neptronic-logo

neptronic EVCB14N Series Modbus Communication Module

neptronic-EVCB14N-Series-Modbus-Communication-Module-product

Introduction

The EVCB14N Series Modbus Communication Module User Guide provides information for using the Neptronic® communication feature. The controller uses Modbus communication protocol over serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic EVCB14N Series devices. The EVCB14N Series Modbus Guide assumes that you are familiar with Modbus terminology.
The following are the requirements for Modbus:

  • Data Model. The EVCB Modbus server data model uses only the Holding Registers table.
  • Function Codes. The EVCB Modbus server supports a limited function codes subset comprising:
    • Read Holding Registers (0x03)
    • Write Single Register (0x06)
    • Write Multiple Registers (0x10)
  • Exception Responses. The EVCB Modbus server supports the following exception codes:
    • Illegal data address
    • Illegal data value
    • Slave device busy
  • Serial Line. The EVCB Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
    • The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
    • The supported baud rates are 9600, 19200, 38400, and 57600.
    • The physical layer also supports variable parity control and stop bit configuration as per the Modbus Comport Config device menu item or holding register index 2.
    • In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.
  • Addressing. The EVCB device only answers at the following address:
    • The device’s unique address (1 to 246) that can be set through the device menu or through holding register index 0.

Holding Registers Table

Table Glossary

Name Description Name Description
W Writable Register ASCII For registers containing ASCII (8-bit) characters
RO Read Only Register MSB Most Significant Byte
Unsigned For range of values from 0 to 65,535, unless otherwise specified LSB Least Significant Byte
Signed For range of values from -32,768 to 32,767, unless otherwise specified MSW Most Significant Word
Bit String For registers with multiple values using bit mask (example, flags) LSW Least Significant Word

Holding Register Table

Register Index  

Description

 

Data Type

 

Range

 

Writable

 

40000

 

Modbus Address and Product Type.

 

Unsigned

MSB = Product type (e.g. 111 for EVCB) LSB = Modbus Address (e.g. 1-246)  

W

 

40001

 

MSTP Baud Rate.

 

Unsigned

Scale 100

0, 9600, 19200, 38400, or 57600

0 = Auto Baud Rate Detection

Value/100 (e.g. 38400 baud = 384)

 

W

 

40002

 

Modbus Slave Communication Port Configuration.

 

Unsigned

1= No parity, 2 Stop bits

2= Even parity, 1 stop bit

3= Odd parity, 1 stop bit

 

W

 

40003

 

Product Name (characters 8 & 7).

ASCII  

1 to 65,535

 

char 8: 0x53 = S

 

char 7: 0x00 =

 

W

 

40004

 

Product Name (characters 6 & 5).

 

ASCII

 

1 to 65535

 

char 6: 0x49 = I

 

char 5: 0x34 = 4

 

W

40005 Product Name (characters 4 & 3). ASCII 1 to 65535 char 4: 0x42 = B char 3: 0x4E = N W
40006 Product Name (characters 2 & 1). ASCII 1 to 65535 char 2: 0x45 = E char 1: 0x56 = V W
Register Index  

Description

 

Data Type

 

Range

 

Writable

40007 Product actual firmware version. Unsigned 1 to 65535 (e.g. 410) RO
40008 Product actual EEPROM version. Unsigned 1 to 65535 (e.g. 203) RO
 

 

 

 

40009

 

 

 

 

System Status 1.

 

 

 

 

Bit String

[B0 – B11]: Reserved

B12: CO2 alarm

0 = Normal; 1 = Alarm

B13: Pressure mode (actual status)

0 = Independent; 1 = Dependent

B14: Air Flow

0 = Normal; 1 = Error

 

 

 

 

RO

 

 

40010

 

 

System Status 2.

 

 

Bit String

[B0-B11, B13-B14]: Reserved

 

B12: Alarm override

0 = Normal; 1 = Alarm

 

 

RO

 

40011

 

Internal Temperature.

Unsigned

Scale 100

0 to 5000

Value x 100 (e.g. 23°C = 2300)

 

RO

 

40012

 

External Temperature.

Signed

Scale 100

-4000 to 10000

Value x 100 (e.g. 18°C = 1800)

 

RO

 

40013

 

Change Over Temperature.

Signed

Scale 100

-4000 to 10000

Value x 100 (e.g. 18°C = 1800)

 

RO

 

 

40014

 

Internal Humidity

Internal humidity, reading of the integrated humidity sensor of TRLH or TRLGH/TDU (models with humidity sensor). If not available, the value will be fixed to 0x7FFF (32767)

 

 

Unsigned

Scale 10

 

 

0 to 1000

Value x 10 (e.g. 45%RH = 450)

 

 

RO

40015 Input 3 reading, pressure sensor value (*Not available on all models) Unsigned

Scale 10

0 to 2500

Value x 10 (e.g. 10 Pa = 100)

RO
 

40016

 

Analog input 1 value.

Unsigned

Scale 100

0 to 1000

Value x 100 (e.g. 2 mV = 200)

 

RO

Register Index  

Description

 

Data Type

 

Range

 

Writable

 

40017

 

Analog Input 2 value.

Unsigned

Scale 100

0 to 1000

Value x 100 (e.g. 3 mV = 300)

 

RO

 

40018

CO2 value in ppm

If using TRLG or TRLG/TDU (models with CO2 sensor) and CO2 is in TRL mode, it is the sensor value in ppm. If using AI1 or AI2 and CO2 is set in Analog more, the reading is from the external sensor.

 

Unsigned

Scale 100

100 to reg 40098

Value x 100 (e.g. 5 ppm = 500)

 

RO

 

40019

 

Air supply temperature.

Signed

Scale 100

-4000 to 10000

Value x 100 (e.g. 5°C = 500)

 

RO

 

40020

 

Control temperature.

Signed

Scale 100

-4000 to 10000

Value x 100 (e.g. 25°C = 2500)

 

W

 

40021

 

Heating demand for heating ramp 1.

Unsigned

Scale 10

0 to 1000

Value x 10 (e.g. 25% = 250)

 

RO

 

40022

 

Cooling demand for cooling ramp 1.

Unsigned

Scale 10

0 to 1000

Value x 10 (e.g. 25% = 250)

 

RO

 

40023

 

Temperature offset applied on internal temperature.

Signed

Scale 100

-500 to 500

Value x 100 (e.g. 0.5°C = 50)

 

W

 

40024

 

Temperature offset applied on external temperature.

Signed

Scale 100

-500 to 500

Value x 100 (e.g. 0.5°C = 50)

 

W

 

40025

 

Temperature setpoint used during the occupancy period of the day.

Unsigned

Scale 10

Range: 40026 to 40027

Value x 10 (e.g. 20°C = 200)

 

W

 

40026

 

Minimum temperature setpoint used during the day.

Unsigned

Scale 10

Range: 100 to 40027

Value x 10 (e.g. 10°C = 100)

 

W

 

40027

 

Maximum temperature setpoint used during the day.

Unsigned

Scale 10

Range: 40026 to 400

Value x 10 (e.g. 40°C = 400)

 

W

 

40028

 

Cooling setpoint during No Occupancy / Night Set Back

Unsigned

Scale 10

Range: 40029 to 400

Value x 10 (e.g. 22°C = 220)

 

W

 

40029

 

Heating setpoint during No Occupancy / Night Set Back

Unsigned

Scale 10

Range: 100 to 40028

Value x 10 (e.g. 16°C = 160)

 

W

Register Index  

Description

 

Data Type

 

Range

 

Writable

 

40030

 

Cooling demand for proportional band 1.

Unsigned

Scale 10

5 to 50

Value x 10 (e.g. 0.3°C = 3)

 

W

 

40031

 

Heating demand for proportional band 1.

Unsigned

Scale 10

5 to 50

Value x 10 (e.g. 0.3°C = 3)

 

W

 

40032

 

Cooling dead band for proportional band 1.

Unsigned

Scale 10

0 to 50

Value x 10 (e.g. 0.3°C = 3)

 

W

 

40033

 

Heating dead band for proportional band 1.

Unsigned

Scale 10

0 to 50

Value x 10 (e.g. 0.3°C = 3)

 

W

 

40034

 

Changeover temperature setpoint.

Unsigned

Scale 10

100 to 400

Value x 10 (e.g. 12°C = 120)

 

W

40035 Night setback override delay in minutes. Unsigned 0 to 180 minutes W
40036 Integral time factor for heating in seconds. Unsigned 0 to 250 seconds W
40037 Cooling anti-cycle delay: delay in minutes before activating or reactivating the cooling contact. Unsigned 0 to 15 minutes W
40038 Floating time 1: Indicates the time in seconds required by the actuator to complete a 90° run. Unsigned 15 to 250 seconds W
40039 Occupancy Delay Mode in minutes Unsigned 0 to 180 minutes W
 

40040

 

Cooling demand for cooling ramp 2.

Unsigned

Scale 10

0 to 1000 %

Value x 10 (e.g. 30% = 300)

 

RO

 

40041

 

Proportional band for cooling ramp 2

Unsigned

Scale 10

5 to 50

Value x 10 (e.g. 0.2°C = 2)

 

W

 

40042

 

Dead band for cooling ramp 2.

Unsigned

Scale 10

0 to 50

Value x 10 (e.g. 0.2°C = 2)

 

W

 

40043

 

Heating demand for heating ramp 2.

Unsigned

Scale 10

0 to 1000 %

Value x 10 (e.g. 30% = 300)

 

W

 

40044

 

Proportional band for heating ramp 2.

Unsigned

Scale 10

5 to 50

Value x 10 (e.g. 0.2°C = 2)

 

W

Register Index  

Description

 

Data Type

 

Range

 

Writable

 

40045

 

Dead band for heating ramp 2.

Unsigned

Scale 10

0 to 50

Value x 10 (e.g. 0.2°C = 2)

 

W

 

40046

 

Changeover demand for the VAV box.

Unsigned

Scale 10

0 to 1000 %

Value x 10 (e.g. 30% = 300)

 

RO

 

40047

Changeover proportional band: the range in which the controller modulates the cooling and heating output from 0 to 100%. Unsigned

Scale 10

5 to 50

Value x 10 (e.g. 0.2°C = 2)

 

W

 

40048

Changeover deadband: the range at which the controller takes no action when the temperature is above or below the setpoint. Unsigned

Scale 10

0 to 50

Value x 10 (e.g. 0.2°C = 2)

 

W

 

40049

 

AO1 min Vdc: minimum voltage of analog output 1.

Unsigned

Scale 10

Range: 0 to reg. 40051

Value x 10 (e.g. 2 Volts = 20)

 

W

 

40050

 

AO2 min Vdc: minimum voltage of analog output 2.

Unsigned

Scale 10

Range: 0 to reg. 40052

Value x 10 (e.g. 2 Volts = 20)

 

W

 

40051

 

AO1 max Vdc: maximum voltage of analog output 1.

Unsigned

Scale 10

Range: reg. 40049 to 100

Value x 10 (e.g. 10 Volts = 100)

 

W

 

40052

 

AO2 max Vdc: maximum voltage of analog output 2.

Unsigned

Scale 10

Range: reg. 40050 to 100

Value x 10 (e.g. 10 Volts = 100)

 

W

* = The minimum and maximum voltages correspond to 0 to 100% demand. The minimum voltage is always applied to the output. The maximum voltage is applied when the demand reaches 100%. For reheat applications, we recommend to leave the minimum voltage at 0Vdc to avoid heating when the demand is 0%.
40053 Time of numerical filter of delta pressure in seconds. Not effective on all models. Unsigned 1 to 10 seconds W
40054 Factor of V=K*sqrt(dP), where dP = 1. Not effective on all models. Unsigned Range: 100 to 9995 CFM W
40055 Minimum air flow for cooling. Not effective on all models. Unsigned Range: 0 or (12.7%) Kfac to reg 40056 CFM W
40056 Maximum air flow for cooling. Not effective on all models. Unsigned Range: reg 40055 to reg 40054 CFM W
 

40057

 

Minimum air flow for heating. Not effective on all models.

 

Unsigned

 

Range: 0 or (12.7%) Kfac to reg 40058 CFM

 

W

Register Index  

Description

 

Data Type

 

Range

 

Writable

40058 Maximum air flow for heating. Not effective on all models. Unsigned Range: reg 40057 to reg 40054 CFM W
40059 Integral time factor of air flow in minutes. Not effective on all models. Unsigned 0 to 60 minutes W
40060 Actual air flow converted from delta pressure sensor. Not effective on all models. Unsigned Range: 0 to reg 40054 CFM RO
40061 Air flow calculated from system demand. Not effective on all models. Unsigned Range: 0 to 9999 CFM RO
 

40062

Configuration value for Air Flow Max used during airflow balancing sequence. Refer to EVCB-Airflow Balance Instructions.

Not effective on all models.

 

Unsigned

 

Range: 0 to 9999 CFM

 

W

 

40063

 

Analog output 1 value.

Unsigned

Scale 10

Unit: Volt, Range: reg 40049 to reg 40051

Value x 10 (e.g. 5 Volts = 50)

 

W

 

40064

 

Analog output 2 value.

Unsigned

Scale 10

Unit: Volt, Range: reg 40050 to reg 40052

Value x 10 (e.g. 5 Volts = 50)

 

W

40065 Percentage of demand to close TRIAC output 1. Not available on all models. Unsigned 15 to 80% W
40066 Percentage of demand to close TRIAC output 2. Not available on all models. Unsigned 15 to 80% W
40067 Percentage of demand to close TRIAC output 3. Not available on all models. Unsigned 15 to 80% W
40068 Percentage of demand to close TRIAC output 4. Not available on all models. Unsigned 15 to 80% W
40069 Percentage of demand to open TRIAC output 1. Not available on all models. Unsigned 0 to reg 40065-4% W
40070 Percentage of demand to open TRIAC output 2. Not available on all models. Unsigned 0 to reg 40065-4% W
 

40071

 

Percentage of demand to open TRIAC output 3. Not available on all models.

 

Unsigned

 

0 to reg 40065-4%

 

W

Register Index  

Description

 

Data Type

 

Range

 

Writable

40072 Percentage of demand to open TRIAC output 4. Not available on all models. Unsigned 0 to reg 40065-4% W
40073 Integral time factor for cooling in seconds. Unsigned 0 to 250 seconds W
40074 Motor position. Not effective on all models. Unsigned 0 to 100% RO
40075 to 40080 – Reserved RO
40081 Air flow offset calibration. Refer to EVCB-Airflow Balance Instructions.Not effective on all models. Signed -500 to 500 CFM W
 

40084

Configuration value for Air Flow Min used during airflow balancing sequence. Refer to EVCB-Airflow Balance Instructions.

Not effective on all models.

 

Unsigned

 

Range: 0 to 9999 CFM

 

W

40082, 40083, and 40085 to 40095 – Reserved RO
40096 Network fallback timeout Present Value in minutes. Unsigned 0 to 60 minutes W
40097 Reserved     RO
40098 Maximum range of the CO2 sensor connected to AI1 or AI2. Unsigned 100 to 5000 PPM W
40099 Maximum concentration of CO2 before the EVC activates an alarm. Unsigned Range: 100 to the greater ppm value between 2000 and reg 40098 W
Register Index  

Description

 

Data Type

 

Range

 

Writable

      B3, B13-B14: Reserved B7: Freeze protection

0 = Disabled; 1 = Enabled

 
      B0: Tstat temperature units

0 = Celsius; 1 = Fahrenheit

 

B1: Modbus temperature units

0 = Celsius; 1 = Fahrenheit

 

B8: User system off mode

0 = User can set Tstat to OFF 1 = User cannot set Tstat OFF

 
 

 

40100

 

 

System Option 1.

F Not effective on all models.

 

 

Bit String

 

B2: Temperature setpoint lock

0 = Unlocked; 1 = Locked

 

B4: TO1/TO2 floating directionF

0 = Direct; 1 = Reverse

B9: Keypad bottom left lock

0 = Unlocked; 1 = Locked

 

B10:Keypad upper left lock

0 = Unlocked; 1 = Locked

 

B11: Keypad arrows lock

0 = Unlocked; 1 = Locked

 

 

W

      B5: TO3/TO4 floating directionF

0 = Direct; 1 = Reverse

 

B12: Program lock

0 = Unlocked; 1 = Locked

 
      B6: Onboard motor directionF

0 = Direct; 1 = Reverse

B15: Schedule

0 = Disabled; 1 = Enabled

 
Register Index  

Description

 

Data Type

 

Range

 

Writable

      B0-B1, B13: Reserved B8: TO3 directionF

0 = Direct; 1 = Reverse

 
      B2: Auto baud rate detection

0 = Enabled; 1 = Disabled

 

B9: TO4 directionF

0 = Direct; 1 = Reverse

 
 

 

 

 

 

40101

 

System Option 2. Notes

B14: Applies only if DI2 is in OverHeat or Override.

B15: Configuration value of the fan operation when an output ramp is configured with the option “Fan On”. When set to (0) On, the fan is continuously in operation even when EVC is off. When set to (1) Off, the fan turns off during the following conditions; User System Mode is set to OFF, when in night setback mode, scheduler forces the EVC OFF or when Digital Input 2 is set to Override and is active.

F Not effective on all models.

 

 

 

 

 

Bit String

B3: Night setback mode

0 = Tstat ON; 1 = Tstat OFF

 

B4: AO1 direction

0 = Direct; 1 = Reverse

 

B5: AO2 direction

0 = Direct; 1 = Reverse

 

B6: TO1 directionF

0 = Direct; 1 = Reverse

 

B7: TO2 directionF

0 = Direct; 1 = Reverse

 

B10: Display RHF

0 = No; 1 = Yes

 

B11: Pressure mode selectF

0 = independent;1 = dependent

 

B12: Auto pressure modechange

0 = Enabled; 1 = Disabled

 

B14: DI 2 Contact

0: NO; 1: NC

 

 

 

 

 

W

        B15: Fan always “on” mode

0 = Always on;

1 = Follow NSB/NoOcc

 
40102 Status value of the actual changeover control mode. Unsigned 0 = Cooling, 1= Heating RO
 

40103

System command status.

F Not effective on all models.

 

Unsigned

 

0 = No Command, 1 = AirFlow 1 Balancing, 4 = AirFlow 2 Balancing

 

W

 

40104

TO OnOff.

*  Not available on all models.

 

Unsigned

1 = TO1 OnOff 2 = TO2 OnOff 4 = TO3 OnOff 8 = TO4 OnOff  

RO

 

40105

 

Occupancy or night setback mode commands.

 

Unsigned

1 = Locally

2 = Off

3 = Occupancy

4 = NoOccupancy

5 = Day

6 = Night

 

W

40106 Status of digital input 1. Unsigned 0 = Open, 1 = Close RO
Register Index  

Description

 

Data Type

 

Range

 

Writable

 

 

 

 

40107

 

 

Analog input 1 signal.

*  Not available on all models.

F Not effective on all models.

** Only available with EVCB14NIT0S.

 

 

 

 

Unsigned

1 = OFF

2 = ETS (external temp)

3 = SENS (changeover sensor)

4 = NoCL (normally cool)

5 = NoHT (normally heat)

6 = STFL* (setpnt airflow 0-10Vdc)

7 = CO2 (carbon dioxide)

8 = AST (air supply temp sensor)

9 = morF (motor position)

10 = EXT50K** (external 50KΩ sensor)

11 = TSTAT temp sensor**

(thermostat temperature sensor)

12 = TSTAT Setpoint** (thermostat setpoint 0-10Vdc)

13 = TSTAT Setpoint 2-10V**

(thermostat setpoint 2-10Vdc)

 

 

 

 

W

40108 User System Control Mode. Unsigned 1 = AUTO

2 = HEAT

3 = COOL

4 = OFF

W
 

40109

Sets the permissions or restrictions to change the system control mode by the user.  

Unsigned

1 = AUTO

2 = HEAT

3 = COOL

4 = COOL-HEAT

5 = AUTO-LOCK

 

W

40110 Indicates the status of the Night Setback mode. Unsigned 1 = Day, 2 = Night, 3 = Derogation RO
 

40111

Configuration of DI1 mode. Night setback or no occupancy status.

*  Only available with EVCB14NIT0S.

 

Unsigned

1=Off

2= Occupancy NO

3= Occupancy NC

4= Night Set Back NO 5= Night Set Back NC

6= Unoccupancy damper*

 

W

 

 

 

 

40112

 

 

Analog input 2 signal.

*  Not available on all models.

** Only available with EVCB14NIT0S.

 

 

 

 

Unsigned

1 = OFF

2 = ETS (external temp)

3 = SENS (changeover sensor)

4 = NoCL (normally cool)

5 = NoHT (normally heat)

6 = STFL* (setpnt airflow 0-10Vdc)

7 = CO2 (carbon dioxide)

8 = AST (air supply temp sensor)

9 = mor (motor position)

10 = EXT50K** (external 50KΩ sensor)

11 = TSTAT temp sensor**

(thermostat temperature sensor)

12 = TSTAT Setpoint** (thermostat setpoint 0-10Vdc)

13 = TSTAT Setpoint 2-10V**

(thermostat setpoint 2-10Vdc)

 

 

 

 

W

40113 Occupancy status of the zone. Unsigned 1 = No Occupancy, 2 = Occupancy, 3 = Derogation RO
 

 

40114

AO1: Analog output 1 control ramp

Notes: Options 11 and 12 are for fan powered applications and only available with models: EVCB14NIT4S, EVCB14NDT4S, and EVCB14NIT4SF.

*  Not available on all models.

 

 

Unsigned

1 = OFF

2 = CR1 (cooling ramp 1)

3 = CR2 (cooling ramp 2)

4 = HR1 (heating ramp 1)

5 = HR2 (heating ramp 2)

6 = ArFL (airflow reading)

7 = CO2 (carbon dioxide)

8 = STFL* (setpnt airflow 0-10Vdc)

9 – 10 = reserved

11 = Fan Auto (follow demand)

12 = Fan On (always on)

 

 

W

Register Index  

Description

 

Data Type

 

Range

 

Writable

 

 

40115

 

AO2: Analog output 2 control ramp

Notes: Options 11 and 12 are for fan powered applications and only available with models: EVCB14NIT4S, EVCB14NDT4S, and EVCB14NIT4SF.

*  Not available on all models.

 

 

Unsigned

1 = OFF

2 = CR1 (cooling ramp 1)

3 = CR2 (cooling ramp 2)

4 = HR1 (heating ramp 1)

5 = HR2 (heating ramp 2)

6 = ArFL (airflow reading)

7 = CO2 (carbon dioxide)

8 = STFL* (setpnt airflow 0-10Vdc)

9 – 10 = reserved

11 = Fan Auto (follow demand)

12 = Fan On (always on)

 

 

W

 

 

40116

 

TO1: Configuration of the ramp used to modulate (pulse or floating) or activate/deactivate (On/Off) TO1 based on demand.

*  Not available on all models.

 

 

Unsigned

1 = OFF

2 = CR1 (cooling ramp 1)

3 = CR2 (cooling ramp 2)

4 = HR1 (heating ramp 1)

5 = HR2 (heating ramp 2)

6 = CO2 (carbon dioxide)

7 = STFL* (setpnt airflow 0-10Vdc)

8 = COR* (changeover ramp)

9 = CH1* (cool/heat 1)

10 = ANLG* (analog 0-10Vdc) 11 = Fan Auto (follow demand) 12 = Fan On (always on)

 

 

W

 

 

40117

 

TO2: Configuration of the ramp used to modulate (pulse or floating) or activate/deactivate (On/Off) TO2 based on demand.

*  Not available on all models.

 

 

Unsigned

1 = OFF

2 = CR1 (cooling ramp 1)

3 = CR2 (cooling ramp 2)

4 = HR1 (heating ramp 1)

5 = HR2 (heating ramp 2)

6 = CO2 (carbon dioxide)

7 = STFL* (setpnt airflow 0-10Vdc)

8 = COR* (changeover ramp)

9 = CH1* (cool/heat 1)

10 = ANLG* (analog 0-10Vdc) 11 = Fan Auto (follow demand) 12 = Fan On (always on)

 

 

W

 

 

40118

 

TO3: Configuration of the ramp used to modulate (pulse or floating) or activate/deactivate (On/Off) TO3 based on demand.

*  Not available on all models.

 

 

Unsigned

1 = OFF

2 = CR1 (cooling ramp 1)

3 = CR2 (cooling ramp 2)

4 = HR1 (heating ramp 1)

5 = HR2 (heating ramp 2)

6 = CO2 (carbon dioxide)

7 = STFL* (setpnt airflow 0-10Vdc)

8 = COR* (changeover ramp)

9 = CH1* (cool/heat 1)

10 = ANLG* (analog 0-10Vdc) 11 = Fan Auto (follow demand) 12 = Fan On (always on)

 

 

W

 

 

40119

 

TO4: Configuration of the ramp used to modulate (pulse or floating) or activate/deactivate (On/Off) TO4 based on demand.

*  Not available on all models.

 

 

Unsigned

1 = OFF

2 = CR1 (cooling ramp 1)

3 = CR2 (cooling ramp 2)

4 = HR1 (heating ramp 1)

5 = HR2 (heating ramp 2)

6 = CO2 (carbon dioxide)

7 = STFL* (setpnt airflow 0-10Vdc)

8 = COR* (changeover ramp)

9 = CH1* (cool/heat 1)

10 = ANLG* (analog 0-10Vdc) 11 = Fan Auto (follow demand) 12 = Fan On (always on)

 

 

W

 

40120

TO1: Signal output type for TRIAC output 1.

*  Not available on all models.

 

Unsigned

 

3 = Pulsing, 4 = On_Off, 5 = Floating

 

W

 

40121

TO2: Signal output type for TRIAC output 2.

*  Not available on all models.

 

Unsigned

 

3 = Pulsing, 4 = On_Off

 

W

 

40122

TO3: Signal output type for TRIAC output 3.

*  Not available on all models.

 

Unsigned

 

3 = Pulsing, 4 = On_Off, 5 = Floating

 

W

Register Index  

Description

 

Data Type

 

Range

 

Writable

 

40123

TO4: Signal output type for TRIAC output 4.

*  Not available on all models.

 

Unsigned

 

3 = Pulsing 4 = On_Off

 

W

 

40124

Pressure independent output selection for VAV damper actuator.

*  Not available on all models.

 

Unsigned

 

3 = Floating1, 4 = Floating2, 5 = Motor

 

W

 

 

40125

 

Motor ramp: Configuration of the ramp used to modulate the actuator based on demand.

*  Not available on all models.

 

 

Unsigned

2 = CR1 (cooling ramp 1)

3 = CR2 (cooling ramp 2)

4 = HR1 (heating ramp 1)

5 = HR2 (heating ramp 2)

6 = Not Available

7 = STFL* (setpnt airflow 0-10Vdc)

8 = COR (changeover ramp)

9 = CH1 (cool/heat 1)

10 = ANLG (analog 0-10Vdc)

 

 

W

40126 Changeover control mode status that indicates the source of changeover values. Unsigned 1 = Local, 2 = Cooling, 3 = Heating W
40127 Reserved     RO
40128 Reserved     RO
 

40129

Configuration of DI2 mode.

*  Only available with EVCB14NIT0S.

 

Unsigned

1=Off 2=Override 3=OverHeat1 4=OverHeat2 5=OverHeatAll 6=ChangeOverNoCooling 7=ChangeOverNoHeating 8=Unoccupancy damper*  

W

 

40130

 

Selected temperature control source (in Programming mode).

 

Unsigned

1 = Internal Temperature 2 = External Temperature 3 = Remote Temperature 4 = Average Temperature 5 = Maximum Temperature  

W

 

40131

Airflow balance mode enter the balancing mode to adjust air flow factor. FNot effective on all models.  

Unsigned

1 = Close

2 = Minimum Flow

3 = Maximum Flow 4 = Full Open  

W

40132 Reserved     RO
 

40133

Configuration to set the motor position in night setback mode.

F Not effective on all models.

 

Unsigned

1 = Auto

2 = Open

 

W

40134 Digital input 2 delay in seconds. Unsigned 0 to 3600 seconds W
 

40135

Time in seconds required by the actuator to complete a 90° run.

*  Not available on all models.

 

Unsigned

 

15 to 250 seconds

 

W

 

40136

Minimum motor position in percentage of stroke for cooling.

*  Not available on all models.

 

Unsigned

 

0 to 100%

 

W

Register Index  

Description

 

Data Type

 

Range

 

Writable

 

40137

Minimum motor position in percentage of stroke for heating.

*  Not available on all models.

 

Unsigned

 

0 to 100%

 

W

40138 Airflow Hysteresis Stop in percentage.* Not available on all models. Unsigned 1 to 100% W
40139 Airflow Hysteresis Start in percentage.* Not available on all models. Unsigned reg 40138 to 100% W
40140 Airflow scale.*Not available on all models. Unsigned 1 = Scale1, 2 = Scale10, 3 = Scale100 W
40141 Airflow fault deadband in percentage.* Not available on all models. Unsigned 1 to 30% W
40142 Airflow fault error in percentage.* Not available on all models. Unsigned 0 to 100% W
40143 Airflow fault hysteresis in percentage.* Not available on all models. Unsigned 1 to 30% W
40144 Airflow fault time.*Not available on all models. Unsigned 2 to 59 minutes W
40145 CL_HT SwitchTimer, waiting time before switching between the heating and cooling modes. Unsigned 0 to 120 minutes W
40146 CL_HT SwitchTimerCount, countdown to indicate the swap between heating and cooling modes. Unsigned 0 to 4,294,967,295 seconds RO
 

40147

FloatingTO1/TO2, TRIAC output 1 or 2 when set to floating, indicates the floating signal demand.

*  Not available on all models.

 

Unsigned

Scale 10

0 to 1000%

Value x 10 (e.g. 15% =150)

 

RO

 

40148

FloatingTO3/TO4, TRIAC output 3 or 4 when set to floating, indicates the floating signal demand.

*  Not available on all models.

 

Unsigned

Scale 10

0 to 1000%

Value x 10 (e.g. 15% =150)

 

RO

 

40149

TO1 Pulsing, TRIAC output 1 when set to Pulsed, indicates the pulse signal demand. * Not available on all models. Unsigned

Scale 10

0 to 1000%

Value x 10 (e.g. 15% =150)

 

RO

 

40150

TO2 Pulsing, TRIAC output 2 when set to Pulsed, indicates the pulse signal demand. * Not available on all models. Unsigned

Scale 10

0 to 1000%

Value x 10 (e.g. 15% =150)

 

RO

 

40151

TO3 Pulsing, TRIAC output 3 when set to Pulsed, indicates the pulse signal demand.* Not available on all models. Unsigned

Scale 10

0 to 1000%

Value x 10 (e.g. 15% =150)

 

RO

 

40152

TO4 Pulsing, TRIAC output 4 when set to Pulsed, indicates the pulse signal demand.* Not available on all models. Unsigned

Scale 10

0 to 1000%

Value x 10 (e.g. 15% =150)

 

RO

Register Index  

Description

 

Data Type

 

Range

 

Writable

 

40153

 

Over heat status.

 

Unsigned

1 = OverHeatNormal

2 = OverHeat1

3 = OverHeat2

4 = OverHeatAll

 

RO

 

 

40154

 

Configuration to override the motor position.

*  Not available on all models.

 

 

Unsigned

 

1 = Auto

2 = Open

3 = Close

 

4 = AirFlowCoolMin

5 = AirFlowCoolMax

 

 

W

 

40155

 

Information displayed on the TRL/TDU.

 

Unsigned

1 = Temp Demand

2 = Setpoint Demand 3 = Temp

 

4 = Setpoint

5 = Off

 

W

40156 Status of digital input 2. Unsigned 0 = Open, 1 = Close RO
40157 Reserved     RO
        B7: Occupancy Control Source  
      [B0-B1, B4-B6, B8, B11-B15]:

Reserved

0 = BI1; 1 = Intern Sensor  
 

40158

 

System Options 3

 

Bit String

B2: CO2 Display

0 = No; 1 = Yes

B9: Motor Position Control Temperature Fault

0 = Close; 1 = Open

 

W

      B3: CO2 Control Source B10: CO2 Control Mode  
      0 = Analog; 1 = TRLG 0 = Open; 1 = Control ramp  
 

40159

 

System Options 4

 

Bit String

  [B0 – B15]: Reserved  

RO

 

40160

Internal CO2, reading of the integrated CO2 sensor of TRLG or TRLGH/TDU (models with humidity sensor). If not available, the value will be fixed to 0x7FFF (32767)  

Unsigned

 

0 to 2000 ppm

 

RO

40161 Internal light sensor reading in Luxes. Unsigned 0 to 16000 Luxes RO
 

40162

 

Internal VOC sensor reading in ppb.

 

Unsigned

 

1 to 60000 ppb

 

RO

Register Index  

Description

 

Data Type

 

Range

 

Writable

 

40163

 

Internal PIR sensor reading.

 

Unsigned

 

0 = NoOccupancy, 1 = Occupancy

 

RO

40164 Occupancy minimum time in minutes. Unsigned 0 to 240 minutes W
40165 Configuration value of the minimum position in cooling/heating mode in %. Unsigned 0 to 100 % W
40166 Control SetPoint. Unsigned

Scale 1

10 to 40

Value x 1 (e.g. 30°C = 30)

RO
40167 CO2 ramp proportional band Unsigned

Scale 1

50 to 250 ppm

Value x 1 (e.g. 50ppm = 50)

W
 

40168

 

CO2 ramp dead band

Unsigned

Scale 1

10 to 50 ppm

Value x 1 (e.g. 50ppm = 50)

 

W

 

40169

 

Temperature sensor combination

 

Unsigned

1 = TSTAT+AI1

2 = TSTAT+AI2

3 = TSTAT+AI1+AI2

4 = AI1+AI2

 

W

 

40170

 

Average temperature

Signed

Scale 100

-4000 to 10000

Value x 100 (e.g. 5°C = 500)

 

RO

 

40171

 

Maximum temperature

Signed

Scale 100

-4000 to 10000

Value x 100 (e.g. 5°C = 500)

 

RO

 

40172

 

External sensor value of analog input 2

Signed

Scale 100

-4000 to 10000

Value x 100 (e.g. 5°C = 500)

 

RO

400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
neptronic.com
Toll-free in North America: 1-800-361-2308
Tel.: 514-333-1433
Fax: 514-333-3163
Customer service fax: 514-333-1091
Monday to Friday: 8:00am to 5:00pm (Eastern time)

Documents / Resources

neptronic EVCB14N Series Modbus Communication Module [pdf] User Guide
EVCB14N Series Modbus Communication Module, EVCB14N Series, Modbus Communication Module, Communication Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *