Introduction

The Compact Make-up Air Unit Modbus Communication Module User Guide provides information for using the Neptronic communication feature. The controller uses Modbus communication protocol over a serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic Compact Make-up Air Unit devices. The Compact Make-up Air Unit Modbus Guide assumes that you are familiar with Modbus terminology. The following are the requirements for Modbus:

  •  Data Model. The Compact Make-up Air Unit Modbus server data model uses only the Holding Registers table.
  •  Register Address:
    •  As per the protocol base (base 0); for PLC add 1 to the protocol base.
    •  As per the holding register (base 40001).
  •  Function Codes. The Compact Make-up Air Unit Modbus server supports a limited function codes subset comprising:
    •  Read Holding Registers (0x03)
    •  Write Single Register (0x06)
    •  Write Multiple Registers (0x10)
  •  Exception Responses. The Compact Make-up Air Unit Modbus server supports the following exception codes:
    •  Illegal data address
    •  Illegal data value
    •  Slave device busy
  •  Serial Line. The Compact Make-up Air Unit Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
    •  The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
    •  The supported baud rates are 9600, 19200, 38400, 57600, and 76800 bps.
    •  The physical layer also supports variable parity control and stop-bit configuration as per the Modbus Comport Config device menu item or holding register index 2.
    •  In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.
    •  If the device does not detect any activity for one second or more, it will find a silent line to prevent a possible baud rate scan on the next frame it detects.
  •  Addressing. The Compact Make-up Air Unit device only answers at the following address:
    •  The device’s unique address (1 to 247) can be set through the device menu or by holding the register index

Holding Registers Table

Glossary

Name Description Name Description
W Writable Register ASCII For registers containing ASCII (8-bit) characters
RO Read Only Register MSB Most Significant Byte
Unsigned For range of values from 0 to 65,535, unless otherwise specified LSB Least Significant Byte
Signed For range of values from -32,768 to 32,767, unless otherwise specified MSW Most Significant Word
Bit String For registers with multiple values using bit mask (example, flags) LSW Least Significant Word

Holding Register Table

Protocol Base Holding Register  

Description

 

Data Type

 

Range

 

Writable

0 40001 Modbus product type and address. Unsigned MB = Modbus Address (e.g. 110), LB = 1-247 W
1 40002 Analog input 1 voltage. Unsigned

Scale 1000

Unit: Volts (V), Range: 0V to 10V

Value x 1000 (e.g. 2V = 2000)

RO
2 40003 Analog input 2 voltage. Unsigned

Scale 1000

Unit: Volts (V), Range: 0V to 10V

Value x 1000 (e.g. 2V = 2000)

RO
3 40004 Analog input 3 temperature. Signed

Scale 100

Units: °C/°F, Range: -40°C to 85°C or -40°F to 185°F

Value x 100 (e.g. 25°C = 2500 or 25°F = 2500)

RO
4 40005 Analog input 4 temperature. Signed

Scale 100

Units: °C/°F, Range: -40°C to 85°C or -40°F to 185°F

Value x 100 (e.g. 25°C = 2500 or 25°F = 2500)

RO
5 40006 Room air temperature value measured by TDF. Unsigned

Scale 100

Units: °C/°F, Range : 0°C to 50°C or 32°F to 122°F

Value x 100 (e.g. 5°C = 500 or 50°F = 5000)

RO
6 40007 Room air relative humidity value measured by TDF. Unsigned

Scale 10

Unit: %RH, Range: 0 to 100%RH

Value x 10 (e.g. 10%RH = 100)

RO
7 40008 Room CO2 concentration value measured by TDF. Unsigned

Scale 1

Unit: PPM, Range: 0 to 2000 PPM

Value x 1 (e.g. 2 PPM = 2)

RO
8 40009 The volatile organic compound index measured by TDF. Unsigned

Scale 1

Unit: No Unit, Range: 0 to 65535,

Value x 1 (e.g. 100 = 100)

RO
Protocol Base Holding Register  

Description

 

Data Type

 

Range

 

Writable

9 40010 Luminous flux measured by TDF. Unsigned

Scale 1

Unit: Lux, Range: 0 to 16000 Lux

Value x 1 (e.g. 2 Lux = 2)

RO
10 40011 CMU on-board potentiometer temperature setpoint. Unsigned

Scale 100

Units: °C/°F, Range: 0°C to 35°C or 32°F to 95°F

Value x 100 (e.g. 2°C = 200 or 50°F = 5000)

RO
11 40012 CMU intake temperature. Signed

Scale 100

Units: °C/°F, Range: -40ºC to 85ºC or -40°F to 185°F

Value x 100 (e.g. 23°C = 2300 or 23°F = 2300)

RO
12 40013 CMU outtake temperature. Signed

Scale 100

Units: °C/°F, Range: -40ºC to 85ºC or -40°F to 185°F

Value x 100 (e.g. 23°C = 2300 or 23°F = 2300)

RO
13 40014 CMU board temperature. Signed

Scale 100

Units: °C/°F, Range: -40ºC to 85ºC or -40°F to 185°F

Value x 100 (e.g. 23°C = 2300 or 23°F = 2300)

RO
14 40015 CMU SSR temperature. Signed

Scale 100

Units: °C/°F, Range: -40ºC to 85ºC or -40°F to 185°F

Value x 100 (e.g. 23°C = 2300 or 23°F = 2300)

RO
15 40016 AI3/BI3 multi-mode input state. Unsigned 0 = Open, 1 = Closed RO
16 40017 AI4/BI4 multi-mode input state. Unsigned 0 = Open, 1 = Closed RO
17 40018 Room movement detection occupancy sensor. Unsigned 0 = No, 1 = Yes RO
18 40019 CMU On/Off contact input state. Unsigned 0 = Off, 1 = On RO
19 40020 Analog output 1 voltage. Unsigned

Scale 100

Unit: Volts, Range: 0V to 10V

Value x 100 (e.g. 3V = 300)

RO
20 40021 Analog output 2 voltage. Unsigned

Scale 100

Unit: Volts, Range: 0V to 10V

Value x 100 (e.g. 3V = 300)

RO
21 40022 Binary output 1 state. Unsigned 0 = Open, 1 = Closed RO
22 40023 Binary output 1 state. Unsigned 0 = Open, 1 = Closed RO
23 40024 Supply air temperature. Unsigned

Scale 100

Units: °C/°F, Range: 0°C to 100°C or 32°F to 212°F

Value x 100 (e.g. 2°C = 200 or 50°F = 5000)

RO
24 40025 Supply air relative humidity. Unsigned

Scale 100

Units: %RH, Range: 0 to 100%RH

Value x 100 (e.g. 23%RH = 2300)

RO
25 40026 Outside air temperature. Signed

Scale 100

Units: °C/°F, Range: -40ºC to 50ºC or -40°F to 122°F

Value x 100 (e.g. 23°C = 2300 or 23°F = 2300)

RO
26 40027 Outside air relative humidity. Unsigned

Scale 100

Units: %RH, Range: 0 to 100%RH

Value x 100 (e.g. 23%RH = 2300)

RO
27 40028 Duct static pressure. Unsigned

Scale 10

Units: Pascal (Pa), Range: 0 to 1250 Pa

Value x 10 (e.g. 50 Pa = 500)

RO
Protocol Base Holding Register  

Description

 

Data Type

 

Range

 

Writable

28 40029 Damper position feedback. Unsigned

Scale 1

Unit: %, Range: 0% to 100%,

Value x 1 (e.g. 100% = 100)

RO
29 40030 Current airflow setpoint in percent of maximum capacity. Unsigned

Scale 1

Unit: %, Range: 0% to 100%,

Value x 1 (e.g. 100% = 100)

RO
30 40031 CMU ECM fan speed feedback value. Unsigned

Scale 1

Unit: RPM, Range: 0 to 10000 RPM,

Value x 1 (e.g. 100 RPM = 100)

RO
31 40032 Heater vernier stage duty cycle. Unsigned

Scale 10

Unit: %, Range: 0 to 100%,

Value x 10 (e.g. 100% = 1000)

RO
32 40033 Network temperature setpoint. Unsigned

Scale 100

Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F,

Value x 1 (e.g. 5°C = 500 or 50°F = 5000)

W
33 40034 TDF temperature setpoint. Unsigned

Scale 100

Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F,

Value x 1 (e.g. 5°C = 500 or 50°F = 5000)

W
34 40035 CMU anti-freeze setpoint. Unsigned

Scale 100

Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F,

Value x 1 (e.g. 5°C = 500 or 50°F = 5000)

W
35 40036 Occupied airflow setpoint in percent of maximum capacity. Unsigned

Scale 1

Unit: %, Range: 0 to 100%,

Value x 1 (e.g. 100% = 100)

W
36 40037 Unoccupied airflow setpoint in percent of maximum capacity. Unsigned

Scale 1

Unit: %, Range: 0 to 100%,

Value x 1 (e.g. 100% = 100)

W
37 40038 Binary input 3 stage weight. Unsigned

Scale 1

Unit: %, Range: 0 to 100%,

Value x 1 (e.g. 100% = 100)

W
38 40039 Binary input 4 stage weight. Unsigned

Scale 1

Unit: %, Range: 0 to 100%,

Value x 1 (e.g. 100% = 100)

W
39 40040 Exhaust fan start delay. Unsigned

Scale 1

Unit: Seconds, Range: 1 to 255 seconds

Value x 1 (e.g. 10 secs = 10)

W
40 40041 Exhaust fan control signal minimum value. Unsigned

Scale 100

Unit: Volts (V), Range: 0 to 10V,

Value x 100 (e.g. 3V = 300)

W
41 40042 Exhaust fan control signal maximum value. Unsigned

Scale 100

Unit: Volts (V), Range: 0 to 10V,

Value x 100 (e.g. 3V = 300)

W
42 40043 Damper stroke time. Unsigned

Scale 1

Unit: Seconds, Range: 1 to 255 seconds,

Value x 1 (e.g. 100 secs = 100)

W
43 40044 Occupancy inputs minimum time. Unsigned

Scale 1

Unit: Minutes, Range: 0 to 240 minutes,

Value x 1 (e.g. 10 mins = 10)

W
Protocol Base Holding Register  

Description

 

Data Type

 

Range

 

Writable

44 40045 Temperature setpoint minimum value. Unsigned

Scale 100

Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F,

Value x 1 (e.g. 5°C = 500 or 50°F = 5000)

W
45 40046 Temperature setpoint maximum value. Unsigned

Scale 100

Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F,

Value x 1 (e.g. 5°C = 500 or 50°F = 5000)

W
46 40047 Dry mode relative humidity setpoint. Unsigned

Scale 1

Unit: %RH, Range: 10 to 90%RH

Value x 1 (e.g. 10%RH = 10)

W
47 40048 Dry mode relative humidity setpoint dead band. Unsigned

Scale 1

Unit: %RH, Range: 1 to 10%RH

Value x 1 (e.g. 10%RH = 10)

W
48 40049 Occupied static pressure control loop setpoint. Unsigned

Scale 10

Unit: Pascal (Pa), Range: 0 to 1250 Pa

Value x 10 (e.g. 3 Pa = 30)

W
49 40050 Unoccupied static pressure control loop setpoint. Unsigned

Scale 10

Unit: Pascal (Pa), Range: 0 to 1250 Pa

Value x 10 (e.g. 3 Pa = 30)

W
50 40051 CO2 concentration setpoint. Unsigned

Scale 1

Unit : PPM, Range : 0 to 1000 PPM

Value x 1 (e.g. 3 PPM = 3)

W
51 40052 CO2 concentration setpoint dead band. Unsigned

Scale 1

Unit : PPM, Range : 0 to 200 PPM

Value x 1 (e.g. 3 PPM = 3)

W
52 40053 Supply air temperature offset. Signed

Scale 100

Unit: °C/°F, Range: ± 5ºC or +/-9ºF

Value x 100 (e.g. 2ºC = 200 or 3ºF = 300)

W
53 40054 Supply air temperature humidity offset. Signed

Scale 100

Unit: %RH, Range: ± 5%RH Value x 100 (e.g. 2%RH = 200) W
54 40055 Outside air temperature offset. Signed

Scale 100

Unit: °C/°F, Range: ± 5ºC or +/-9ºF

Value x 100 (e.g. 2ºC = 200 or 3ºF = 300)

W
55 40056 Outside air temperature humidity offset. Signed

Scale 100

Unit: %RH, Range: ± 5%RH Value x 100 (e.g. 2%RH = 200) W
56 40057 Room air temperature offset. Signed

Scale 100

Unit: °C/°F, Range: ± 10ºC or ± 18ºF Value x 100 (e.g. 2ºC = 200 or 3ºF = 300) W
57 40058 Room air relative humidity offset. Signed

Scale 100

Unit: %RH, Range: ± 5%RH Value x 100 (e.g. 2%RH = 200) W
58 40059 Static pressure offset. Signed

Scale 10

Unit: Pascal (Pa), Range: ± 125 Pa Value x 10 (e.g. 2 Pa = 200) W
59 40060 Minimum fan speed. Unsigned

Scale 1

Unit: %, Range: 0 to 100%

Value x 1 (e.g. 3% = 3)

W
Protocol Base Holding Register  

Description

 

Data Type

 

Range

 

Writable

60 40061 Temperature control proportional band. Unsigned

Scale 100

Unit: °C/°F, Range: 0.5°C to 20°C or 33°F to 68°F,

Value x 100 (e.g. 5°C = 500 or 50°F = 5000)

W
61 40062 Temperature control integral time. Unsigned

Scale 1

Unit: Seconds, Range: 0 to 255 seconds,

Value x 1 (e.g. 100 secs = 100)

W
62 40063 Temperature control derivate time. Unsigned

Scale 1

Unit: Seconds, Range: 0 to 255 seconds,

Value x 1 (e.g. 100 secs = 100)

W
63 40064 Static pressure control proportional band. Unsigned

Scale 1

Unit: Pascal (Pa), Range: 0 to 250 Pa

Value x 1 (e.g. 3 Pa = 3)

W
64 40065 Static pressure control integral time. Unsigned

Scale 1

Unit: Seconds, Range: 0 to 255 seconds,

Value x 1 (e.g. 100 secs = 100)

W
65 40066 Static pressure control derivate time. Unsigned

Scale 1

Unit: Seconds, Range: 0 to 255 seconds,

Value x 1 (e.g. 100 secs = 100)

W
66 40067 Control band. Unsigned

Scale 100

Unit: °C/°F, Range: 2°C to 10°C or 36°F to 50°F,

Value x 100 (e.g. 5°C = 500 or 50°F = 5000)

W
67 40068 Modbus timeout. Unsigned

Scale 1

Unit: Seconds, Range: 15 to 1800 seconds,

Value x 1 (e.g. 100 secs = 100)

W
68 40069 Number of synchronization timeouts. Unsigned

Scale 1

Unit: No Unit, Range: 0 to 65535,

Value x 1 (e.g. 100 = 100)

W
69 40070 No heat detection deadband. Unsigned

Scale 100

Unit: °C/°F, Range: 2°C to 8°C or 36°F to 46°F,

Value x 100 (e.g. 5°C = 500 or 5°F = 500)

W
70 40071 No heat detection delay. Unsigned

Scale 1

Unit: Seconds, Range: 30 to 240 seconds,

Value x 1 (e.g. 100 secs = 100)

W
71 40072 Exhaust fan state. Unsigned 0 = Off, 1 = On RO
72 40073 On/Off damper state. Unsigned 0 = Closed, 1 = Open RO
73 40074 On/Off damper feedback. Unsigned 0 = Closed, 1 = Open RO
74 40075 CMU fan enable. Unsigned 0 = No, 1 = Yes RO
75 40076 CMU heater stage 2 state. Unsigned 0 = Off, 1 = On RO
76 40077 Binary input 3 contact type. Unsigned 0 = NO, 1 = NC W
77 40078 Binary input 4 contact type. Unsigned 0 = NO, 1 = NC W
78 40079 Binary output 1 contact type. Unsigned 0 = NO, 1 = NC W
79 40080 Binary output 2 contact type. Unsigned 0 = NO, 1 = NC W
Protocol Base Holding Register  

Description

 

Data Type

 

Range

 

Writable

80 40081 Enable occupancy inputs. Unsigned 0 = No, 1 = Yes W
81 40082 Dry mode. Unsigned 0 = Disable, 1 = Enable W
82 40083 CO2 extract. Unsigned 0 = Disable, 1 = Enable W
83 40084 Static pressure loop. Unsigned 0 = Disable, 1 = Enable W
84 40085 Occupancy inactive mode. Unsigned 0 = Unoccupied, 1 = Off W
85 40086 CMU occupancy state. Unsigned 1 = Occupied | 2 = Unoccupied | 3 = Off W
86 40087 Temperature setpoint source. Unsigned 1 = On Board | 2 = TSTAT | 3 = Network W
87 40088 AI1 input mode. Unsigned 1 = Off | 2 = SAT | 3 = SARH | 4 = OAT | 5 = OARH | 6 = Static Pressure | 7 = Fan Setpoint | 8 = Damper Feedback W
88 40089 AI2 input mode. Unsigned 1 = Off | 2 = SAT | 3 = SARH | 4 = OAT | 5 = OARH | 6 = Static Pressure | 7 = Fan Setpoint | 8 = Damper Feedback W
89 40090 AI3/BI3 input mode. Unsigned 1 = Off | 2 = SAT | 3 = OAT | 4 = Damper Feedback | 5 = Occupancy | 6 = Fan Speed Stage W
90 40091 AI4/BI4 input mode. Unsigned 1 = Off | 2 = SAT | 3 = OAT | 4 = Damper Feedback | 5 = Occupancy | 6 = Fan Speed Stage W
91 40092 AO1 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W
92 40093 AO2 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W
93 40094 BO1 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W
94 40095 BO2 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W
95 40096 Static pressure sensor range. Unsigned 1 = 250 Pa | 2 = 500 Pa | 3 = 1250 Pa W
96 40097 Analog input 1 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W
97 40098 Analog input 2 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W
98 40099 Analog output 1 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W
99 40100 Analog output 2 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W
100 40101 Control temperature source. Unsigned 1 = SAT | 2 = RAT W
101 40102 LCD screen top line value. Unsigned 1 = None | 2 = Time | 3 = CO2 | 4 = SARH | 5 = RARH W
102 40103 LCD screen displayed temperature. Unsigned 1 = Default | 2 = Alternate | 3 = SAT | 4 = TSTAT W
103 40104 LCD screen last reset reason. Unsigned 1 = No reason | 2 = Independent Watchdog | 3 = Window Watchdog | 4 = Software Reset | 5 = Power Down RO
Protocol Base Holding Register  

Description

 

Data Type

 

Range

 

Writable

 

 

104

 

 

40105

 

 

Alarm status.

 

 

Bit String

B0 = Unblocking Damper Required B1 = SSOR1 Sens Not Detected B2 = SSOR2 Sens Not Required B3 = SAT Not Detected

B4 = RAT Not Detected

B5 = Timeout Comm B6 = AI1 Reading Error B7 = AI2 Reading Error

B8 to B31 = Reserved

 

 

RO

 

 

 

 

105

 

 

 

 

40106

 

 

 

 

System alarm host.

 

 

 

 

Bit String

B0 = Thermal Cutout B1 = Comm Timeout

B3 = Heater Temp Cutout B4 = SSR Temp Cutout B5 = Board Temp Cutout B6 = Duct Temp Cutout

B7 = Heater Temp 1 Failure B8 = Heater Temp 2 Failure B9 = Board Temp Failure B10 = SSR Temp Failure

B11 = TRL Failure B13 = Invalid Config

B14 = Fan Temp Failure B16 = External Temp Failure B17 = Supply Temp Failure B22 = Fan Feedback Error B30 = Air Flow Not Detected B31 = Heat Not Detected

B2, B12, B15, B18 to B21, B23

to B29 = Reserved

 

 

 

 

RO

400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com
Toll-free in North America: 1-800-361-2308
Tel.: 514-333-1433
Fax: 514-333-3163
Customer service fax: 514-333-1091
Monday to Friday: 8:00 am to 5:00 pm (Eastern time)