nyleLOGO

Nyle R513A BMSe Gateway

nyle-R513A-BMSe-Gateway-PODUCT

nyle-R513A-BMSe-Gateway-FIG-1

Description

The BMS Gateway accessory for e-Series and R513A C-Series heat pumps allows direct communication from a heat pump to building management systems programmed by third parties. It allows commands and data to be transferred in both directions.Older R134A C-Series heat pumps are compatible with this accessory; however, some points will not be available on older units. BMS-C gateways are recom-mended with R134A C-Series heat pumps The gateway is installed inside the heat pump’s elec-trical enclosure on a factory-supplied DIN rail. Then, it is wired to the BMS system through Ethernet and/or control wiring terminals. One gateway accessory package is required for each heat pump that is to be connected to a BMS system. Systems with Main Control Panels do not need this accessory if the BMS Gateway option was selected for the MCP, and the MCP installation manual should be consulted for configuration information for those systems.
Your gateway may be field-installed, or it may be factory-installed. If factory-installed, refer only to the “Field Supplied Items Required” and “Configuration and BMS Integration” sections of this manual.

Safety Precautions

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER.

Ensure control power is OFF at the control panel when wiring accessories to the unit to prevent injury or death due to electrical shock.

WARNING

To prevent inductive power transfer, do not run sensor or communication wiring in parallel with any wires carrying 120v or greater voltage power. If this is unavoidable, use shielded wire or conduit for sensor wiring.

Dimensions, Specifications, and Required Items

nyle-R513A-BMSe-Gateway-FIG-2

Included in kit:

  • 1x BMS Gateway unit
  • 1x Power Wire
  • 1x Communication Wire

Field requirements for installation:

  • Active BACnet® IP or MSTP BMS system
  • Ethernet cable to BACnet IP BMS, OR
  • 22-3 minimum twisted/shielded wire to BACnet MSTP BMS
  • Ethernet cable to laptop for configuration
  • Small phillips head screwdriver
  • Multimeter
  • Laptop for configuration
  • BMS integrator responsible for final programming.

Specifications

nyle-R513A-BMSe-Gateway-FIG-3

  • Installation
  • Mounting
  • Note: If the gateway unit was factory-installed,please skip this section.
  • To mount the gateway:

DANGER

Power the heat pump off at the breaker so no live voltage power is present at the unit to prevent injury or death due to electrical shock.

  1. Open the door to the electrical enclosure.
  2. Identify the mounting location. The heat pump will have a vacant DIN rail space in the electrical enclo-sure box available to mount the gateway. The exact location of the vacant DIN rail space varies by heat pump or main control panel, and can be found in the installation manuals for those products in their “Control Wiring” sections. The gateway unit can be mounted vertically or horizontally
  3. Hook the Gateway unit over the top DIN rail in the specified mounting location.

Wiring
Note: If the gateway unit was factory-installed, please skip this section.

DANGER

Power the heat pump offat the breaker, so no live power is present at the unit to prevent injury or death due to electrical shock.

Within the heat pumps electrical enclosure:

  1. Wire the Gateway R1: TX+/RX-/GND terminals to the heat pump’s communication module with 22-3 minimum twisted pair cable. Refer to Figure 1.
  2. Wire the Gateway FG/N-/L terminals to the heat pump’s Terminal Block 1 (TB1) with 18-3 minimum solid or stranded wire.
  3. Make wiring connections from the enclosure to the building BMS systems.
    1. BACnet® IP systems use ethernet
    2. BACnet MSTP systems use 22-3 minimum twisted pair cable

For MSTP Systems Only:

  • NOTICE: Refer to your BMS System’s manual for specifics on how to set up the termination and bias resistors on the BMS Gateway component.

Figure 1: BMS Gateway Wiring

nyle-R513A-BMSe-Gateway-FIG-4

Configuration and BMS Integration

WARNING: DO NOT connect the heat pump to the building network before gateway configuration! This will potentially overwrite the default IP address of the gateway and make finding the gateway on the network more difficult. If this occurs, it may be necessary to find the gateway on the network using the MAC address on the gateway label.

Configuration Prep and Login 

  1. Power up the heat pump, and allow it to finish its startup, before attempting to configure the BMS gateway. After startup is completed, connect a laptop or PC directly to the gateway, using the ethernet port on the gateway.
  2. Open a web browser and connect directly to https://192.168.1.24
  3. You may get a “Web Server Security Uncon-figured” message. It is ok to proceed with HTTPS from that warning message.
  4. You may get a “Your Connection is not Pri-vate” message. If so, click “Advanced”, and click “proceed to 192.168.1.24 (unsafe)”.
  5.  Login to the gateway web interface. Username is “admin”. Password is written on the gateway’s la-bel, and is also available via QR code on the gate-way. It may be necessary to temporarily unseat the gateway from the DIN rail to read the label.
  6. On the first login, the security mode will need to be set. Nyle recommends “Basic HTTP” or “HTTPS with own trusted certificate”.
  7. After selecting a mode, you will get a “redirecting” message, and then the Fieldserver GUI should open.

Network Settings

  1. To configure network settings, on the GUI land-ing page, click on the “Settings” tab. Within “Set-tings”, click on the “Network” tab.
  2. On the first connection, you will get a warning message that you are about to leave the reg-istration process. Click “Exit Registration”.
  3. You should now see a page with “ETH 1” and “Routing” tabs. Click the “Routing” tab.
  4. Select the default connection in the first row of the table.
  5. Click the “Add Rule Button” to add a new row.
  6. Set a new Destination Network, Netmask, and Gateway IP Address as needed.
  7. Set the priority for each connection from 1 (highest) to 255 (lowest).
  8. Click the “Save” button.
  9. Now click the “ETH 1” tab to access the ethernet settings.
  10. Be advised, if IP addresses are changed, you will need to reconnect to the gateway via your browser using the new IP address before you can continue with configuration settings! Only proceed once ready to connect to the building’s network.
  11. DHCP to automatically accept IP settings can be enabled here, or IP settings can be manually configured.
    1.  For manual configuration, set IP Address, Netmask, Default Gateway, and Domain Name Server.
    2.  If the gateway will be connected to a router, the gateway MUST set the “Gateway” field to the IP address of the router.
  12. Click “Save” to activate the settings changes.

Protonode Configuration

  1. To configure the protonode, start from the “Device List” page in the GUI and click “Settings”.
  2. 10. Choose “Configuration”, and click the “Profiles Configuration” Button.
    • Set the “protocol_select” field
    • Set to 1 for BACnet IP
    • Set to 2 for BACnet MSTP
    • Set to 3 for BACnet MSTP (Single Node)
    • Hit “submit” after entering the correct value.
  3. Selecting a protocol will change the list of visible param-eters to only parameters applicable to your protocol.
  4. Set the remaining parameters according to the needs of your network and BMS system. Press “submit” to save each value.
  5. Refer to “Table 1: Configuration Parameters for BMS Gateway” on page 8
  6. If your gateway was factory installed, this step was done in the factory. Click the “Add Profile” Button.
    •  Choose profile “Group 1” for the e360 heat pump.
    • Choose profile “Group 2” for all C-Series heat pumps.
    • Verify the chosen profile is in the “Active Pro-files” list.
    • When verified, press the ‘System Restart” button.
  7. Connect the gateway to the building network.
  8. Reconnect to the new gateway IP address with your web browser, if necessary. Verify communi-cations in accordance with the “Testing” instruc-tions in the next section.
  9. The gateway should now allow for building man-agement system integration. Points lists for dif-ferent heat pumps are available at the end of this section for this process.

Table 1: Configuration Parameters for BMS Gateway

nyle-R513A-BMSe-Gateway-FIG-5

Points Lists
The Group 1 profile for e360 Heat Pumps allows access to the following points:

nyle-R513A-BMSe-Gateway-FIG-6

nyle-R513A-BMSe-Gateway-FIG-7

Points Lists

nyle-R513A-BMSe-Gateway-FIG-8

The Group 2 profile for R513A C-Series heat pumps allows access to the following points:

nyle-R513A-BMSe-Gateway-FIG-9

nyle-R513A-BMSe-Gateway-FIG-10

nyle-R513A-BMSe-Gateway-FIG-11

Testing
Good practice will include thorough verification that values reported by the heat pump match the values received in the BMS system. Ideally, this would include monitoring through an active heat demand and comparing BMS-reported values to heat pump-reported values. In addition, system communication can be checked. For serial connections, check that the TX and RX LEDs are rapidly ashing. You can also log into the field server GUI with a web browser, as in the “configuration” section. From there, clicking on “Diagnostics and Debugging” and then on “connections”, shows you a table of communication connections. The “errors” column would indicate if there are errors requiring additional troubleshooting. Communication errors are usually caused by:

  • Baud rate, parity, data bits, or stop bits set incorrectly
  • Device addresses incorrectly
  • Wiring problems
  • Device not listed in the Web Configurator
  • IP Addressing incorrect.

If communication errors cannot be troubleshot, a “Di-agnostic Capture” can be taken and emailed to Nyle Water Heating for assistance.

  1. Connect to the field server GUI with your web browser
  2. Click on “Diagnostics”
  3. Select “Full Diagnostic”
  4. Set the capture time period
  5. Click Start. When the capture period is finished, a download button will appear.
  6. Download the capture
  7. Email the capture to NWHScontrols@nyle.com, along with any supporting information needed to describe your problem.

Service Log

nyle-R513A-BMSe-Gateway-FIG-12

690 Maine Ave Bangor, ME 04401 1 (844)-432-8420

Nyle Water Heating Systems engages in continuous improvement. Sequences, features and capabilities can change without notice at any time. Refer to most current documentation prior to installation or commissioning of all equipment.

FAQS

Q: Can older R134A C-Series heat pumps use the BMS Gateway accessory?

A: Older R134A C-Series heat pumps are compatible with the BMS Gateway accessory, but some points may not be available on older units. It is recommended to use BMS-C gateways with R134A C-Series heat pumps.

Q: How do I know if I need the BMS Gateway accessory for my Main Control Panel?

A: Systems with Main Control Panels do not need the BMS Gateway accessory if the BMS Gateway option was selected for the MCP. Refer to the MCP installation manual for configuration information for those systems.

Documents / Resources

nyle R513A BMSe Gateway [pdf] Instruction Manual
R513A BMSe Gateway, R513A, BMSe Gateway, Gateway

References

Leave a comment

Your email address will not be published. Required fields are marked *