JBM-100-E/JBM-100-EP
JBM-100-L-E/JBM-100-L-EP
Multiple Entry Power Connection with Junction Box
Instructions
JBM-100-L-EP Multiple Entry Power Connection with Junction Box
Multiple entry power connection with junction box
![]() |
![]() |
JBM-100-E
JBM-100-EP
JBM-100-L-E
JBM-100-L-EP
PTB 20 ATEX 1008 U BAS 21 UKEX 0657 U |
![]() ![]() |
|
IECEx PTB 20.0014U | ||
![]() |
JBM-100-E(P): ТС RU C-BE.МЮ62.В.00054/18 Ex e IIC Gb U Ex tb IIIC Db U Ex e mb IIC Gb U Ex tb mb IIIC Db U Ta –55°C…+56°C IP66 ООО “ТехИмпорт” JBM-100-L-E(P): ТС RU C-BE.МЮ62.В.00054/18 Ex e IIC Gb U Ex tb IIIC Db U Ex e mb IIC Gb U Ex tb mb IIIC Db U Ta –55°C…+40°C IP66 ООО “ТехИмпорт” |
|
![]() |
Non lighted versions (1): Ex e IIC Gb Ex tD A21 IP66 |
Lighted versions (2): Ex e mb IIC Gb Ex tD mbD 21 IP66 |
![]() |
Ex eb IIC T* Gb Ex eb mb IIC T* Gb |
|
BAS 21 UKEX 0657 U | Ex eb mb IIC Gb Ex tb mb IIIC Db |
|
![]() |
Non lighted versions (1): CL I ZN 1 AEx eb IIC T* Gb ZN 21 AEx tb IIIC T*°C Db Ex eb IIC T* Gb Ex tb IIIC T*°C Db |
Lighted versions (2): CL I ZN 1 AEx eb mb IIC T* Gb ZN 21 AEx mb tb IIIC T*°C Db Ex eb mb IIC T* Gb Ex mb tb IIIC T*°C Db |
* For system Temperature Code, see heating cable or design documentation.
** Specific conditions for use may apply for ATEX/UKEX and IECEx.
- Non lighted versions:
- Lighted versions:
WARNING: To prevent electrical shock, short circuit or arc ing, this prod uct must be in stalled correctly and water ingress must be avoid ed before and during the installation.
WARNING: The purchaser should make the manufacturer aware of any external effects or aggressive substances that the equipment may be exposed to.
Before installing this product, read the installation instructions completely.
CAUTION: Prolonged or repeated contact with the sealant in the core sealer may cause skin irritation. Wash hands thoroughly. Overheating or burning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination of cigarettes or tobacco. Consult MSDSVEN 0058 for further information.
Rated voltage | nVent RAYCHEM JBM-100-E(P): 480 Vac** JBM-100-L-E(P): 254 Vac |
Ambient temperature | JBM-100-E(P): –55°C to +56°C** JBM-100-L-E(P): –40°C to +40°C, except for VPL: in that case ambient temperature can be up to +56°C. |
Ingress protection | IP66 |
Maximum pipe temperature:
Heater type | Tmax continuous | Tmax intermittent 1000 h cumulative | Tmax power off |
BTV | 65°C | 85°C | – |
QTVR | 110°C | 110°C | – |
XTV | 121°C | 250°C | – |
KTV | 150°C | 250°C | – |
HTV | 205°C | 260°C | – |
VPL | See tables below | – | 260°C |
VPL: maximum pipe temperature in dependence of heat type and voltage
Heater Type | 230 Vac | 254 Vac | 277 Vac |
5VPL2-CT | 230°C | 225°C | 225°C |
10VPL2-CT | 210°C | 200°C | 195°C |
15VPL2-CT | 180°C | 145°C | 105°C |
20VPL2-CT | 150°C | Not allowed |
Heater Type | 385 Vac | 400 Vac | 480 Vac |
5VPL4-CT | 230°C | 230°C | 230°C |
10VPL4-C | 215°C | 215°C | 205°C |
15VPL4-C | 195°C | 195°C | 160°C |
20VPL4-C | 150°C | 150°C | 150°C |
VPL: Maximum pipe temperature in dependence
≤ 150°C | ≤ 180°C | ≤ 230°C |
30 A | 25 A | 20 A |
30 A | 25 A | 20 A |
30 A | 25 A | – |
30 A | – | – |
≤ 150°C | ≤ 180°C | ≤ 230°C |
30 A | 25 A | 20 A |
30 A | 25 A | 20 A |
30 A | 25 A | – |
30 A | – | – |
Specific conditions for use using ATEX/UKEX or IECEx approvals:
For ambient temperatures >+40°C:
Use a power cable with continuous temperature resistance of minimum +90°C
Use a metallic power cable gland approved for use in hazardous areas (for example GL-38-M25-METAL).
For voltages >254 Vac and BTV, QTVR, XTV, KTV or HTV heating cables:
Use a power cable with continuous temperature resistance of minimum +90°C
Use a metallic power cable gland approved for use in hazardous areas (for example GL-38-M25-METAL).
For pipe temperature > 150°C and XTV, KTV or HTV heating cables, the maximum operating current shall be reduced to maximum 20A.
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
Remove the tubes and dispose of them in the core sealer plastic bag.
![]() |
![]() |
Install power cable and gland. Pull in power and ground wires, strip off 13 mm of insulation and terminate. (For -EP version only: connect earth plate to ground according to local requirements).
Install lid.
τ = 1.02 to 1.47Nm
Apply insulation and cladding.
Weather seal the stand entry.
Leave these instructions with the end user for future reference.
North America Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nVent.com |
België/Belgique Tel +32 16 21 35 02 Fax +32 16 21 36 04 salesbelux@nVent.com |
Bulgaria Tel +359 5686 6886 Fax +359 5686 6886 salesee@nVent.com |
Česká Republika Tel +420 606 069 618 czechinfo@nVent.com |
Danmark Tel +45 70 11 04 00 Fax salesdk@nvent.com salesdk@nVent.com |
Deutschland Tel 0800 1818205 Fax 0800 1818204 salesde@nVent.com |
España Tel +34 911 59 30 60 Fax +34 900 98 32 64 ntm-sales-es@nVent.com |
France Tél 0800 906045 Fax 0800 906003 salesfr@nVent.com |
Hrvatska Tel +385 1 605 01 88 Fax +385 1 605 01 88 salesee@nVent.com |
Italia Tel +39 02 577 61 51 Fax +39 02 577 61 55/28 salesit@nVent.com |
Lietuva/Latvija/Eesti Tel +370 5 2136633 Fax +370 5 2330084 info.baltic@nVent.com |
Magyarország Tel +36 1 253 7617 Fax +36 1 253 7618 saleshu@nVent.com |
Nederland Tel 0800 0224978 Fax 0800 0224993 salesnl@nVent.com |
Norge Tel +47 66 81 79 90 salesno@nVent.com |
Österreich Tel +0800 29 74 10 Fax +0800 29 74 09 salesat@nVent.com |
Polska Tel +48 22 331 29 50 Fax +48 22 331 29 51 salespl@nVent.com |
Republic of Kazakhstan Tel +7 7122 32 09 68 Fax +7 7122 32 55 54 saleskz@nVent.com |
Россия Тел +7 495 926 18 85 Факс +7 495 926 18 86 salesru@nVent.com |
Serbia and Montenegro Tel +381 230 401 770 Fax +381 230 401 770 salesee@nVent.com |
Schweiz/Suisse Tel +41 (41) 766 30 80 Fax +41 (41) 766 30 81 infoBaar@nVent.com |
Suomi Puh 0800 11 67 99 salesfi@nVent.com |
Sverige Tel +46 31 335 58 00 salesse@nVent.com |
Türkiye Tel +90 560 977 6467 Fax +32 16 21 36 04 salesee@nVent.com |
United Kingdom Tel 0800 969 013 Fax 0800 968 624 salesthermaluk@nVent.com |
nVent.com/RAYCHEM
©2022 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates.
All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.
RAYCHEM-IM-INSTALL038-JBM100X-ML-2210
Documents / Resources
![]() |
nVent RAYCHEM JBM-100-L-EP Multiple Entry Power Connection with Junction Box [pdf] Instructions JBM-100-E, JBM-100-EP, JBM-100-L-E, JBM-100-L-EP, JBM-100-L-EP Multiple Entry Power Connection with Junction Box, Multiple Entry Power Connection with Junction Box, Entry Power Connection with Junction Box, Connection with Junction Box, Junction Box |