NET - logoLED CAMBRIDGE LINEAR 
NET- 51- 11- XX

Safety Information

  • All electrical work must be undertaken by a qualified contractor to ensure compliance with the latest edition BS 7671 and IEE/IET wiring regulations.
  • Before installing a LED Cambridge fitting or doing any maintenance, ensure the power supply is turned off at the circuit breaker or fuse box.
  • This product is designed for permanent connection to fixed wiring; the circuit should be protected with the appropriate MCB of the fuse.

Environment

  • Please Do NOT dispose of electrical items or packaging as unsorted waste, use the recycling facilities provided by your local authorities.

PRODUCT DIMENSIONS

NET LED LIGHTING Led Cambridge Linear Net-51 11 XX

Important Warranty Information

The LED Cambridge fitting has a 3-year warranty, which can be extended free of charge to 5 years by registering online via the website address below The registrant must provide the product part number and date of manufacture, which can be found on the label attached to the luminaire housing.NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 1

NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 2 NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - qr id
http://tinyurl.com/ooyn6wj

NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - fig 1

KEY DATA NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - fig 2
Light Source LED
Power 38W / SOW
Luminous Flux 5000Im / 65001m
Luminous Efficacy >1301m/W
Colour Temperature 3000K / 4000K / 5500K
Colour Rendering >80 CRI
Housing Material SPCC
Diffuser Material PC
IP Rating IP20
Manufacturer Sealite UK

SUPPLY / EARTH CLASS

220- 240 V AC 50/60 Hz
Fig.1 Mains Input termination
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 4

Installation procedure: Carefully read the installation instructions and ensure the mains supply is isolated before installation. Please follow the safety information overleaf before carrying out any installation. Please retain this leaflet for future reference.

NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - fig 6 NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - fig 4
Replaceable control gear by professional Replaceable (LED only)light source by a professional

Step 1: Carefully remove the fitting from the packaging. Using a flat screwdriver, rotate the retention clip Step
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - fig 5Step 2: Select the mounting points most suitable for the surface. Mount the fitting onto the mounting into the open position to release the diffuser. surface.
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - fig 7Step 3: For side cable entry, drill out the 20mm cable gland position, then secure the cable with a Cable Gland. For rear cable entry, select one of the three pre-cut cable access holes. Select the color temperature on the Tri-colour switch.
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - fig 8

Step 4a: Connect the input wires according to the wiring diagram below.
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - fig 9
Step 4b – Dimmable and Dimmable Emergency, please refer to the above QR code for wiring instructions.
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - qr id 1

https://www.tridonic.com/com/en/download/technical/LCA_PRE_LC_EXC_ProductManual_en.pdf

For Dimmable and Dimmable Emergency, please refer to the above QR Code for wiring instructions.
Ensure that the Emergency Test Record is completed.
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 7Example of Emergency Test Report

SELF-TEST EMERGENCY INSPECTION GUIDE

About:
Initial Test
Connect LED load, emergency module, battery, and LED driver, then connect mains supply, this emergency conversion module will automatically start to do an initial test. If the components are not functioning correctly, the LED indicator will flash RED. If everything is correct, then it will go into charge mode.
Functional Test
Functional tests are carried out for 10 seconds automatically every 30 calendar days.
Duration Test
Emergency conversion module will automatically make a full duration test every 180 calendar days to check the capacity of the battery.
Note
If the mains supply is off during the self-test period, the emergency conversion module would terminate the self-test immediately and go into emergency mode.
Timer reset functionality
The timer for function and duration test can be set to a particular time of the day by cycling the un-switched line supply 3 times within 1 minute.

LED STATUS INDICATOR 

Colour LED indication Status Comment
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 8 Green Slow flashing green (3sec on, 1sec off) Charging mode
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 9 Green Permanent green Fully Charged & Operational
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 10 Green Fast flashing green (0.1sec on, 0.1sec off) Function test underway
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 8 Green Slow flashing green (lsec on, 1sec off) Duration test underway
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 11 Red Permanent red Load failure Open circuit / Short cicuit / LED failure
NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 12 Red Slow flashing red (1 sec on, 1 sec off) Battery failure Battery failed the duration test or function test / No battery

RESET INDICATOR

 

NET LED LIGHTING Led Cambridge Linear Net-51 11 XX - icon 13
If faulty status is triggered, the LED indicator will flash RED. To reset the emergency kit, touch the two reset points for 5-10seconds with a piece of wire, or a short-circuit needle.

Part Number: Installation Date:
Luminaire Ref/Location In case of difficulty, contact the Installation Engineers: Tel ..
Full Recharge Time 24 Hours Duration 3 Hours Lamp Type – LED
ROUTINE INSPECTION TEST RECORD (ENSURE SELF-TEST LED INDICATOR IS DISPLAYING PERMANENT GREEN STATUS)
  Year 1 Year 2 Year 3  Year 4 Year 5
Monthly Check  Signed Date Signed Date Signed Date Signed Date Signed Date
Inspection
Inspection
Inspection
Inspection
Inspection
Inspection
Inspection
Inspection
Inspection
Inspection
Inspection
Inspection

NET - logoNET LED Ltd.
Buckingway Business Park
300 Anderson Road
Cambridge, CB24 4UQ
sales4netled.co.uk
www.netled.co.uk
Technical Helpline: 01223 851505
Email:support@netled.co.uk
www.netled.co.uk/downloads