PLT-LOGO

PLTSP3P417 LED T8 Tube with Emergency Backup

PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-PRODUCT

COLOR SELECTABLE

COLOR SELECTABLE LED TS TYPE B TUBE W/ EMERGENCY BACKUP WARNING, CAUTION, SAFETY AND INSTALLATION INSTRUCTIONS

WARNING

  • Installation, service, and maintenance of luminaries should be performed by a qualified licensed electrician.
  • Read these instructions carefully before installation.
  • Installers should examine all parts that are not intended to be replaced by the retrofit kit for damage and replace any damaged parts before installation of the retrofit kit.
  • There is an emergency LED tube, installation instructions, luminaire marking labels, and miscellaneous hardware in this kit.

CAUTION

  • Only those open holes indicated in the photography and/or drawing may be made or altered as a result of kit installation. Do not make any other holes in the wiring enclosure or components.
  • Installers should not disconnect existing wires from lamp holder terminals to make new connections at the lamp holder terminals.
  • Instead, installers should cut existing lamp holder leads away from the lamp holder and make new electrical connections to the lamp holder lead wires by employing applicable connectors.
  • Install this kit only in the luminaries that have the construction feature and dimensions shown in the photographs and/or drawings and where the input rating of the retrofit kit does not exceed the input rating of the luminaire.
  • FOR RETROFIT KITS CERTIFIED TO CANADIAN REQUIREMENTS: THE RETROFIT KIT IS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE THE SUITABILITY OF THE COMBINATION SHALL BE DETERMINED BY AUTHORITIES HAVING JUSRISICTION.
  • PRODUCT MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN BY THE APPLICABLE AND APPROPRIATE ELECTRICAL CODES. THE INSTALLATION GUIDE DOES NOT SUPERSEDE LOCAL OR NATIONAL REGULATIONS FOR ELECTRICAL INSTALLATIONS.
  • LED retrofit kit installation requires knowledge of luminaire electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
  • Luminaire wiring and electrical parts may be damaged when drilling for the installation of an LED retrofit kit. Check for enclosed wiring and components.
  • The retrofit position is located at the edge of the target luminaire with installed max of four LED tubes. LED tubes manufactured by PRECISION LIGHTING & TRANFORMER INC, model PL TSP3E21X.
  • This kit is intended to retrofit target luminaires with the following characteristics:
    • Surface-mounted, Type IC, or Type non-IC recessed-mounted
    • With or without a diffuser
    • Not dimmable
    • Max 4 LED tubes which are manufactured by PRECISION LIGHTING & TRANSFORMER INC (E4790302), Model PLTSP2E21X
    • The retrofit position is located at the edge of the four LED tubes
    • One single branch circuit as power supply connection
    • Refer to the below table for Min compartment dimensions
    • Max. mounting height: 8.07′
  Model Number MINIMUM LAMP COMPARTMENT DIMENSIOINS [length X width X height]
Target Luminaire PLTSP3P417 47.83×23.82×2.95in 1215x605x75mm

Installation Instructions

  1. Turn the DIP switch on the B side to the “ON” position.PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (1)
  2. Combine the adapter and the end cap of B side.PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (2)
  3. Disconnect power to the fixture.
  4. Remove existing tubes, reflector, and grille, and remove the lamp housing.
  5. Open the Test Switch hole on the side of the fixture.PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (3)
  6. Install the external test switch.PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (4)
  7. Connect the AC terminal wire (Black, White, Red) in the accessory box to the junction box.PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (5)
  8. Install the lamp housing, reflector, and existing tubes.
  9. Install the emergency LED lamp.PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (6)
  10. AC & test switch terminal male and female are plugged together.PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (7)
  11. The AC wire and the test switch wire enter the interior of the fixture.PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (8)
  12. Install the fixed clip on the B side.PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (9)

Wiring Diagram

PLTSP3P417-LED-T8-Tube-with-Emergency-Backup-FIG- (10)

FCC

This device complies with Part 15 of the FCC Rules.

Operation is subject to the following two conditions:

  1. this device may not cause harmful interference, and
  2. this device must accept any interference received, including interference that may cause undesired operation.

WARNING

  • Before installing, servicing, or performing routine maintenance on this equipment, follow these general precautions.
  • To reduce the risk of death, personal injury, or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards, read all warnings and instructions included with and on the fixture box and all fixture labels.
  • Proper grounding is required to ensure safety.
  • Power must be turned off at the breaker before installation or maintenance.
  • This product must be installed per the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved.
  • Wear gloves and eye protection at all times while installing, servicing, or performing maintenance on the luminaire, and avoid direct eye exposure to the light source while it is on.
  • To prevent wiring damage or abrasion, do not expose wiring to the edges of sheet metal or other sharp objects.
  • Do not install damaged products. Inspect the luminaire for damage that may have occurred during transit. If damaged, contact the manufacturer immediately.
  • These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation, operation, or maintenance.
  • Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s or owner’s purposes, contact the manufacturer.

CONTACT INFORMATION

Documents / Resources

PLT PLTSP3P417 LED T8 Tube with Emergency Backup [pdf] Instruction Manual
PLTSP3P417 LED T8 Tube with Emergency Backup, PLTSP3P417, LED T8 Tube with Emergency Backup, with Emergency Backup, Emergency Backup, Backup

References

Leave a comment

Your email address will not be published. Required fields are marked *