POTTER SCADA Modbus Link Modbus interface
Features
- Modbus TCP/IP · Connect to 10 Potter panels in a single building, local campus, or multiple sites worldwide using LAN/WAN/Internet
- Native Ethernet networking connectivity with fire panels and Modbus Link, eliminating need for additional hardware, converters, gateways, or network interface cards
- Modbus Link is a software solution that will run as a service on a customer provided Windows® 10 computer
- End-to-end supervision of all panels
- Deliver supplementary life safety signals to Modbus master SCADA/BMS/DCIM systems · Automatically discover all points minimal configuration
- CSV file summarizes mapping
- Modbus interface is unlisted and all signals are supplementary.
- Developed, manufactured and supported by Potter in the U.S.A.
Description
The Potter Modbus Link is TCP/IP based software that enables up to 10 compatible Potter fire panels to report panel and point status information to Modbus SCADA systems in commercial buildings, campuses, and industrial facilities. This supplementary slave device interface allows third party Modbus masters (clients) to display and respond to fire system activity. Life safety functions are retained in the fire alarm control panels. The Modbus Link converts native Potter panel protocol into Modbus. All the Potter and Modbus communications utilize an Ethernet-TCP/IP network. The Modbus Link is unique in that it is a licensed software solution that will run as a Windows® service on a site provided computer.
Technical Specifications
Panels Per Modbus Link | 10 |
PC & OS Platforms Required | Windows® 10 Professional, 64-bit, English (USA) Intel® i5 (or equivalent) 2.6 GHz, 16GB RAM |
Network Technology Requirements | Ethernet with static IPs |
Software Requirements | .Net version 4.7.2 MS Visual C++ 2017 Redistributable |
Supported Fire Alarm Control Panels (v. 6 and above) | IPA -4000, IPA -100, IPA -60AFC-1000, AFC-100, AFC-50, ARC-100 PFC-4064 |
Regulatory Standards | None – for supplementary signaling |
Protocol | Modbus TCP/IP |
Modbus Link Architecture
Ordering Information
Model | Description | Stock No. |
Modbus Link Software | ||
MODBUS-LINK | Modbus Link enables a user to integrate up to 10 compatible Potter fire panels into Modbus master/SCADA system. 1-year software services agreement (SSA) is included with MODBUS- LINK. | 3993021 |
MODBUS-LINK- CONNECT | Modbus Link connection licenses. Each Potter fire panel connected to the Modbus Link requires a license. 1-year software services agreement (SSA) is included with MODBUS- LINK-CONNECT | 3993022 |
(Optional) Software Service Agreements (SSA) | ||
MODBUS-LINK-SSA | (Optional) 1-year software services agreement for MODBUS-LINK. MODBUS-LINK must have an SSA in order to get the software updates. | 3993023 |
MODBUS-LINK- CONNECT-SSA | (Optional) 1-year software services agreement for MODBUS-LINK-CONNECT. Each MODBUS-LINK-CONNECT must have an SSA in order to get the software updates. | 3993024 |
Potter Electric Signal Company, LLC
• St. Louis, MO
• Phone: 800-325-3936
• www.pottersignal.com
Documents / Resources
![]() |
POTTER SCADA Modbus Link Modbus interface [pdf] Owner's Manual SCADA Modbus Link Modbus interface, SCADA, Modbus Link Modbus interface, Modbus interface |