pro Universal Process Data Recorder PC - icon 17
Refer Table 1 (Default : °C)
Range Low
PPI UniLog Pro Universal Process Data Recorder PC - icon 18
-19999 to 30000 Counts with Selected Resolution (Default : 0.0)
Range High
PPI UniLog Pro Universal Process Data Recorder PC - icon 19
-19999 to 30000 Counts with Selected Resolution
(Default : 100.0)
Apply Lower Clip on Displayed PV
PPI UniLog Pro Universal Process Data Recorder PC - icon 20
Disable
Enable
(Default : Disable)
Preset Lower Clip Level
PPI UniLog Pro Universal Process Data Recorder PC - icon 21
-19999 to 30000
(Default : 0)
Apply Upper Clip on Displayed PV
PPI UniLog Pro Universal Process Data Recorder PC - icon 22
Disable
Enable
(Default : Disable)
Preset Upper Clip Level
PPI UniLog Pro Universal Process Data Recorder PC - icon 23
-19999 to 30000 (Default : 100.0)
Zero Offset
PPI UniLog Pro Universal Process Data Recorder PC - icon 24
-1999 / 3000 or
-1999.9 / 3000.0
(Default : 0)
ALARM CONFIGURATION
Parameters Settings (Default Value)
Alarms Per Channel
PPI UniLog Pro Universal Process Data Recorder PC - icon 25
1 to 4 (Default : 4)
Relay-1 Logic
PPI UniLog Pro Universal Process Data Recorder PC - icon 26
Normal
Reverse
(Default : Normal)
Relay-2 Logic
PPI UniLog Pro Universal Process Data Recorder PC - icon 27
Normal
Reverse
(Default : Normal)
RECORDER CONFIGURATION 
Parameters Settings (Default Value)
Normal Recording Interval
PPI UniLog Pro Universal Process Data Recorder PC - icon 28
0:00:00 (H:MM:SS) to 2:30:00 (H:MM:SS)
(Default : 0:00:30)
Zoom Recording Interval
PPI UniLog Pro Universal Process Data Recorder PC - icon 29
0:00:00 (H:MM:SS) to 2:30:00 (H:MM:SS)
(Default : 0:00:01)
Record Generation on Alarm Status Toggle
PPI UniLog Pro Universal Process Data Recorder PC - icon 30
Disable
Enable
(Default : Enable)
Select Recording Mode
PPI UniLog Pro Universal Process Data Recorder PC - icon 31
Continuous Batch (Default : Continuous)
Time Interval for Batch Recording
PPI UniLog Pro Universal Process Data Recorder PC - icon 32
0:01 (HH:MM) to 250:00 (HHH:MM)
(Default : 1:00)
RTC SETTING
Parameters Settings
Set Clock Time (HH:MM)
PPI UniLog Pro Universal Process Data Recorder PC - icon 33
0.0 to 23:59
Set Calendar Date
PPI UniLog Pro Universal Process Data Recorder PC - icon 34
1 to 31
Set Calendar Month
PPI UniLog Pro Universal Process Data Recorder PC - icon 35
1 to 12
Set Calendar Year
PPI UniLog Pro Universal Process Data Recorder PC - icon 36
2000 to 2099
UTILITIES
Parameters Settings
Master Lock Enable Disable
PPI UniLog Pro Universal Process Data Recorder PC - icon 37
No
Yes
UIM Default
PPI UniLog Pro Universal Process Data Recorder PC - icon 38
No
Yes
CIM Default
PPI UniLog Pro Universal Process Data Recorder PC - icon 39
No
Yes
Make CIM & UIM Compatible
PPI UniLog Pro Universal Process Data Recorder PC - icon 40
No
Yes

* For Uni Log Pro Plus with more Than One AIS Only

TABLE-1
Option Description
°C Degree Centigrade
°F Degree Fahrenheit
(none) No Unit (Blank)
°K Degree Kelvin
EU Engineering Units
Percentage
Pa Pascals
Mpa Pascals
kPa Pascal’s
bar Bar
mbar Millie bar
psi PSI
kg/sq.cm kg/cm2
mmH2O mm water gauge
inH2O Inches water gauge
mmHg mm mercury
Torr Torr
litre/hr Litres per hour
litre/min Litres per minute
%RH % Relative Humidity
%02 % Oxygen
%002 % Carbon di-oxide
%CP % Carbon Potential
V Volts
A Amps
mA Millie Amps
mV Millis Volts
ohm Ohms
ppm Parts per million
rpm Revolutions per minute
music Millie seconds
Sec Seconds
min Minutes
hrs Hours
PH PH
%PH %PH
miles/hr Miles per hour
mg Millie grams
g Grams
kg Kilo grams
TABLE- 2
Option Range (Min. to Max.) Resolution
PPI UniLog Pro Universal Process Data Recorder PC - icon 41J Type T/C 0 to +960°C / +32 to +1760°F Fixed 1°C / 1°F
PPI UniLog Pro Universal Process Data Recorder PC - icon 42K Type T/C -200 to +1376°C / -328 to +2508°F
PPI UniLog Pro Universal Process Data Recorder PC - icon 43T Type T/C -200 to +385°C / -328 to +728°F
PPI UniLog Pro Universal Process Data Recorder PC - icon 44R Type T/C 0 to +1771°C / +32.0 to +3219°F
PPI UniLog Pro Universal Process Data Recorder PC - icon 45S Type T/C 0 to +1768°C / +32 to +3214°F
PPI UniLog Pro Universal Process Data Recorder PC - icon 46B Type T/C 0 to +1826°C / +32.0 to +3218°F
PPI UniLog Pro Universal Process Data Recorder PC - icon 47N Type T/C 0 to +1314.0°C / +32 to +2397.0°F
PPI UniLog Pro Universal Process Data Recorder PC - icon 48 Reserved for customer specific Thermocouple type not listed above.
PPI UniLog Pro Universal Process Data Recorder PC - icon 49RTD Pt100 -199 to +600°C / -328 to +1112°F or -199.9 to 600.0°C/ -328.0 to 1112.0°F User settable
1°C/ 1°F or 0.1°C / 0.1°F
PPI UniLog Pro Universal Process Data Recorder PC - icon 500 to 20mA DC -19999 to +30000 units User settable 1 / 0.1 / 0.01/ 0.001 units
PPI UniLog Pro Universal Process Data Recorder PC - icon 614 to 20mA DC
PPI UniLog Pro Universal Process Data Recorder PC - icon 510 to 50mV DC
PPI UniLog Pro Universal Process Data Recorder PC - icon 520 to 200mV DC
PPI UniLog Pro Universal Process Data Recorder PC - icon 530 to 1.25V DC
PPI UniLog Pro Universal Process Data Recorder PC - icon 540 to 5.0V DC
PPI UniLog Pro Universal Process Data Recorder PC - icon 550 to 10.0V DC
PPI UniLog Pro Universal Process Data Recorder PC - icon 561 to 5.0V DC

ID SETTING FOR MORE THAN 1 AIS
Applicable only for UNILOG PRO PLUS

PPI UniLog Pro Universal Process Data Recorder PC - fig 2

FRONT PANEL LAYOUT

PPI UniLog Pro Universal Process Data Recorder PC - fig 3

Symbol Key Function
PPI UniLog Pro Universal Process Data Recorder PC - icon 57 PAGE Press to enter or exit set-up mode.
PPI UniLog Pro Universal Process Data Recorder PC - icon 58 DOWN Press to decrease the parameter value. Pressing once decreases the value by one count; holding pressed speeds up the change.
PPI UniLog Pro Universal Process Data Recorder PC - icon 59 UP Press to increase the parameter value. Pressing once increases the value by one count; holding pressed speeds up the change.
PPI UniLog Pro Universal Process Data Recorder PC - icon 60 ENTER Press to store the set parameter value and to scroll to the next parameter on the PAGE.

PV Error Indications

Error Message Cause
Over Range Process Value above Max. Range
Under Range Process Value below Min. Range
Sensor Open Thermocouple / RTD broken
Com. Fail Communication Link with CI M broken

ELECTRICAL CONNECTIONS

USER INTERFACE MODULE (UIM)

PPI UniLog Pro Universal Process Data Recorder PC - fig 4

COMMUNICATION PORT FOR INTERFACING WITH AIS(S)

Applicable only for UNILOG PRO PLUS

PPI UniLog Pro Universal Process Data Recorder PC - fig 5

ANALOG INPUT MODULE CONNECTIONS

AIS-8UM

PPI UniLog Pro Universal Process Data Recorder PC - fig 6

AIS-16UM

PPI UniLog Pro Universal Process Data Recorder PC - fig 7

PPI logo101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales : 8208199048 / 8208141446
Support : 07498799226 / 08767395333
E: sales@ppiindia.net, support@ppiindia.net
Jan 2022