nVent RAYCHEM LogoJBM-100-E/JBM-100-EP
JBM-100-L-E/JBM-100-L-EP
Multiple Entry Power Connection with Junction Box
Instructions

JBM-100-L-EP Multiple Entry Power Connection with Junction Box

Multiple entry power connection with junction box

nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 1 nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Parts 1

JBM-100-E
JBM-100-EP
JBM-100-L-E
JBM-100-L-EP

PTB 20 ATEX 1008 U
BAS 21 UKEX 0657 U
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Icon II 2 G Ex eb mb IIC Gb
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Icon II 2 D Ex tb mb IIIC Db
IECEx PTB 20.0014U
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Icon 1 JBM-100-E(P):
ТС RU C-BE.МЮ62.В.00054/18
Ex e IIC Gb U Ex tb IIIC Db U
Ex e mb IIC Gb U Ex tb mb IIIC Db U
Ta –55°C…+56°C IP66
ООО “ТехИмпорт”
JBM-100-L-E(P):
ТС RU C-BE.МЮ62.В.00054/18
Ex e IIC Gb U Ex tb IIIC Db U
Ex e mb IIC Gb U Ex tb mb IIIC Db U
Ta –55°C…+40°C IP66
ООО “ТехИмпорт”
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Icon 2 Non lighted versions (1):
Ex e IIC Gb
Ex tD A21 IP66
Lighted versions (2):
Ex e mb IIC Gb
Ex tD mbD 21 IP66
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Icon 3 Ex eb IIC T* Gb
Ex eb mb IIC T* Gb
BAS 21 UKEX 0657 U Ex eb mb IIC Gb
Ex tb mb IIIC Db
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Icon 4 Non lighted versions (1):
CL I ZN 1 AEx eb IIC T* Gb
ZN 21 AEx tb IIIC T*°C Db
Ex eb IIC T* Gb
Ex tb IIIC T*°C Db
Lighted versions (2):
CL I ZN 1 AEx eb mb
IIC T* Gb
ZN 21 AEx mb tb IIIC
T*°C Db
Ex eb mb IIC T* Gb
Ex mb tb IIIC T*°C Db

* For system Temperature Code, see heating cable or design documentation.
** Specific conditions for use may apply for ATEX/UKEX and IECEx.

  1. Non lighted versions:
  2. Lighted versions:

POOL BLASTER 30000ML Cordless Vacuum Cleaner - Icon 1 WARNING: To prevent electrical shock, short circuit or arc ing, this prod uct must be in stalled correctly and water ingress must be avoid ed before and during the installation.
POOL BLASTER 30000ML Cordless Vacuum Cleaner - Icon 1 WARNING: The purchaser should make the manufacturer aware of any external effects or aggressive substances that the equipment may be exposed to.
Before installing this product, read the installation instructions completely.
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Icon 5 CAUTION: Prolonged or repeated contact with the sealant in the core sealer may cause skin irritation. Wash hands thoroughly. Overheating or burning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination of cigarettes or tobacco. Consult MSDSVEN 0058 for further information.

Rated voltage nVent RAYCHEM JBM-100-E(P): 480 Vac** JBM-100-L-E(P): 254 Vac
Ambient temperature JBM-100-E(P): –55°C to +56°C**
JBM-100-L-E(P): –40°C to +40°C, except for VPL: in that case ambient temperature can be up to +56°C.
Ingress protection IP66

Maximum pipe temperature:

Heater type Tmax continuous Tmax intermittent 1000 h cumulative Tmax power off
BTV 65°C 85°C
QTVR 110°C 110°C
XTV 121°C 250°C
KTV 150°C 250°C
HTV 205°C 260°C
VPL See tables below 260°C

VPL: maximum pipe temperature in dependence of heat type and voltage

Heater Type  230 Vac  254 Vac  277 Vac
5VPL2-CT 230°C 225°C 225°C
10VPL2-CT 210°C 200°C 195°C
15VPL2-CT 180°C 145°C 105°C
20VPL2-CT 150°C Not allowed
Heater Type  385 Vac  400 Vac  480 Vac
5VPL4-CT 230°C 230°C 230°C
10VPL4-C 215°C 215°C 205°C
15VPL4-C 195°C 195°C 160°C
20VPL4-C 150°C 150°C 150°C

VPL: Maximum pipe temperature in dependence

≤ 150°C ≤ 180°C ≤ 230°C
30 A 25 A 20 A
30 A 25 A 20 A
30 A 25 A
30 A
≤ 150°C ≤ 180°C ≤ 230°C
30 A 25 A 20 A
30 A 25 A 20 A
30 A 25 A
30 A

Specific conditions for use using ATEX/UKEX or IECEx approvals:
For ambient temperatures >+40°C:
Use a power cable with continuous temperature resistance of minimum +90°C
Use a metallic power cable gland approved for use in hazardous areas (for example GL-38-M25-METAL).
For voltages >254 Vac and BTV, QTVR, XTV, KTV or HTV heating cables:
Use a power cable with continuous temperature resistance of minimum +90°C
Use a metallic power cable gland approved for use in hazardous areas (for example GL-38-M25-METAL).
For pipe temperature > 150°C and XTV, KTV or HTV heating cables, the maximum operating current shall be reduced to maximum 20A.

nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 2 nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 2
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 4 nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 5
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 6 nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 7
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 8 nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 9
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 10 nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 11
nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 12 nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 13

nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 14

Remove the tubes and dispose of them in the core sealer plastic bag.

nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 15

nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 16 nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 17

nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 18

Install power cable and gland. Pull in power and ground wires, strip off 13 mm of insulation and terminate. (For -EP version only: connect earth plate to ground according to local requirements).

nVent RAYCHEM JBM 100 L EP Multiple Entry Power Connection with Junction Box - Figure 19

Install lid.
τ = 1.02 to 1.47Nm
Apply insulation and cladding.
Warning icon Weather seal the stand entry.
Leave these instructions with the end user for future reference.

North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com
België/Belgique
Tel +32 16 21 35 02
Fax +32 16 21 36 04
salesbelux@nVent.com
Bulgaria
Tel +359 5686 6886
Fax +359 5686 6886
salesee@nVent.com
Česká Republika
Tel +420 606 069 618
czechinfo@nVent.com
Danmark
Tel +45 70 11 04 00
Fax salesdk@nvent.com
salesdk@nVent.com
Deutschland
Tel 0800 1818205
Fax 0800 1818204
salesde@nVent.com
España
Tel +34 911 59 30 60
Fax +34 900 98 32 64
ntm-sales-es@nVent.com
France
Tél 0800 906045
Fax 0800 906003
salesfr@nVent.com
Hrvatska
Tel +385 1 605 01 88
Fax +385 1 605 01 88
salesee@nVent.com
Italia
Tel +39 02 577 61 51
Fax +39 02 577 61 55/28
salesit@nVent.com
Lietuva/Latvija/Eesti
Tel +370 5 2136633
Fax +370 5 2330084
info.baltic@nVent.com
Magyarország
Tel +36 1 253 7617
Fax +36 1 253 7618
saleshu@nVent.com
Nederland
Tel 0800 0224978
Fax 0800 0224993
salesnl@nVent.com
Norge
Tel +47 66 81 79 90
salesno@nVent.com
Österreich
Tel +0800 29 74 10
Fax +0800 29 74 09
salesat@nVent.com
Polska
Tel +48 22 331 29 50
Fax +48 22 331 29 51
salespl@nVent.com
Republic of Kazakhstan
Tel +7 7122 32 09 68
Fax +7 7122 32 55 54
saleskz@nVent.com
Россия
Тел +7 495 926 18 85
Факс +7 495 926 18 86
salesru@nVent.com
Serbia and Montenegro
Tel +381 230 401 770
Fax +381 230 401 770
salesee@nVent.com
Schweiz/Suisse
Tel +41 (41) 766 30 80
Fax +41 (41) 766 30 81
infoBaar@nVent.com
Suomi
Puh 0800 11 67 99
salesfi@nVent.com
Sverige
Tel +46 31 335 58 00
salesse@nVent.com
Türkiye
Tel +90 560 977 6467
Fax +32 16 21 36 04
salesee@nVent.com
United Kingdom
Tel 0800 969 013
Fax 0800 968 624
salesthermaluk@nVent.com

nVent RAYCHEM LogonVent.com/RAYCHEM
©2022 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates.
All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.
RAYCHEM-IM-INSTALL038-JBM100X-ML-2210

Documents / Resources

nVent RAYCHEM JBM-100-L-EP Multiple Entry Power Connection with Junction Box [pdf] Instructions
JBM-100-E, JBM-100-EP, JBM-100-L-E, JBM-100-L-EP, JBM-100-L-EP Multiple Entry Power Connection with Junction Box, Multiple Entry Power Connection with Junction Box, Entry Power Connection with Junction Box, Connection with Junction Box, Junction Box

References

Leave a comment

Your email address will not be published. Required fields are marked *