IM-H55092 RayClic Connection System
Instruction Manual
APPROVALS
![]() |
718K Pipe Heating Cable |
![]() |
877Z De-Icing and Snow Melting Not UL Listed with XL-Trace Edge heating cable for buried piping |
![]() |
For HWAT and IceStop only Hazardous Locations: For IceStop (GM-XT) only Class I, Div. 2, Groups A, B, C, D |
DESCRIPTION
nVent RAYCHEM RayClic-PC Power Connection and End Seal Kit
nVent RAYCHEM RayClic-PS Powered Splice and End Seal Kit
nVent RAYCHEM RayClic-PT Powered Tee and End Seal Kit
These kits are for use with nVent RAYCHEM IceStop,
XL-Trace Edge and HWAT heating cables. The connection is designed to be strapped to the pipe or mounted on the wall at the start of the heating cable circuit. These installation instructions should be used in conjunction with the IceStop, XL-Trace Edge and HWAT System Installation and Operation Manuals. For technical support, contact your nVent representative or call nVent (800) 545-6258.
TOOLS REQUIRED
• Wire cutters | • TORX® T20 screwdriver |
• Utility knife | • Wrenches (2) |
ADDITIONAL UL LISTED OR CSA CERTIFIED MATERIALS REQUIRED:
- 1/2 inch conduit and fittings
- Junction box
OPTIONAL ACCESSORIES (NOT INCLUDED IN THIS KIT)
- RayClic-SB-02 Wall mounting bracket
WARNING:
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions.
- To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of nVent, agency certifications, and national electrical codes, ground fault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers.
- Bus wires will short if they contact each other. Keep bus wires separated.
- Keep components and heating cable ends dry before and during installation.
- The black heating cable core is conductive and can short. It must be properly insulated and kept dry.
- Component approvals and performance are based on the use of nVent-specified parts only. Do not use substitute parts or vinyl electrical tape.
- Leave these instructions with the end user for reference and future use.
KIT CONTENTS
RAYCLIC-PC POWER CONNECTION KIT
Item | Qty | Description |
A | 1 | Power connection |
B | 1 | Pipe mounting bracket |
C | 2 | Plastic cable ties |
D | 1 | Clip |
E | 1 | End seal |
F | 4 | Labels (1 HWAT, 1 Deicing & Snow Melting, 2 Warning) |
G | 1 | Cable lubricant |
RAYCLIC-PS POWERED SPLICE KIT
Item | Qty | Description |
A | 1 | Powered splice |
B | 1 | Pipe mounting bracket |
C | 2 | Plastic cable ties |
D | 2 | Clips |
E | 2 | End seals |
F | 4 | Labels (1 HWAT, 1 De-Icing & Snow Melting, 2 Warning) |
G | 1 | Cable lubricant |
RAYCLIC-PT POWERED TEE KIT
Item | Qty | Description |
A | 1 | Powered splice |
B | 1 | Pipe mounting bracket |
C | 2 | Plastic cable ties |
D | 3 | Clips |
E | 3 | End seals |
F | 4 | Labels (1 HWAT, 1 Deicing & Snow Melting, 2 Warning) |
G | 1 | Cable lubricant |
If you experience difficulty during installation, refer to the “Troubleshooting Guide” on page 8.
Power Connection, Splice, and Tee Installation
Roof Installation
End Seal Installation
Troubleshooting Guide
Problem | Solution |
Braid clips are missing. | The braid clips are attached to the cardboard packing insert under the lid. The braid clips must be used to ensure a ground connection. If clips are missing or lost, call nVent at 800-545-6258. |
The mounting bracket Is missing. | A pipe mounting bracket is supplied with the Power Connection, Powered Splice and Powered Tee kits. A wall molting bracket or additional pipe mounting bracket may be ordered using one of the catalog numbers listed under ‘Optional Accessories’ on the front page of these instructions when you place your order. |
The connector does not snap onto the bracket. | The bracket has two sets of attachment clips. Fold up the four outer clips for the Power Connection kit. Fold up only the center clips for the Powered Splice and Powered Tee kits. |
Heating cable type not mentioned. | nVent RAYCHEM RayClic connection kits are approved for use only with HWAT, XL-Trace Edge, and IceStop heating cables. Do not use it with other heating cables. |
The braid clip does not fit. | Be sure the clip is installed on the metal braid, not on the outer jacket. |
The heating cable does not have an aluminum wrap. | Only HWAT heating cables have the aluminum wrap under the braid. Skip the aluminum wrap removal step for XL-Trace Edge and IceStop heating cables. |
The heating cable cannot be inserted into the connector. | Check for the following: • Apply cable lubricant to the heating cable primary (white) jacket. • Outer jacket strip length is 31 /8 inches. • Braid clip is installed on top of the metal braid, not on the outer jacket. • Braid is pulled back over braid clip. • For HWAT, 1 inch of braid is removed. • Sealing nut is loose (but not removed). • Connection screws are loose. |
Ud does not close. | Be sure all screws are fully tightened before closing the lid. |
The heating cable cannot be inserted into the end seal. | The outer jacket must be removed from the heating cable before the end seal is installed (see the ‘End Seal Installation’ instructions on page 7). Make sure 1 inch of the outer jacket, braid, and aluminum wrap (HWAT only) are removed. |
The heating cable cannot be removed. | The power connection and end seal are designed to be installed only once; the heating cable cannot be removed once installed. Additional nVent RAYCHEM RayClic -E end seals can be ordered from Vent. |
Heating Cable Circuit Testing
Instructions:
- Open the RayClic Cover.
- Set multimeter to AC voltage function.
- Insert multimeter test probes into the two test ports.
WARNING: To avoid shock do not cross the test probes or touch them to the metal pressure plate when measuring voltage.
North America Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nVent.com |
Europe, Middle East, Africa Tel +32.16.213.511 Fax +32.16.213.604 thermal.info@nVent.com |
Asia Pacific Tel +86.21.2412.1688 Fax +86.21.5426.3167 cn.thermal.info@nVent.com |
Latin America Tel +1.713.868.4800 Fax +1.713.868.2333 thermal.info@nVent.com |
©2021 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
RAYCHEM-IM-H55092-RayClicConnectionSystem-EN-2111
nVent.com/RAYCHEM