PIXSYS TCT101 Timer Counter Tachometer

PIXSYS-TCT101-Timer-Counter-Tachometer-product

PIXSYS www.pixsys.net
e-mail: sales@pixsys.netsupport@pixsys.net
Software V 2.08
2300.10.140-RevH 240314

SIZE AND INSTALLATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-1

TECHNICAL DATA

  • Operating temperature: Operating temperature 0-40°C, humidity 35..95uR%
  • Sealing: Front panel IP65 (with optional gasket) , Box IP30, Terminal blocks IP20
  • Material: PC ABS UL94V0 self-extinguishing
  • Digital Inputs: 3PNP/NPN configurable as analogue for potentiometers (max 28 Vdc in PNP mode)
  • Outputs: 1 relays 5A resistive charge
  • OUT 24V: 30mA(24Vac),40mA(24 Vdc),60mA (110…230Vac)
  • Serial: RS485
  • Back-UP: Rechargeable battery, approx. 7days autonomy
  • Programming Software: Labsoftview 2.6 or later
  • Power Supply: 24…230Vac/Vdc +/-15% 50/60Hz / 2W

INTRODUCTION

Thanks for choosing a Pixsys device. TCT101-4ABC-T can be set in 3 different modes: ,timer counter or tachometer. 3 universal digital inputs are availables (NPN/PNP/Potential free contact) and can be used for reading external switches, proximity sensors and bidirectional encoders. One input is also analogue in order to allow setpoint modification by external potentiometer. Rs485 serial interface allows communication via Modbus RTU protocol.

  • Read carefully the safety guidelines and programming instructions contained in this manual before using/connecting the device.
  • Disconnect power supply before proceeding to hardware settings or electrical wirings.
  • Only qualified personnel should be allowed to use the device and/or service it and in accordance to technical data and environmental conditions listed in this manual.
  • Do not dispose electric tools together with household waste materials in observance of European Directive 2002/96/CE

WIRING DIAGRAM

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-2

Potentiometer:
To modify Set1 or Set2 by external potentiometer follow the steps below:

  1. use potentiometers 5kOhm to 10kohm
  2. connect cursor to pin I3; a wrong connection may damage the potentiometer and lead to lock of the device.
  3. accuracy on input is max 1000 points, therefore set the parameters “Upper limit” and “Lower limit” with a max difference of 1000 units.
    (Ex.: LoS1 to 50,0 and uPS1 to 150,0 to modify time value related to Set1 between 50 and 150 seconds with steps of one tenth). Greater differences would make unstable the less significant digit.
  4. To calibrate the scale of potentiometer enter the configuration mode and select: Hin.3 as Pot Fin.3 as Set1 or Set2 P.tAr as Enable Exit configuration mode and place potentiometer at minimum level and press PIXSYS-TCT101-Timer-Counter-Tachometer-fig-37key,  then place potentiometer at max level and press premere PIXSYS-TCT101-Timer-Counter-Tachometer-fig-3key: the device automatically exit the calibration procedure.
    N.B.:Aswitch-off of the device would interrupt the calibration.

MEMORY CARD

(optional)

Parameters and setpoint values can be copied from one device to another using the Memory car.

There are two methods:

  • With the device connected to the power supply insert the memory card when the controller is off On activation display 1 shows and display 2 shows PIXSYS-TCT101-Timer-Counter-Tachometer-fig-3
    (Only if the values stored on Mmeory Card are correct).
  • By pressing the PIXSYS-TCT101-Timer-Counter-Tachometer-fig-3key display 2 shows PIXSYS-TCT101-Timer-Counter-Tachometer-fig-3Confirm using thePIXSYS-TCT101-Timer-Counter-Tachometer-fig-37 key.PIXSYS-TCT101-Timer-Counter-Tachometer-fig-7

The device loads the new data and starts again

With the controller disconnected from the power supply:
The memory card is equipped with an internal battery with a life of about 1000 uses.
Insert the memory card and press the programming button.
When writing the parameters, the LED turns red and on completing the procedure it changes to green. It is possible to repeat the procedure.

UPDATING MEMORY CARD.

To update the memory card values, follow the procedure described in the first method, setting display 2 to PIXSYS-TCT101-Timer-Counter-Tachometer-fig-3 so as not to load the parameters on controller.
Enter configuration and change at least one parameter
Exit configuration. Changes are saved automatically.

SETPOINT MODIFICATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-8

LOADING DEFAULT VALUES

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-9

CONFIGURATION PARAMETER MODIFICATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-10

PARAMETERS LIST

TCT101-4ABC-T allows to select operating mode, modifying first configuration parameter. According to chosen mode, only the relevant parameters will be displayed.
Refer to technical notes of each mode to find parameters list.

TCT101 MODE CONFIGURATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-11

Here below you can find parameters to set serial port and Modbus protocol, independently from selected operating mode.

SERIAL CONFIGURATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-12

SERIAL COMMUNICATION

  • TCT101-4ABC-T is provided with RS485 serial and can receive/transmit data via MODBUS RTU protocol. Device can be configured only as Slave. This function allows to control multiple controllers connected to a supervisory system (Master). Each instrument will answer to a Master query only if it contains some addresses as on parameterPIXSYS-TCT101-Timer-Counter-Tachometer-fig-13 (SlaveAddress).
  • Allowed addresses range are from 1 to 254 and there should not be controllers with the same address on the same line.
  • Address 255 can be used by the Master to communicate with all connected equipments (all connected devices will answer Master query with this address), while with 0 all devices receive command, but no answer is expected (broadcast mode).
  • TCT101-4ABC-T can introduce an answer delay (in milliseconds) to Master request. This delay has to be set on parameter PIXSYS-TCT101-Timer-Counter-Tachometer-fig-14(Serial Delay).
  • At each parameter modification, instrument stores values in EEPROM memory (100000 writing cycles).
  • NB: Modifications made to Word different to those described in the following table can lead to instrument malfunction.

MODBUS RTU PROTOCOL MAIN FEATURES

 

Baudrate

Selectable by parameter
 

Format

8,N,1 (8 bit data, no parity, 1 stop bit)
 

Supported functions

WORD READING (0x03, 0x04) (max 20 word) SINGLE WORD WRITING (0x06)

MULTIPLE WORDS WRITING (0x10) (max 20 word)

 

 

Read/Write

RO Read Only WO Write Only RW Read / Write
 

Reset Value

?               Data unknown at reset EEPROM Value stored on EEPROM Valore Value indicated at reset
Modbus Address Description Read Write Reset Value
0 Device type (ID TCT101-4ABC-T) RO 153
1 Software version RO 203
3 Slave address RO EEPROM
10 Setpoint storing delay RW 0
11 Parameter storing delay RW 0
100 Relay outputs status

– bit 0 = relay Q1

– bit 1 = relay Q2

RO ?
101 Digital inputs status

– bit 0 status I1

– bit 1 status I2

– bit 2 status I3

RO ?
102 Keys status

– bit 0 UP key status

– bit 1 DOWN key status

– bit 2 SET key status

– bit 3 FNC key status

RO ?
300 Loading default values

– writing 9999 restores all default values

– writing 9998 restores all default values keeping unchanged slave address

– writing 9997 restores all default values keeping unchanged communication baudrate

– writing 9996 restores all default values keeping unchanged slave address and communication baudrate

RO 153
400 Setpoint 1 RW EEPROM
401 Setpoint 2 RW EEPROM

PARAMETERS LIST

FUNCTION CONFIGURATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-15

BACKUP MEMORY CONFIGURATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-16

INPUT CONFIGURATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-17

OUTPUT CONFIGURATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-18

DISPLAY CONFIGURATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-19

SETPOINT CONFIGURATION

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-20PIXSYS-TCT101-Timer-Counter-Tachometer-fig-21

MODBUS WORD ADDRESSES IN TIMER MODE

500 Timer H value RO ?
501 Timer L value RO ?
502 Timer value / 60 RO ?
503 Module 60 timer value RO ?
504 Timer status

– 0 timer in stop

– 1,2 timer in start

RO ?
505 Active timer

– 0 no active timer

– 1 timer 1 active

– 2 timer 2 active

RO ?
506 Timer logic outputs

– bit 0 timer 1 logic output

– bit 1 timer 2 logic output

RO ?
507 Wait Hold timer status

– bit 0 Wait status

– bit 1 Hold status

RO ?
508 Timer serial command done RO ?
509 Timer in Hold RO ?
510 Hold H timer value RO ?
511 Hold L timer value RO ?
512 Hold / 60 timer value RO ?
513 Hold module 60 timer value RO ?
514 Partial minutes (only for timer in hours) RO ?
530 Timer serial command

– 0 no command

– 1 start timer command

– 2 stop timer command

– 3 reset timer command

– 4 reset start timer command

– 5 stop reset timer command

– 6 enables/ desables wait timer function command

– 7 enables/ desables hold timer command function

WO 0
1000 Parameter P-00 RW EEPROM
1001 Parameter P-01 RW EEPROM
1002 Parameter P-02 RW EEPROM
  RW EEPROM
1052 Parameter P-52 RW EEPROM
1053 Parameter P-53 RW EEPROM

TCT101-4ABC-T “TIMER” MODE

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-21 PIXSYS-TCT101-Timer-Counter-Tachometer-fig-23

PARAMETERS LIST

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-24 PIXSYS-TCT101-Timer-Counter-Tachometer-fig-25 PIXSYS-TCT101-Timer-Counter-Tachometer-fig-25 PIXSYS-TCT101-Timer-Counter-Tachometer-fig-27 PIXSYS-TCT101-Timer-Counter-Tachometer-fig-28

MODBUS WORD ADDRESSES IN COUNTER MODE

600 Counter 1 H value RO ?
601 Counter 1 L value RO ?
602 Counter 1 H counts RO ?
603 Counter 1 L counts RO ?
604 Counter 1 logic output

– bit 0 Counter 1 logic output

RO ?
605 Counter 1 Lock Hold status

– bit 0 lock function status

– bit 1 hold function status

RO ?
606 Counter 1 count direction

– 0 normal count direction

– 1 reverse count direction

RO ?
607 Counter 1 serial command done

Shows value of the last serial command done

RO 0
608 Counter 1 H hold value RO ?
609 Counter 1 L value RO ?
610 Counter 1 H frequency (Hz) RO ?
611 Counter 1 L frequency (Hz) RO ?
612 Counter 1 H frequency value RO ?
613 Counter 1 L frequency value RO ?
620 Counter 1 serial command

– 0 no command

– 1 load command

– 2 enable/disable lock function

– 3 enable/disable hold function

– 4 reverse count direction

– 5 Enter onward count

– 6 Enter backward count

WO 0
630 Counter 2 H value RO ?
631 Counter 2 L value RO ?
632 Counter 2 H counts RO ?
633 Counter 2 L counts RO ?
634 Counter 2 logic output RO ?
635 Counter 2 Lock Hold status RO ?
636 Counter 2 count direction RO ?
637 Counter 2 serial command done RO 0
638 Counter 2 H Hold value RO ?
639 Counter 2 L Hold value RO ?
640 Counter 2 H frequency (Hz) RO ?
641 Counter 2 L frequency (Hz) RO ?
642 Counter 2 H frequency value RO ?
643 Counter 2 L frequency value RO ?
650 Counter 2 serial command WO 0
2000 Parameter P-00 RW EEPROM
2001 Parameter P-01 RW EEPROM
2002 Parameter P-02 RW EEPROM
  RW EEPROM
2052 Parameter P-52 RW EEPROM
2053 Parameter P-53 RW EEPROM

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-29 PIXSYS-TCT101-Timer-Counter-Tachometer-fig-30

PARAMETERS LIST

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-31 PIXSYS-TCT101-Timer-Counter-Tachometer-fig-32 PIXSYS-TCT101-Timer-Counter-Tachometer-fig-33

MODBUS WORD ADDRESSES IN TACHOMETER MODE

700 Tachometer H value RO ?
701 Tachometer L value RO ?
702 Tachometer H minimum peak value RO ?
703 Tachometer L minimum peak value RO ?
704 Tachometer H maximum peak value RO ?
705 Tachometer L maximum peak value RO ?
706 Tachometer logic outputs

– bit 0 logic output 1

– bit 1 logic output 2

RO ?
707 Tachometer serial command done

Shows value of the last serial command done

RO 0
708 Tachometer word Out-Enable

– bit 0 out enable output 1

– bit 1 out enable output 2

RO ?
709 Tachometer Hold

– bit 0 tachometer hold status

RO ?
710 Hold H tachometer value RO ?
711 Hold L tachometer value RO ?
720 Tachometer serial command

– 0 no command

– 1 command

– 2 command enable / disable output

– 3 command enable / disable hold function

– 4 command reset max. and min. peak

– 5 command clear output (if in latch)

WO 0
3000 Parameter P-00 RW EEPROM
3001 Parameter P-01 RW EEPROM
3002 Parameter P-02 RW EEPROM
  RW EEPROM
3052 Parameter P-52 RW EEPROM
3053 Parameter P-53 RW EEPROM

PIXSYS-TCT101-Timer-Counter-Tachometer-fig-35 PIXSYS-TCT101-Timer-Counter-Tachometer-fig-36

Frequently Asked Questions

Q: What are the available modes for TCT101-4ABC-T?

A: The device can be set in three different modes: timer, counter, or tachometer.

Q: What type of inputs are supported by the device?

A: The device supports three universal digital inputs (NPN/PNP/Potential free contact) for reading external switches, proximity sensors, and encoders.

Q: How can I modify Set1 or Set2 using an external potentiometer?

A: Follow the steps mentioned in the manual, using a potentiometer with a resistance of 5kOhm to 10kOhm and connecting it appropriately to pin I3.

Documents / Resources

PIXSYS TCT101 Timer Counter Tachometer [pdf] User Manual
TCT101, TCT101 Timer Counter Tachometer, TCT101, Timer Counter Tachometer, Counter Tachometer, Tachometer