HumiTherm-cS
Advanced ‘Temperature + Humidity’
Programmable Controller with Alarms
User Manual
HumiTherm-cS Advanced Temperature + Humidity Programmable Controller
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net
ELECTRICAL CONNECTIONS

ENCLOSURE ASSEMBLY

BOARD ASSEMBLY
The electronic assembly comprises of four Printed Circuit Boards (PCB); CPU PCB, Display PCB, Output PCB & Power Supply PCB. The figure below shows position of each PCB inside the enclosure. 
JUMPER SETTINGS
MOUNTING DETAILS
SERIAL COMM. MODULE
INPUT CONFIGURATION PARAMETERS: PAGE 12
| Parameters | Settings (Default Value) |
|||||||||||||||||||||||||||
| Select Channel |
Humidity (Default : Temp) |
|||||||||||||||||||||||||||
| Input Type |
||||||||||||||||||||||||||||
| Signal Low |
|
|||||||||||||||||||||||||||
| Signal High |
|
|||||||||||||||||||||||||||
| Range Low |
-199.9 to 999.9 (Default : 0.0) |
|||||||||||||||||||||||||||
| Range High |
-199.9 to 999.9 (Default : 100.0) |
|||||||||||||||||||||||||||
| Offset |
-50.0 to 50.0 (Default : 0.0) |
CONTROL PARAMETERS : PAGE 11
| Parameters | Settings (Default Value) |
| Select Channel |
Humidity (Default : Temp) |
| Control Action |
|
| Setpoint Low Limit |
Temp = -199.9°C to SP.Hi RH = 0.0% to SP.Hi (Default : 0) |
| Setpoint High Limit |
Temp = SP.Lo to 600.0°C RH = SP.Lo to 100.0% (Default : 100) |
| Parameters | Settings (Default Value) |
| Heat/humidification Power Low Limit |
0.0% to Power High Limit (Default : 0.0) |
| Heat/humidification Power High Limit |
Power Low Limit to 100.0% (Default : 100.0) |
| Proportional Band (Cool Pre-dominant Zone) |
For Temp = 0.1 to 999.9°C For RH = 0.1 to 999.9% (Default : 50.0) |
| Integral Time (Cool Pre-dominant Zone) |
1 to 3600 Seconds (Default : 100 sec.) |
| Derivative Time (Cool Pre-dominant Zone) |
1 to 600 Seconds (Default : 16 sec.) |
| Proportional Band (Heat Pre-dominant Zone) |
For Temp = 0.1 to 999.9°C For RH = 0.1 to 999.9% (Default : 50.0) |
| Integral Time (Heat Pre-dominant Zone) |
1 to 3600 Seconds (Default : 100 sec.) |
| Derivative Time (Heat Pre-dominant Zone) |
1 to 600 Seconds (Default : 16 sec.) |
| Cycle Time |
0.5 to 100.0 Seconds (in steps of 0.5 secs.) (Default : 10.0 sec.) |
| Hysteresis |
0.1 to 999.9 (Default : 2.0) |
COMPRESSOR SETTING PARAMETERS: PAGE 17
| Parameters | Settings (Default Value) |
| Compressor Output Mode |
ON AUTO (Default : Auto) |
| Compressor Strategy |
Dry Bulb PV %RH PV (Default : Dry Bulb SP) |
| Boundary Set-point |
Temp. SP Low Limit to Temp. SP High Limit (Default : 45.0) |
| Compressor Set-point |
0.0 to 50.0 (Default : 0.2) |
| Compressor Hysteresis |
0.1 to 25.0 (Default : 0.2) |
| Compressor Time Delay |
0.00 to 10.00 Min (in steps of 5 secs.) (Default : 0 Sec.) |
SUPERVISORY PARAMETERS: PAGE 13
| Parameters | Settings (Default Value) |
| Tune Command |
|
| Standby Function |
|
| Control / alarm Set-point Adjustment Permission |
|
| Digital Input Function |
NoneWater Level Alarm ACK (Default : None) |
| Water Level Logic |
Open as LowClose as Low (Default : Open as Low) |
| Baud Rate |
(Default: 9.6) |
| Parity |
NoneEven Odd (Default: Even) |
| Device Slave Id |
1 to 127 (Default : 1) |
| Serial Write Permission |
ALARM PARAMETERS: PAGE-10
| Parameters | Settings (Default Value) |
| Select Channel |
(Default : Temp) |
| Alarm-1 Type |
NoneProcess Low Process High Deviation Band Window Band (Default : None) |
| Alarm-1 Hysteresis |
0.2 to 99.9 (Default : 2.0) |
| Alarm-1 Inhibit |
|
| Alarm-2 Type |
(Default: None) |
| Alarm-2 Hysteresis |
0.2 to 99.9 (Default : 2.0) |
| Alarm-2 Inhibit |
|
| Select Channel |
TempHumidity (Default : Temp) |
| Recorder Output Type |
(Default : 4 – 20mA) |
| Recorder Low |
Temp. : 199.9 – 999.9 RH : 0 to 100% (Default : 0.0) |
| Recorder High |
Temp. : 199.9 – 999.9 RH : 0 to 100% (Default : 100.0) |
TABLE- 1
| Option | Range (Min. to Max.) | Resolution |
| 3-wire, RTD Pt100 |
-199.9 to +600.0°C | 0.1 °C |
| 0 to 20mA DC current |
-199.9 to 999.9 units | 0.1 units |
| 4 to 20mA DC current |
||
| 0 to 50mV DC voltage |
||
| 0 to 200mV DC voltage |
||
| 0 to 1.25V DC voltage |
||
| 0 to 5.0V DC voltage |
||
| 0 to 10.0V DC voltage |
||
| 1 to 5.0V DC voltage |
FRONT PANEL LAYOUT
Front Panel
Keys Operation
| Symbol | Key | Function |
![]() |
PAGE | Press to enter or exit set-up mode. |
![]() |
DOWN | Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change. |
![]() |
UP | Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change. |
![]() |
ENTER | Press to store the set parameter value and to scroll to the next parameter on the PAGE. |
![]() |
Temp. Set-point Edit | Press to enter edit mode for Temperature Set-point. |
![]() |
%RH Set-point Edit |
Press to enter edit mode for %RH Set-point. |
![]() |
Standby Mode | Press to enter/exit Standby operation mode. |
![]() |
View Status | Press to view infrequently used process information like output control power and Wet Bulb SP. |
PV Error Indications
| Message | PV Error Type |
| Over-range (Dry Bulb Temperature above Max. Range) |
|
| Under-range (Dry Bulb Temperature below Min. Range) |
|
| Open (Dry Bulb Sensor (RTD) Broken / Open) |
101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales: 8208199048 / 8208141446
Support: 07498799226 / 08767395333
E: sales@ppiindia.net,
support@ppiindia.net
Jan 2022
Documents / Resources
![]() |
PPI HumiTherm-cS Advanced Temperature + Humidity Programmable Controller [pdf] User Manual HumiTherm-cS Advanced Temperature Humidity Programmable Controller, HumiTherm-cS, Advanced Temperature Humidity Programmable Controller, Temperature Humidity Programmable Controller, Humidity Programmable Controller, Programmable Controller, Controller |
None
Open as Low
(Default: 9.6)
None
(Default : Temp)
None
(Default: None)
Temp
(Default : 4 – 20mA)