MULTIBETON Fixed Value Control Set

Overview
Use the fixed value control set to connect an underfloor heating system to a higher-temperature heating circuit (e.g., radiators) by reducing the boiler/primary flow temperature to the required underfloor heating flow temperature through hydraulic mixing of return water. The set also includes a safety temperature limiter to protect against exceeded flow temperatures.
Specifications
| Operating medium | Non-corrosive heating water per VDI 2035 or ÖNORM H 5195; or glycol/water mixture up to 50% glycol |
| Fixed value control set use range (medium temperature) | -10 °C to +110 °C |
| Permissible operating pressure | Up to 6 bar |
| Safety temperature limiter | 55 °C (factory-set maximum temperature) |
| Circulation pump | Wilo-Para 15-130/4-20/SC |
| Energy efficiency index | ≤ 0.20 |
| Operating voltage | AC 230 V, 50 Hz |
| Power consumption (P1) | Min. 3 W, Max. 20 W |
| Protection class | IP 40 |
| Pump length | 130 mm |
| Thermostatic head | Startec 4 |
| Sensor | Liquid immersion sensor with 2 m capillary tube |
| Thermostatic head setpoint range | 20 °C to 50 °C |
| Thermostatic head connection thread | M 30 x 1.5 |
| Integrated thermostatic valve | Constant volume flow = 2.56 m³/h |
| Return regulating valve | DN20 |
| Regulating valve insert | Constant volume flow = 1.93 m³/h |
| Presettable ζ-value (open) | 93.2 |
| Permissible operating temperature | 120 °C |
| Permissible operating pressure | 10 bar |
Quick Setup & Use
- Fit the assembly (circulation pump and control bar) directly to the union fittings of the underfloor heating manifold using a flat seal.
- Screw the upper control bar (with immersion sensor) onto the return manifold bar; screw the lower control bar (with thermometer) onto the flow manifold bar.
- Mount the assembly in the manifold cabinet using the supplied fixing clamps (install threaded extensions with washers at the two upper fixing points before fitting clamps).
- Screw the flow thermostatic valve with 3/4 union fitting into the return manifold bar; screw the return regulating valve with 3/4 union fitting into the flow manifold bar.
- Wire the circulation pump electrically according to the manufacturer’s specifications, integrating the safety temperature limiter glued into the control bar as a 1-pole NC contact.
- Fill, bleed, and pressurise the system; bleed the circulation pump (refer to the enclosed pump operating instructions).
- Set the primary circuit temperature to the design value (e.g., 70 °C).
- Adjust the return flow limiter using the specified method/turns and check that the underfloor heating return temperature is at least 20–25 °C.
- Set the underfloor heating desired flow temperature on the thermostatic head; monitor the manifold flow temperature and flow rates for proper adjustment during commissioning.

Application
- Flow thermostatic valve and head with immersion sensor integrated in the control bar
- Return regulating valve integrated in the control bar
- Wilo-Para 15-130/4-20/SC pump
- Safety temperature limiter 55 °C, glued into the control bar
- Backflow preventer integrated in the control bar
- Plug-in thermometer
- Seals
- Thread extensions incl. washers
- Installation instructions
- Brief instructions Wilo-Para 15-130/4
To prevent the flow temperature from being exceeded without authorisation (e.g. in the event of a defective thermostatic head), the fixed set point control set has a safety temperature limiter glued into the control bar. It interrupts the power supply to the circulation pump if the factory-set maximum temperature of 55 °C is exceeded. The circulation pump starts automatically as soon as the temperature falls below the maximum temperature again.
Assembly
Fit the assembly with circulation pump and control bar directly to the union fittings of the heating circuit manifold with a flat seal:
- Remove the 3/4″ end plugs from the manifold bar;
- Screw the upper control bar of the fixed value control set (with immersion sensor) to the return heating circuit manifold bar;
- Screw the lower control bar (with thermometer) to the flow heating circuit manifold bar;
- Mount the assembly in the manifold cabinet using the fixing clamps supplied with the manifolds. Attention! The threaded extensions including the washers are fitted to the two upper fixing points of the clamps before the fixing clamps are fitted. This raises the assembly and prevents contact between the pump housing and the cabinet wall.
- Screw the flow thermostatic valve incl. 3/4″ union fitting into the return manifold bar.
- Screw the return flow regulating valve incl. 3/4″ union fitting into the flow manifold bar.
- Wire the circulation pump electrically according to the manufacturer’s specifications. Please note that the safety temperature limiter glued into the control bar must be integrated into the circuit as a 1-pole NC contact.
- The total pressure loss of the underfloor heating can be found in the design data. If this data is not known, the default setting “2” should be used as an approximation.

Note: Depending on the system configuration, it may be necessary to provide additional components, e.g. a hydraulic separator or a non-return valve, between the fixed value control set and the high-temperature primary circuit. These can prevent the circulation pumps from influencing each other adversely and the associated incorrect flow or flow noise. The boiler manufacturer’s technical documentation must be observed.
If the set flow temperature of the underfloor heating is not reached at the design flow temperature of the primary circuit (e.g. 70 °C), the return flow limiter must be opened in small steps until the desired set value is reached.
The flow temperature of the primary circuit must be approx. 10 to 15 K above the desired underfloor heating temperature.
The desired flow temperature of the underfloor heating must be set on the thermostatic head and observed over a certain period of time on the thermometer of the fixed value control set. This may take some time during initial commissioning, as the entire water volume of the still cold heating circuits must be heated up by adding water from the primary circuit. The return temperature of the underfloor heating should therefore be at least 20 to 25 °C for proper adjustment.
For certain systems (e.g. thermal heating with hot water storage tank), it may be necessary to provide additional installations. If the flow of heating medium in the primary circuit is interrupted, e.g. due to night shut-off or domestic hot water heating, it is possible that the pump of the fixed value control set may press into the return flow of the radiators or that noises may occur at the heat generator.
For this reason, a non-return valve, hydraulic separator or similar should also be provided in these systems. The manufacturer’s documentation and hydraulic diagrams of the boiler manufacturer must always be observed.
Attention: The electrical installation of the circulation pump may only be carried out by a qualified electrician. The applicable VDE safety regulations must be observed.
- Filling and venting of the fixed value control set via the integrated filling and draining tap in the flow bar of the heating circuit manifold. A backflow preventer integrated in the control manifold prevents an incorrect flow in the direction of the return heating circuit manifold. To bleed the circulation pump, please refer to the enclosed operating instructions.
Adjustment of the Fixed Value Control Set
- Fill, bleed and pressurise the system.
- Carry out hydraulic balancing of the underfloor heating circuits (see also the description of the heating circuit manifolds). All valves of the heating circuit manifolds (flow and return) must be set to the characteristic values specified in the planning.
- Increase the primary circuit temperature to the design temperature (e.g. 70 °C).
- Unscrew the sealing cap on the return flow limiter (spanner size 19) and use a 5 mm hexagon spanner to close the spindle by turning it clockwise as far as it will go (smallest setting value “0”).
- Use the hexagon spanner to set the spindle to the calculated value in turns (see below) by turning it anti-clockwise (e.g. open by 2 turns).
- Check the flow temperature at the manifold and the flow rates of the underfloor heating circuits. The return temperature of the underfloor heating should be at least 20 – 25 °C.
- If the flow temperature at the manifold is too low, open the regulating cone of the return flow limiter further by turning it anti-clockwise. Ensure that the heating circuits continue to receive a sufficient quantity of water.
- Finally, the sealing cap on the return flow limiter can be screwed back on.
Technical Data
- Energy efficiency index: ≤ 0.20
- Operating voltage: AC 230 V 50 Hz
- Climate Protection Directive: ErP 2015 ready
- Power consumption: P1 (W) min. = 3 W, max. = 20 W
- Length: 130 mm
- Protection class: IP 40
- Media temperature
Thermostatic Head Startec 4
- Liquid sensor as immersion sensor with 2 m capillary tube
- Memo number 20 – 30 – 40 – 50
- Setpoint range 20 °C – 50 °C
- Connection thread M 30 x 1.5
- Integrated thermostatic valve (constant volume flow = 2.56 m³/h)
Return Regulating Valve DN20
- Regulating valve insert (constant volume flow = 1.93 m³/h)
- Presettable
- ζ-value (open) 93.2
- Permissible operating temperature 120 °C
- Permissible operating pressure 10 bar
| Setting turns | Constant volume flow value |
|---|---|
| 0.25 | 0.22 |
| 0.5 | 0.37 |
| 1 | 0.62 |
| 1.5 | 0.92 |
| 2 | 1.27 |
| 2.5 | 1.55 |
| 3 | 1.72 |
| 3.5 | 1.85 |
Calculation example
| Differential pressure to be throttled | Δp = 34 mbar |
| Heat flow | Q = 2440 W |
| Temperature spread | ΔT = 15 K (70/55 °C) |
| Solution | |
| Mass flow | ·m = Q / (c · ΔT) = 2440 / (1.163 · 15 K) = 140 kg/h |
| Setting turns (from diagram) | = 1.25 |
Troubleshooting
The desired flow temperature in the underfloor heating circuits is not reached!
- Flow temperature in primary circuit too low
Possible remedy
- Raise to at least 10 – 15 K above the desired underfloor heating temperature
Possible cause
- Return temperature in secondary circuit too low (min. 20 °C)
Possible remedy
- Return flow limiter not adjusted (preset, see diagram on page 3)
Possible cause
- No hydraulic balancing of the underfloor heating circuits
Possible remedy
- Carry out balancing according to planning documents
Possible cause
- Actuators are closed
Possible remedy
- Check heat requirement from room thermostat
Possible cause
- Circulation pump fault
Possible remedy
- Follow the enclosed operating instructions
Noises or reheating in the boiler or radiators!Possible causes:
- Particularly in the case of boilers with hot water storage tanks, the pump of the fixed-value control set may press into the return flow of the radiators or cause noises in the boiler at the changeover valve or the boiler pump.
Possible remedies
- Additional installation of non-return valves or a hydraulic separator in the primary circuit. In any case, the manufacturer’s documentation and hydraulic diagrams of the boiler manufacturer must be observed.