NET LED - logo

Proudly working in partnership withNET LED 60598 1 FXBX LED Emergency Exit Box - icon 1NET LED 60598 1 FXBX LED Emergency Exit Box - icon

FXBX LED EMERGENCY EXIT BOXNET LED 60598 1 FXBX LED Emergency Exit Box - icon

Thank you for purchasing our FXBX LED Emergency Exit Box.
Our products have been designed according to the relevant standards and if installed and maintained correctly they will provide a long service life.
BS EN 60598-1 / BS EN 60598-2-22 / BS EN 50172 / BS EN 1838 / BS EN 62034 / ISO 7010 / ISO 3864

Installation, Maintenance, and Servicing Notes

NET LED 60598 1 FXBX LED Emergency Exit Box - fig

  • Ensure that the mains supply is switched off before installing, maintaining, or servicing the luminaire.
  • Luminaires should only be installed by qualified personnel.
  • The LED light source and control gear are non-replaceable. Once end-of-life is reached, the luminaire should be replaced.
  • In case of mains supply failure, the battery will automatically energize the emergency light for a minimum 3hr period. After 3hrs 5m the luminaire will enter standby mode to protect the battery from over-discharge. The battery must be recharged within 6 months of a full discharge.
  • Self-test emergency luminaires are programmed to carry out functional and full duration tests according to BS EN 50172:2004.
  • The first battery charge will take up to 16hrs.
  • Battery recharge takes up to 8hrs. Note that the full cycle (discharge and recharge) takes up to 12hrs.
  • Contact Fox Lux if a battery replacement is required.
  • Warranty terms apply. See website for details.

Testing Options

Standard Testing and commissioning must be carried out manually according to BS EN 50172:2004.
Self-test A functional test is carried out automatically once a week and runs for the 30s. Full duration test is carried out automatically every 52 weeks. The first full-duration test is carried out automatically within the first 4 weeks after the luminaire is connected to mains. This luminaire can be used with the optional Remote Control (REM10) which adds extra features to Fox Lux emergency luminaires. Please refer to the REM10 user  guide

.

LED Status Indications

GREEN LED  RED LED Green Red STATUS ACTION REQUIRED
Solid ON OFF NET LED 60598 1 FXBX LED Emergency Exit Box - icon 3 NET LED 60598 1 FXBX LED Emergency Exit Box - icon 2 OK
Normal Flash OFF NET LED 60598 1 FXBX LED Emergency Exit Box - icon 4 NET LED 60598 1 FXBX LED Emergency Exit Box - icon 2 Charging
OFF Solid ON NET LED 60598 1 FXBX LED Emergency Exit Box - icon 10 NET LED 60598 1 FXBX LED Emergency Exit Box - icon 6 Battery disconnected / Duration test failure Connect battery /
Replace battery
Fast Flash OFF NET LED 60598 1 FXBX LED Emergency Exit Box - icon 5 NET LED 60598 1 FXBX LED Emergency Exit Box - icon 2 Functional/Duration test in progress
Normal Flash Normal Flash NET LED 60598 1 FXBX LED Emergency Exit Box - icon 4 NET LED 60598 1 FXBX LED Emergency Exit Box - icon 7 Battery temperature Contact Fox Lux
OFF Normal Flash NET LED 60598 1 FXBX LED Emergency Exit Box - icon 10 NET LED 60598 1 FXBX LED Emergency Exit Box - icon 7 Light source fault Replace luminaire

NET LED 60598 1 FXBX LED Emergency Exit Box - icon 4Normal flash = 1Hz (once/second)
NET LED 60598 1 FXBX LED Emergency Exit Box - icon 5Fast flash = 2Hz (twice/second)

NET LED 60598 1 FXBX LED Emergency Exit Box - icon 8

Dustbin IconEnsure this product is disposed of responsibly according to WEEE directive 2002/96/EC

FXBX LED Exit Box

FXBX Exit Box Range

 

Reference Description Testing  Remote Operating temp. ta Net weight
FXBX/M/3 Emergency Exit Box 3hr Maintained (standard) Manual control 0°C – 40°C 1.15kg
FXBX-S/M/3 Emergency Exit Box 3hr Maintained (self-test) Self-test REM10* 0.14kg
FXBX-D DOWN ARROW legend panel
FXBX-R The RIGHT ARROW legend panel
FXBX-L The LEFT ARROW legend panel
FXBX-U UP ARROW legend panel

*Remote Control REM10 allows the competent user to carry out functional tests and/or full duration tests at any time and to check system status. Please refer to the REM10 user guide.

Installation Guide

1: Isolate mains supplyNET LED 60598 1 FXBX LED Emergency Exit Box - fig 2

Ensure that the mains supply is switched off before installing, maintaining, or servicing the emergency luminaire.

2: Remove side panel and legend

NET LED 60598 1 FXBX LED Emergency Exit Box - fig 3

3: Body installationNET LED 60598 1 FXBX LED Emergency Exit Box - fig 4

Drill where indicated and use wall plugs+screws*
Remove knock-out on the side or top if connected to 20mm conduit *supplied screws and rawl plugs are suitable for masonry only. Please purchase alternative fixings if required.

4: Electrical connectionNET LED 60598 1 FXBX LED Emergency Exit Box - fig 5

5: Restraint of cablesNET LED 60598 1 FXBX LED Emergency Exit Box - fig 6

Secure mains cable by using cable clip and screws or the grommet supplied in the box.

6: Integrated downlightNET LED 60598 1 FXBX LED Emergency Exit Box - fig 7

If downlight is not required, remove the jumper to disconnect

7: Complete labels NET LED 60598 1 FXBX LED Emergency Exit Box - fig 8

– Enter installation date on battery label
– Enter the appropriate code on the luminaire label

8: Refit legend and side panelNET LED 60598 1 FXBX LED Emergency Exit Box - fig 9

9: Restore mains supplyNET LED 60598 1 FXBX LED Emergency Exit Box - fig 10

NET LED Limited | 300 Anderson Road | Buckingway Business Park | Cambridge | CB24 4UQ Tel: 01223 851505 Email: sales@netled.co.uk 
Our T&C‘s are available online

Documents / Resources

NET LED 60598-1 FXBX LED Emergency Exit Box [pdf] Instruction Manual
60598-1, 60598-2-22, 50172, 1838, 62034, ISO 7010, ISO 3864, FXBX LED Emergency Exit Box