POTTER SCM24W-153075 Select A Strobe Chime Combination Owner’s Manual
POTTER SCM24W-153075 Select A Strobe Chime Combination

  • Meets or exceeds NFPA/ANSI Standards and ADA Accessability Guidelines
  • UL Listed for wall mounting
  • Screw terminal capacity up to AWG #12
  • Universal mounting plate included
  • Selectable settings: 15cd or 30cd
  • Polarized strobes with wide operating voltage range using fi ltered
    DC or unfi ltered FWR input voltage
  • Horn fi eld selectable tones:
    • 2700 Hz or 2400 Hz
    • Temporal or Non-temporal
    • High or Low dBA Output
  • Mounts to 4” square, single gang, double gang, or octagonal back box
  • Tamper-proof candela selector switch
  • Synchronization requires Sync Module (SMD10-3A)
  • Available in red or white housing

Amseco’s Select-A-Strobe/Chime Series is designed to provide audible (private mode)  for fi re alarm protection systems. It complies with ADAand meets or exceeds NFPA/ANSI audible emergency evacuation signal and UL 464 (private mode) 1971. The SCM24W Series features a unique candela intensity fi eld selector switch for alternating the candela output 15cd to 30cd (75cd on axis). The chime provides two different selectable tones and a high/low output setting that can be achieved with the use of mini-jumpers located on the back of the unit. These appliances are polarized for connecting to supervised fi re alarm circuits. The strobe is designed with a xenon fl ash tube and provides a candela intensity fi eld selector switch for maximum performance.
The SCM24W-153075 can be synchronized by using the SMD10-3A Sync Module to comply with NFPA recommendations concerning photosensitive epilepsy when installing two or more visual appliances within the fi eld of view. The strobe signals are listed for indoor use, wall mount, under UL1971 standard.

Ordering Information

 Model Number Housing Color Input Voltage Operating Voltage Range Selectable Strobe Output (cd) Horn Sound Ouput Wiring Type Mounting Type  Sync Module Operating Temperature Range
SCM24W-153075R Red Regulated 24V DC/ FWR 16-33 VDC16-33 VFWR 15 or 30 Selectable Terminals Wall SMD10-3A 32°F – 120°F (0°C – 49°C)
SCM24W-153075W White

Engineering Specifications

The audible and visual alarm indicating appliances shall be Amseco model SCM24W 153075 or equivalent device. The chime shall be listed under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fi re protective service. The candela output shall be fi eld selectable, having a dual setting of 15cd or 30cd output. The chime shall provide two different fi eld selectable temporal or steady tones, and a high/low fi eld selectable output setting. The signaling strobe shall operate on a 24V DC coded system. The strobe shall be designed to produce one signal fl ash per second with continuously applied minimum voltage. The strobe/chime shall have a universal back mounting plate, capable of wall mounting to a back box. When strobe synchronization is required, the SCM24W-153075 shall be compatible with the Amseco SMD10-3A (daisy chain) or other source of Amseco sync protocol. Audible and visual signaling devices shall be installed in accordance with current NFPA guidelines.

Dimensions inches (mm)

Dimensions

Warning Icon WARNING

Strobes must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which the applied voltage is interrupted ON and OFF as the strobe may fail to fl ash. The applied voltage must be within its rated input voltage range. Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.

UL Required Minimum Light Output Horizontal Vertical
15cd 30cd 15cd 30cd
DEGREES 0 75.00 75.00 75.00 75.00
5-25 13.50 27.00 13.50 27.00
30 11.25 22.50 13.50 27.00
35 11.25 22.50 9.75 19.50
40 11.25 22.50 6.90 13.80
45 11.25 22.50 5.10 10.20
50 8.25 16.50 4.05 8.10
55 6.75 13.50 3.30 6.60
60 6.00 12.00 2.70 5.40
65 5.25 10.50 2.40 4.50
70 5.25 10.50 2.25 4.50
75 4.50 9.00 1.95 3.90
80 4.50 9.00 1.80 3.60
85-90 3.75 7.50 1.80 3.60
Compound 45 3.60 7.20
Strobe Light Only Max. RMS operating  Current (mA)
Regulated 24V DC Regulated 24V FWR
15cd 88 127
30cd 134 184

Button Function
Back of SCM24W

Tone Selection PC3Pattern PC2Tone PC1Volume
Jumper Icon Non- Temporal 2700 Hz High
Icon Temporal 2400 Hz Low

Selecting Switch

Sound Output Dispersion Horizontal (dB) Vertical (dB)
DEGREES +90 -6 -3
+60 -2 -2
+30 -1 -1
0 0 0
-30 -1 -3
-60 -2 -5
-90 -6 -6

Wiring Diagram

Wiring Diagram
Wiring Diagram
Wiring Diagram
Wiring Diagram
Wiring Diagram
Wiring Diagram

Specifications

Strobe Horn Current Draw Table PC3: Pattern PC2: Tone PC1: Volume Maximum RMS Operating Current (mA) Minimum Sound Output (dBA @ 10ft per UL464)
PC3 PC2 PC1 Regulated 24VDC Regulated 24V FWR Regulated 24VDC
Chime and Strobe (15cd) Non-Temp 2700 Hz High 1 1 1 112 155 66
Low 1 1 0 109 153 61
2400 Hz High 1 0 1 111 155 54
Low 1 0 0 109 153 50
Temporal 2700 Hz High 0 1 1 112 155 65
Low 0 1 0 109 153 60
2400 Hz High 0 0 1 111 155 53
Low 0 0 0 109 153 48
Chime and Strobe (30cd) Non-Temp 2700 Hz High 1 1 1 155 217 66
Low 1 1 0 152 215 61
2400 Hz High 1 0 1 154 217 54
Low 1 0 0 152 215 50
Temporal 2700 Hz High 0 1 1 155 217 65
Low 0 1 0 152 215 60
2400 Hz High 0 0 1 154 217 53
Low 0 0 0 152 215 48
Chime Only Non-Temp 2700 Hz High 1 1 1 45 58 66
Low 1 1 0 40 52 61
2400 Hz High 1 0 1 44 57 54
Low 1 0 0 40 52 50
Temporal 2700 Hz High 0 1 1 45 58 65
Low 0 1 0 40 52 60
2400 Hz High 0 0 1 44 57 53
Low 0 0 0 40 52 48

Installation Options

Installation Options