Phason DOL119 Plus Touch Controller User Guide

DOL119 Plus Touch Controller

Specifications:

  • Input power: 120/230 VAC, 50/60 Hz
  • Fuses: 15 A, 250 VAC ABC-type ceramic (F1 and F2)
  • Variable stages: 2 (VARI-1, VARI-2)
  • Relay stages: 6 (STG-1 to STG-6)
  • Alarm relay: 10 A at 120/230 VAC, general-purpose
    (resistive)

Product Usage Instructions:

1. Display Cable (A)

Disconnect the cable during installation and reconnect it when
done.

2. Voltage Switch (B)

Set the switch to the correct line voltage as per your
electrical system.

3. Incoming Power (C)

Connect the incoming power from the panel to power up the
unit.

4. Temperature Sensor (D)

Connect the primary temperature sensor to TEMP1. Additional
sensors can be connected to other terminals.

5. Actuator Feedback (E)

Connect the feedback potentiometer from the actuator to ACT-1
and ACT-2.

6. Alarm Relay (F)

Connect an external alarm system or siren to the alarm
relay.

7. General-Purpose Relays (G)

Connect single-speed/stage heating/cooling equipment to STG-1 to
STG-6.

8. Variable Stages (H)

Connect variable speed fans to VAR-1 and VAR-2 using appropriate
wiring.

9. Fuses (I)

F1 is for VAR-1 and F2 is for VAR-2. Ensure correct fuse
placement for protection.

10. USB Port (J)

Connect a USB drive for saving/loading settings or updating
firmware when required.

11. Outdoor Sensor (K)

Connect a Phason 3K Temperature Sensor for measuring outdoor
temperature to the designated port.

FAQ:

Q: What should I do if the unit does not power on?

A: Check the incoming power connection and ensure the voltage
switch is set correctly.

Q: Can I connect multiple temperature sensors?

A: Yes, you can connect multiple temperature sensors to the
designated terminals following the provided guidelines.

J B

I

H

G

D

A

C

F

E

N

M

O N

M

K

L

(A) Display cable Disconnect the cable during installation. Reconnect it when done.
(B) Voltage switch Set the switch to the correct line voltage.
(C) Incoming power Connect the incoming power from the panel.
(D) Temperature sensor (TEMP1 to TEMP4) Connect the primary temperature sensor to TEMP1. Connect any additional sensors to the other terminals.
(E) Actuator feedback (ACT-1 and ACT-2) Connect the feedback potentiometer from the actuator.

(F) Alarm relay Connect an external alarm system or siren.
(G) General-purpose relays (STG-1 to STG-6) Connect single-speed/stage heating/cooling equipment.
(H) Variable stages (VAR-1 and VAR-2) Connect variable speed fans. (I)Fuses (F1 and F2) The fuses are for the variable stages. F1 is for VAR-1 F2 is for VAR-2.
(J) USB Connect a USB drive when saving or loading settings, or updating firmware.

(K) OUTDOOR Connect a Phason 3K Temperature Sensor for measuring outdoor temperature.
(L) +5V Can provide +5 VDC
(M) DOL (M: AUX1 to AUX3) Connect DOL119 Carbon Dioxide or DOL 53 Ammonia Sensors. Place the jumpers on the correct pins.
(N) DOL 114 (TEMP / HUM) Connect a DOL 114 Temperature and Humidity Sensor. Place the jumpers on the correct pins.
(O) Pulse counter (COUNT) Not available, used for future development.

34340003-QS

Input power 120/230 VAC, 50/60 Hz
Fuses (2: F1and F2) 15 A, 250 VAC ABC-type ceramic

Variable stages (2: VARI-1, VARI-2)

Relay stages (6: STG-1 to STG-6)

Alarm relay

10 A at 120/230 VAC, general-purpose (resistive) 10 A at 120/230 VAC, general-purpose (resistive) 0.4 A at 125 VAC; 2 A at 30 VDC, resistive load

7 FLA at 120/230 VAC, PSC motor

1/3 HP at 120 VAC, 1/2 HP at 230 VAC

0.2 A at 125 VAC; 1 A at 30 VDC, inductive load

1/2 HP at 120 VAC, 1 HP at 230 VAC, PSC motor 360 W tungsten at 120 VAC

Mounting holes and orientation

Incoming power

Single-speed fan or electric heater

Gas-fired furnace

Variable speed fan

Correct three-phase wiring

Incorrect three-phase wiring

Curtain machine

DC-powered actuator

AC-powered actuator

Temperature sensor

DOL 114 temperature and humidity

DOL 119 carbon dioxide

DOL 53 ammonia

Normally open alarm system

Normally closed alarm system

www.phasoncontrols.com

sales@phasoncontrols.com

Toll-free North America: 800-590-9338

International: 204-233-1400