ONLINE 10 kVA UPS External Maintenance Bypass Switch User Manual

10 kVA UPS External Maintenance Bypass Switch

Specifications

  • Dimensions: 88 x 440 x 195 mm (height x width x depth)
  • Weight: 3.8 kg

Product Overview

  1. UPS Input Breaker
  2. Maintenance bypass switch (with Maintenance switch cover)
  3. Control output signal connector
  4. Output terminal
  5. Utility input terminal
  6. UPS output terminal
  7. UPS input terminal
  8. Grounding terminal

Installation

Inspection

Unpack the package and check the contents for any damage. Notify
the carrier and dealer immediately if any parts are missing or
damaged.

Initial Setup

  1. Ensure compliance with local electric laws/regulations.
  2. Verify mains wire and breakers are rated for UPS capacity.
  3. Switch off mains switch in the building.
  4. Prepare wires according to specifications.
  5. Connect UPS and External Maintenance Bypass Switch terminals as
    per diagrams.

Operation

Normal Operation

Load is supplied by UPS via rectifier and inverter.

Transfer to Bypass Operation

[Include specific steps for transferring to bypass operation
here]

Transfer to Normal Operation

[Include specific steps for transferring back to normal
operation here]

Support

ONLINE sets great store by reliable support and service.

FAQ

Q: What should I do if there is damage to the unit during
transportation?
A: Notify the carrier and dealer immediately if there is any
damage or lacking from some parts.
Q: Can I use a wall receptacle as the input power source for
the UPS?
A: Do not use the wall receptacle as the input power source for
the UPS, as it is rated current is less than the UPS’s maximum
input current.
Q: How should I choose the wire color for installation?
A: The selections for color of wires should be followed by the
local electrical laws and regulations.

“`

USER MANUAL EXTERNAL MAINTENANCE BYPASS SWITCH
for UPS XANTO 10,000 ­ 20,000 VA, 3/3-phase
Version: 07/2025
www.online-ups.com

Content
1 Indroduction ………………………………………………………………………………………………………………………………….. 3 2 Product Overview ………………………………………………………………………………………………………………………….. 3 3 Installation …………………………………………………………………………………………………………………………………….. 4 4 Operation ………………………………………………………………………………………………………………………………………. 5 5 Specification of Critical Components ……………………………………………………………………………………………. 7 6 Support ………………………………………………………………………………………………………………………………………….. 8 7 Warranty ……………………………………………………………………………………………………………………………………….. 9 Imprint …………………………………………………………………………………………………………………………………………………. 10

USER MANUAL EXTERNAL MAINTENANCE BYPASS SWITCH
for UPS XANTO 10,000 ­ 20,000 VA, 3/3-phase

1 Introduction
The module is used as an external maintenance bypass switch (Art.-No. HU10-20kVA33-RACK) to provide continuous power without shutting down the connected loads during UPS scheduled maintenance or battery replacement. It is perfect to use in conjunction with 3-phase in/out 10/20 kVA UPS.
The module can be installed in a 19″ rack.

2 Product Overview

6

7

2

3

1

4

5

8

1. UPS Input Breaker 2. Maintenance bypass switch (with Maintenance switch cover) 3. Control output signal connector 4. Output terminal
Technical data

5. Utility input terminal 6. UPS output terminal 7. UPS input terminal 8. Grounding terminal

Dimensions Weight

88 x 440 x 195 mm (height x width x depth) 3.8 kg

User manual External Maintenance Bypass Switch · Page 3

3 Installation
Inspection
Unpack the package and check the package contents. The shipping package contains:
· 1 x External maintenance bypass switch · 1 x Quick guide · 1 x Control signal cable
PLEASE NOTE Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking from some parts. Please keep the original package in a safe place for future use.

Initial Setup
The Installation and wiring must be performed in accordance with the local electric laws / regulations and execute the following instructions by professional personnel.
1) Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.

PLEASE NOTE Do not use the wall receptacle as the input power source for the UPS, as it is rated current is less than the UPS’s maximum input current. Otherwise, the receptacle may be burned and destroyed.

2) Switch off the mains switch in the building before installation. 3) Turn off and shut down the connected UPS. 4) Prepare wires based on the following table:

UPS Model
10 kVA UPS 20 kVA UPS

Wire Spec (AWG)
12 10

PLEASE NOTE All wire requirements are in accordance with the line diameter provided in the table. The selections for color of wires should be followed by the local electrical laws and regulations.
5) Remove the terminal block cover on the rear panel of the module. Then connect the wires according to the following terminal block diagrams: Connect UPS and External Maintenance Bypass Switch. Remove the terminal block cover on the rear panel of the module. Then connect output terminals of
User manual External Maintenance Bypass Switch · Page 4

UPS to output terminals of switch module. Connect utility input terminals of UPS-to-UPS input terminals of switch module. Connect signal slots of UPS and switch module with control signal cable attached to the package.
4 Operation
Normal operation
Load is supplied by UPS via rectifier and inverter
User manual External Maintenance Bypass Switch · Page 5

Transfer to Bypass Operation
Step 1 ­ switch UPS to internal Bypass (please refer to UPS manual) Load is supplied direct from UPS input
Step 2 ­ open the maintenance switch cover then turn External Maintenance Bypass Switch on HU10-20KVA-3/3-RACK to BYBASS position Load is supplied direct from Mains via HU10-20KVA-3/3-RACK
User manual External Maintenance Bypass Switch · Page 6

Step 3 ­ switch UPS Input Breaker on HU10-20KVA-3/3-RACK to position OFF Load is supplied direct from Mains via HU10-20KVA-3/3-RACK ­ UPS is OFF

Transfer to Normal Operation
Step 1 ­ switch UPS Input Breaker on HU10-20KVA-3/3-RACK to position ON Step 2 ­ turn Maintenance Bypass Switch on HU10-20KVA-3/3-RACK to UPS position then close the maintenance switch cover Step 3 ­ switch UPS to Normal Operation (please refer to UPS manual)
5 Specification of Critical Components

Model

Parameter

Input breaker (each pole) Bypass switch Input / Output terminal

Current Voltage Current Voltage Current Voltage

10 kVA UPS
Max.
25 A 400 V 25 A 400 V 32 A 400 V

20 kVA UPS
Max.
40 A 400 V 40 A 400 V 40 A 400 V

User manual External Maintenance Bypass Switch · Page 7

6 Support
ONLINE USV-Systeme AG (ONLINE) is one of the leading manufacturers of uninterruptible power supplies (UPS). Since 1988, the German company has focussed on the development, production, sale and support of UPS systems. Based on unit numbers sold, ONLINE products are the German number one in the UPS market and internationally recognised because of their top quality and excellent support. As a German provider, ONLINE guarantees direct approachability, simple processing and short response times. Comprehensive support is a matter of course ­ before and after purchase.
ONLINE sets great store by reliable support and service.
· Free direct advice and support on: E-Mail: support@online-usv.de Phone: +49 (0)89 242 39 90-17
· Free 24 h advance exchange · Interactive UPS configurator online or as app · Optional extended warranty · Unbureaucratic 14 day money-back guarantee · Excellent product availability and wide network of distributors Further information: > www.online-ups.com
User manual External Maintenance Bypass Switch · Page 8

7 Warranty
ONLINE USV-Syteme AG (ONLINE) guarantees that this product will be free of material and production faults for a period of three years from the purchase date. ONLINE’s obligation in accordance with this guarantee is restricted to the repair or replacement (at ONLINE’s discretion) of any faulty products. Before warranty claims can be asserted, a Returned Material Authorization (RMA) number must be obtained from customer services. Products must be returned with the postage paid by the sender, a brief description of the problem and evidence of the place and date of purchase. This warranty does not apply to devices damaged by accidents, negligence or misuse or those which have otherwise been altered or modified. Apart from the above exceptions, ONLINE accepts no explicit or tacit warranty, including a guarantee of conventional quality or suitability for a specific purpose. In some jurisdictions, the restriction or exclusion of tacit guarantees is prohibited, which means that the restrictions or exclusions above may not apply to the purchaser. Irrespective of the above exclusions, ONLINE shall under no circumstances for direct, indirect, specific, auxiliary or subsequent damage caused as a result of the use of this product, even if ONLINE was informed about the possibility of such damage. In particular, ONLINE shall not be liable for costs of whatsoever nature, such as lost profit or revenue, loss of equipment, loss of the use of device, loss of software or data, replacement costs, third-party claims or other costs.
User manual External Maintenance Bypass Switch · Page 9

Imprint

ONLINE USV-Systeme AG
Luise-Ullrich-Straße 8 82031 Grünwald/Germany Phone +49 (0)89-242 39 90-10 E-Mail info@online-usv.de > www.online-usv.de

ONLINE USV-Systeme AG c/o swizzconnexx
Pilatusstrasse 17 5630 Muri/Switzerland
Phone +41 (0)41-500 28 68 E-Mail info@online-usv.ch
> www.online-usv.ch

ONLINE UPS-Systems S.r.l.
Via Ferruccio Gilera 110 20862 Arcore (MB)/Italia Phone +39 (0)39-205 14 44 E-Mail commerciale@online-ups.it > www.online-ups.it

The content is copyright © 2025 by ONLINE USV-Systeme AG. All rights reserved. Unauthorised reproduction in part or in whole is not permitted without consent.

User manual External Maintenance Bypass Switch · Page 10

ONLINE USV-Systeme AG · Luise-Ullrich-Straße 8 · DE 82031 Grünwald · www.online-usv.de

Documents / Resources

ONLINE 10 kVA UPS External Maintenance Bypass Switch [pdf] User Manual
HU10-20kVA33-RACK, 10 kVA UPS External Maintenance Bypass Switch, 10 kVA UPS, External Maintenance Bypass Switch, Maintenance Bypass Switch, Bypass Switch, Switch

References

Leave a comment

Your email address will not be published. Required fields are marked *