NOTIFIER WRA-xC-I02 Wall Mounted Loop Powered Addressable Sounder Strobes

NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes-PRO

MODELS

  • WRA-xC-I02 = Sounder Strobe Isolation Red Flash
  • WWA-xC-I02 = Sounder Strobe Isolation White Flash
  • Adjustable performance
  • Wall Mounted Sounder Strobe
  • x = Denotes body colour (P – Pure White, R – Red)

GENERAL

  • The range is used in analogue addressable fire alarm systems.
  • These devices must only be connected to control panels that use a compatible proprietary analogue addressable communication protocol.
  • These devices receive their power from the loop, and can be controlled via the communication protocol(s).

Note: if the control equipment is not capable of taking over 99 module addresses, a fault condition will be generated for every address over 99. For isolator specification refer to document S00-7400 available on request.NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (1)

This symbol on our product shows a crossed-out “wheelie-bin” as required by law regarding the Waste of Electrical and Electronic Equipment (WEEE) disposal. This indicates your responsibility to contribute in saving the environment by proper disposal of this Waste i.e. Do not dispose of this product with your other wastes.
To know the right disposal mechanism please check the applicable law.

INSTALLATION / PRODUCT ORIENTATION

Affix B501AP to a suitably flat wall. Terminate the cable to the appropriate terminals. For surface mount wiring the cable can enter the B501AP via the break outs provided. Select the appropriate Light Coverage,Tone and Volume settings via the DIP switch.

Make sure the product is fitted in the correct orientation!
Scan the barcode below to see the correct fitting to the wall:NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (2)

CONTINUITY SPRING

The B501AP incorporates a continuity spring between terminals 2 and 4. This allows the continuity of the field wiring to be checked without the need for the device to be present. Inserting the device will disengage the spring. Removing the device will close the loop.NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (3)

TERMINAL CONNECTIONSNOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (4)

ANTI TAMPER RELEASE

IMPORTANT: Follow the instruction strictly:NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (5)

  1. Insert a flat screwdriver
  2. Lever the screwdriver down and twist the device anticlockwise.
  3. Remove the screwdriver to unlock the device.NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (6)

For a full video on how to release the anti-tamper feature please scan the QR code:NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (7)

Tone selection

DIP setting

SW 1,2,3,4,5

O=Off/1=On

No Pattern Type

 

Nominal Frequency Max consumption (mA, RMS) Switching Frequency Description Market Standard 2nd Stage Tone Typical Sound Output (dB)
Volume – HIGH (24V/15V) Volume – NORM (24V/15V) Volume – HIGH Volume – NORM
0,0,0,0,0 1 Alternating 525/440 9 / 15.4 4.7 / 8.1 2Hz (100ms/400ms) French Fire Sound
AFNOR
France NFS 32-001 7 99 98
1,0,0,0,0 2 Alternating 800/922 8.5 / 14.7 4.9 / 8.5 1Hz   UK BS5839 Pt1 8 98 95
0,1,0,0,0 3 Alternating 800/922 8.4 / 14.7 4.9 / 8.4 2Hz Alternating tone telecoms UK BS5839 Pt1, FP1063.1 8 97 94
1,1,0,0,0 4 Alternating 2400/2900 9.9 / 17.7 5.8 / 10.3 3Hz Alternating High Frequency     10 99 95
0,0,1,0,0 5 Alternating 2500/3100 10.2 / 18.3 4.3 / 7.5 2Hz Security Alarm     10 98 90
1,0,1,0,0 6 Alternating 988/645 10 / 17.8 6 / 10.5 2Hz       8 100 97
0,1,1,0,0 7 Continuous 630 8.6 / 15 3.1 / 5.3   All clear Sweden   1 98 94
1,1,1,0,0 8 Continuous 922 9.1 / 15.3 4.8 / 8.3       BS 5839 Pt 1 2 96 93
0,0,0,1,0 9 Continuous 1200 9.3 / 16.3 4.6 / 7.6         2 92 90
1,0,0,1,0 10 Continuous 2810 9 / 15 5 / 8.9   HF Continuous     4 97 93
0,1,0,1,0 11 Sweep 150-1000 9.7 / 17.2  

7 / 12.6

Rising from 150Hz to 1000Hz in 10 seconds, then 40 seconds at 1000Hz, then falling from 1000Hz to 150Hz in 10 seconds, then 20 seconds at 150Hz, then repeating. Total period 80 seconds.  

Gasalarm” Tone

   

22

 

100

 

98

1,1,0,1,0 12 Intermittent 420 8.8 / 15.4 5.1 / 8.6 0.625s on, 0.625 sec off AS2220 alert tone NZ, Aus AS2220 13 100 98
0,0,1,1,0 13 Sweep 500-1200 9 / 15.7 4.9 / 8.6 0.25 sec off, 3.75 sec on AS2220 evacuate tone NZ, Aus AS2220 12 101 99
1,0,1,1,0 14 Intermittent 630 8.4 / 14.7 3.1 / 5.3 3.33Hz 150ms on, 150ms off Swedish alarm tone Sweden   7 97 93
0,1,1,1,0 15 Intermittent 922 8.9 / 15.4 4.8 / 8.5 0.8Hz 0.25s on, 1s off Intermittent Tone UK BS 5839 Pt 1 8 95 91
1,1,1,1,0 16 Intermittent 922 8.9 / 15.5 4.8 / 8.5 0.5Hz 1s on, 1s off Back up alarm LF & BS5839 Pt 1 UK BS5839 Pt 1 8 96 90
0,0,0,0,1 17 Intermittent 2810 9.2 / 16.3 5.2 / 9.3 1Hz Back up alarm HF & BS5839 Pt 1 2nd tone UK BS5839 Pt 1 10 98 95
1,0,0,0,1 18 Intermittent 922 8.9 / 15.3 4.8 / 8.5 1Hz 500ms on, 500ms off LF BS5839 Pt 1 UK BS5839 Pt 1 8 95 92
0,1,0,0,1 19 Intermittent 950 10 / 17.8 5.5 / 9.8 0.22Hz (0.5s on, 0.5s off) rptx3, 1.5s off   Australia ISO8201 12 99 96
1,1,0,0,1 20 Continuous 800 7.9 / 13.8 3.1 / 5.3       BS 5839 Pt 1 22 98 94
0,0,1,0,1 21 Sweep 400-1200 8.8 / 15.8 4.7 / 8.2 (0.5s on, 0.5s off)*3, 1.5s off Temporal 3 Evacuation tone Australia ISO8201 Temporal 3 12 99 96
1,0,1,0,1 22 Sweep 1200 – 500 8.5 / 14.8 4.7 / 8.1 0.99Hz 1s on, 0.01s off Evacuate, DIN tone & PFEER Germany DIN, PFEER 20 100 98
0,1,1,0,1 23 Sweep 2400 – 2850 7.4 / 13.1 3.5 / 6 7Hz Fast sweep VdS Germany VdS 10 96 90
1,1,1,0,1 24 Sweep 500 – 1200 8.8 / 17.1 4.9 / 9.6 (0.5s off, 3.5s on) Slow whoop evacuate Netherlands Netherlands NEN 2575 8 98 96
0,0,0,1,1 25 Sweep 800 – 970 8.1 / 14.1 5.3 / 9.6 50Hz LF Buzz BS5839 Pt 1 UK BS5839 Pt 1 8 100 98
1,0,0,1,1 26 Sweep 800 – 970 7.6 / 13.2 3.3 / 5.6 7Hz Fast sweep LF BS5839 Pt 1 UK BS5839 Pt 1 8 100 95
0,1,0,1,1 27 Sweep 800 – 970 8.3 / 14.2 3.5 / 6 1Hz Medium sweep LF, BS5839 Pt 1, VdS UK, Germany BS5839 Pt 1 VdS 8 101 97
1,1,0,1,1 28 Sweep 2400 – 2850 6.5 / 11.5 3.3 / 5.7 50Hz High frequency buzz     10 96 90
0,0,1,1,1 29 Sweep 500 – 1000 8.9 / 15.6 3.6 / 5.8 7Hz Fast whoop     8 100 96
1,0,1,1,1 30 Sweep 500 – 1200 – 500 9.5 / 16.5 4.7 / 8.4 0.166Hz rise 1s, stable 4s, fall 1s Siren style tone     8 99 97
0,1,1,1,1 31 Sweep 800 – 1000 10 / 17.6 5.8 / 10.3 2Hz       8 101 99
1,1,1,1,1 32 Sweep 2400 – 2850 8.6 / 15.8 3.8 / 6.6 1Hz       10 97 91

Address settings

To set one of the 159 available addresses for the device use the two rotay switches located either side of the dip switch unit. The `tens` digits goes from 0 to 15 and the `units` from 0 to 9. *100 – 159 Only available with advanced protocol.

NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (8)

Dimensions

NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (9)

Volume, coverage and frequency settings

NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (10)

  • DIP setting 0=Off/

Table 2NOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (11)

Coverage dataNOTIFIER-WRA-xC-I02-Wall-Mounted-Loop-Powered-Addressable-Sounder-Strobes- (12)

For the `O` class detailed coverage data, in accordance with EN54-23, please request the following doc.: S00-7006

Notifier by Honeywell,
Pittway Tecnologica Srl, Via Caboto 19/3, 34147
Trieste, Italy

EN 54-3:2001 +A1: 2002 + A2:2006
Fire detection and fire alarm systems – Sounders

EN54-23:2010
Fire detection and fire alarm systems – Visual Alarm Devices

EN 54-17:2005
Fire detection and fire alarm systems – Short-circuit isolators.

W*A-*C-I02

For LPCB: approved to EN 54-3: 2014 + A1: 2019. Sounder Output data, in accordance with EN54-3, is available on Document Ref: S00-7005

KAC ALARM COMPANY LIMITED, Honeywell House, Skimped Hill Lane, Bracknell, Berks, RG12 1EB.
T. 02034091779
E. technical@kac.co.uk
W. www.kac.co.uk