Danfoss-LOGO

Danfoss 80G8280 Ejector Controller

Danfoss-80G8280-Ejector-Controller-PRODUCT

Informazzjoni dwar il-Prodott

  • The EKE 80 Ejector Controller receives input signals from Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC.
  • It can control multiple HP/LP ejectors and up to 2 modulating control valves to facilitate the ‘lift’ of the MT suction pressure, thereby decreasinkonsum tal-enerġija g.
  • The EKE 80 drive controller is suitable for both new and retrofit systems.
  • Identify the connectors on the EKE 80 Ejector Controller according to the manual.
  • Connect the necessary input signals from the Danfoss controllers or PLC to the designated connectors on the EKE 80.
  • Ensure proper power supply connection to the controller.
  • Follow the specific wiring instructions for connecting HP/LP ejectors and modulating control valves.
  • Ittestja s-sistema biex tiżgura l-funzjonalità xierqa.
  • Refer to the manual for detailed information on connecting various components to the EKE 80 Ejector Controller.
  • Use the specified connectors and follow the wiring guidelines provided.
  • Power on the EKE 80 Ejector Controller.
  • Set the desired parameters using the interface connected to the controller.
  • Monitor the system performance and make adjustments as needed for optimal efficiency.

Introduzzjoni

  • The EKE 80 Ejector Controller receive inputs signals from the Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC.
  • It can control multiple HP/LP ejectors and up to 2 modulating control valves to facilitate the ‘lift’ of the MT suction pressure and thereby decrease energy consumption.
  • The EKE 80 drive controller is suitable for both new and retrofit systems.

Identifikazzjoni

Danfoss-80G8280-Ejector-Controller-FIG-2

Applikazzjoni example

Danfoss-80G8280-Ejector-Controller-FIG-3

Karatteristiċi ġenerali u twissijiet

Karatteristiċi tad-djar tal-plastik

  • Immuntar tal-binarji DIN konformi ma' EN 60715
  • V0 li jintefa waħdu skont IEC 60695-11-10 u test tal-wajer li jkantat/sħun f'960 °C skont IEC 60695-2-12
  • Test tal-ballun: 125 °C skond IEC 60730-1. Kurrent ta 'tnixxija: ≥ 250 V skond IEC 60112

Karatteristiċi oħra

  • Kundizzjonijiet operattivi CE: -20T60 / UL: 0T50, 90% RH mingħajr kondensazzjoni
  • Kondizzjonijiet tal-ħażna: -30T80, 90% RH li ma jikkondensawx
  • Biex jiġi integrat f'apparat tal-Klassi I u/jew II
  • Indiċi ta' protezzjoni: IP40 biss fuq il-qoxra ta' quddiem
  • Perjodu ta 'stress elettriku fuq partijiet iżolanti: twil
  • Adattat għall-użu f'ambjenti bi grad ta 'tniġġis 2
  • Kategorija ta' reżistenza għas-sħana u n-nar: D
  • Immunità kontra voltage surges: category II, category III for versions without display
  • Klassi u struttura tas-softwer: klassi A

Konformità
marka CE

  • Dan il-prodott huwa ddisinjat biex jikkonforma mal-istandards tal-UE li ġejjin:
  • Vol baxxtage direttiva LVD 2014/35/UE:
    • EN60730-1: 2011 (Kontroll elettriku awtomatiku għal użu domestiku u użu simili. Rekwiżiti ġenerali)
    • EN60730-2-9: 2010 (Rekwiżiti Partikolari għal Kontrolli li Jħossu t-Temperatura)
  • Kompatibilità elettromanjetika Direttiva EMC 2014/30/UE:
  • EN 61000-6-3: 2007 +A1: 2011 (Standard ta' emissjoni għal ambjenti residenzjali, kummerċjali u industrijali ħfief)
  • EN 61000-6-2: 2005 (Immunità għal ambjenti industrijali)
  • Direttiva RoHS 2011/65/UE u 2015/863/UE:
    • EN50581:2012
  • RoHS taċ-Ċina
    Approvazzjoni UL:
  • UL file E31024

Twissijiet ġenerali

  • Kull użu li mhux deskritt f'dan il-manwal huwa kkunsidrat mhux korrett u mhux awtorizzat mill-manifattur
  • Ivverifika li l-installazzjoni u l-kundizzjonijiet tat-tħaddim tal-apparat jirrispettaw dawk speċifikati fil-manwal, speċjalment dwar il-provvista voltage u l-kundizzjonijiet ambjentali
  • This device contains live electrical components therefor,e all the service and maintenance operations must be performed by qualified personnel
  • L-apparat ma jistax jintuża bħala mezz ta 'sikurezza
  • Ir-responsabbiltà għal korriment jew ħsara kkawżata mill-użu mhux korrett tal-apparat hija biss tal-utent

Twissijiet ta' installazzjoni

  • Pożizzjoni tal-immuntar rakkomandata: vertikali
  • L-installazzjoni trid titwettaq skont l-istandards u l-leġiżlazzjoni lokali tal-pajjiż
  • Dejjem ħadmu fuq il-konnessjonijiet elettriċi bl-apparat skonnettjat mill-provvista tal-enerġija prinċipali
  • Qabel ma twettaq kwalunkwe operazzjoni ta 'manutenzjoni fuq l-apparat, skonnettja l-konnessjonijiet elettriċi kollha
  • Għal raġunijiet ta' sigurtà, l-apparat għandu jitwaħħal ġewwa pannell elettriku mingħajr ebda partijiet ħajjin aċċessibbli
  • Tesponix l-apparat għal sprejs kontinwu tal-ilma jew għal umdità relattiva akbar minn 90%.
  • Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of fiammable gases are present, dust, strong vibrations or shock, large and rapid fluctuations in ambient temperature that in combination with high humidity,y can condensate, strong magnetic and/or radio interference (e.g., transmitting antennae)
  • Meta tgħaqqad it-tagħbijiet, oqgħod attent mill-kurrent massimu għal kull relay u konnettur
  • Use cable ends suitable for the corresponding connectors. After tightening the screws of the connectors, slightly tug the cables to check their tightness
  • Uża kejbils xierqa tal-komunikazzjoni tad-data. Irreferi għall-Gwida ta 'Installazzjoni "Speċifikazzjoni tan-netwerk tal-ħardwer MCX" għat-tip ta' kejbil li għandu jintuża u rakkomandazzjonijiet ta 'setup
  • Naqqas il-mogħdija tas-sonda u l-kejbils tad-dħul diġitali kemm jista 'jkun, u tevita mogħdijiet spirali li jagħlqu tagħmir tal-enerġija. Issepara minn tagħbijiet induttivi u kejbils tal-enerġija biex tevita ħsejjes elettromanjetiċi possibbli
  • Evita li tmiss jew kważi tmiss il-komponenti elettroniċi mwaħħla fuq il-bord biex tevita skariki elettrostatiċi
  • Il-prodott mhuwiex adattat biex jiġi espost direttament għall-Internet

DISCLAIMER: Użu Professjonali Biss

  • Dan il-prodott mhuwiex suġġett għar-regolament PSTI tar-Renju Unit, peress li huwa għall-provvista u l-użu biss minn professjonisti bl-għarfien espert u l-kwalifiki meħtieġa.
  • Any misuse or improper handling may result in unintended consequences. By purchasing or using this product, you acknowledge and accept the professional-use-only nature of its application.
  • Danfoss ma jassumi l-ebda responsabbiltà għal danni, korrimenti, jew konsegwenzi ħżiena (“ħsara”) li jirriżultaw mill-użu mhux korrett jew mhux xieraq tal-prodott u inti taqbel li tindennizza lil Danfoss għal kwalunkwe dannu bħal dan li jirriżulta mill-użu ħażin jew mhux xieraq tiegħek tal-prodott.

Speċifikazzjonijiet tekniċi

Provvista ta' enerġija

  • 21 – 265 V AC, 50/60 Hz. Maximum power consumption: 15 W. Insulation between power supply and the extra-low voltage: imsaħħaħ
  • 40 – 230 V DC

Interface tal-komunikazzjoni

Interface Użu Tikketta tal-konnettur Tekniku data
CANbus Fieldbus għall-konnessjoni ma 'interfaces ta' l-utent, kontrolluri MCX, għodod ta 'servizz eċċ. CAN CAN-RJ Physical layer according to ISO 11898-2 High Speed CAN bus Frame format according to CAN 2.0B specification

Transceiver not isolated (power supply has reinforced isolation)

Apparat USB Ippreparat għall-użu fil-futur USB-DEV Ipplaggja: Tip Mini B
USB ospitanti For connection to the Flash drive for application software update, datalogging and service USB-H Ipplaggja: Tip A
RS485-1

RS485-2 (MCX20B2 biss)

Communication bus to BMS (e.g. Modbus slave), service tools, smart devices (e.g. Modbus master), RS485-1 can be polarized as master from the application RS485-1 RS485-2 Physical layer according to EIA 485 Ref3

Provide 500 V peak transient galvanic isolation

Ethernet Għal web server functionality, integration (e.g. Modbus TCP)

NOTICE! Do not route cable outside of buildings. Connect only to IT equipment compliant with EN 60950 or EN 62368 (Information technology equipment. Safety. General requirements)

Ethernet Tip ta 'interface: 10 BASE-T u 100 BASE-TX, IEEE 802.3.

MDI-X (Automatic medium- dependent interface crossover)

Tulijiet tal-wajer

Interface Tul massimu tal-wajer (m) Max. baudrate (bps) Min. daqs tal-wajer
Ethernet 100 10/100 M  
  1000 50 K AWG18
  500 125 K AWG22
CANbus 250 250 K AWG24
  80 500 K AWG26
  30 1 M AWG26
RS485 1000 125 K AWG22
Wiring tas-sinjal 30    

Konnessjoni

Konnetturi Tip Dimensjonijiet
Fuq Bord
Input diġitali 1 konnettur Tip ta 'konnettur plug-in bil-kamin b'3 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Input analogu 11-14 konnettur Tip ta 'konnettur plug-in bil-kamin b'7 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Input diġitali 2 konnettur Tip ta 'konnettur plug-in bil-kamin b'3 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Input diġitali 3 konnettur Tip ta 'konnettur plug-in bil-kamin b'3 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Input diġitali 4 konnettur Tip ta 'konnettur plug-in bil-kamin b'3 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Input diġitali 5-8 konnettur Tip ta 'konnettur plug-in bil-kamin b'5 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Bord tal-qiegħ
Output diġitali 1-5 konnettur Tip ta 'konnettur plug-in bil-kamin b'10 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Konnettur tal-ħruġ diġitali 6 Tip ta 'konnettur plug-in bil-kamin b'6 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Konnettur Ethernet Tip ta 'plagg RJ 8 8 / 45 mod  
Konnettur USB ospitanti USB Tip A  
Input analogu 1-5 konnettur Tip ta 'konnettur plug-in bil-kamin b'11 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Konnettur tal-provvista tal-enerġija Tip ta 'konnettur plug-in bil-kamin b'2 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Output diġitali 9-13 konnettur Tip ta 'konnettur plug-in bil-kamin b'10 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Output analogu 1-2 konnettur Tip ta 'konnettur plug-in bil-kamin b'8 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Konnettur RS485 -2 Tip ta 'konnettur plug-in bil-kamin b'3 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Konnettur RS485-1 Tip ta 'konnettur plug-in bil-kamin b'3 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

konnettur CAN Tip ta 'konnettur plug-in bil-kamin b'4 direzzjonijiet •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Konnettur CAN-RJ Tip ta 'plagg RJ6 tat-telefon 6/12 mod  
Konnettur USB DEV USB Mini B  

Interface tal-utent

Display LCD

  • Modalità tal-wiri: STN blu trasmissiv
  • back-light: white LED back-light, adjustable via software
  • display format: 128 x 64 dots
  • active visible area: 58 x 29 mm
  • contrast: adjustable via software

Aġġustament tas-settings tal-wiri

  • Settings of the LCD display like contrast and brightness, might need to be adjusted due to external ambient factors.
  • Press and release the Enter and X key after powering on to access the BIOS menu and select the DISPLAY menu.
  • Use UP and DOWN arrow keys to adjust the contrast or the brightness of the display at the desired level.

Wirja esterna

Danfoss-80G8280-Ejector-Controller-FIG-4

Dimensjoni

Dimension EKE 80

Danfoss-80G8280-Ejector-Controller-FIG-5

Konnessjoni, livell aktar baxx

Twissija
Il-provvista voltage of AI may not share the signal with other controllers

Danfoss-80G8280-Ejector-Controller-FIG-6

Konnessjoni, livell ta 'fuq

Danfoss-80G8280-Ejector-Controller-FIG-7

AI Tikketta Deskrizzjoni Sinjal tip choice Via software or fieldbus Default Modbus jirreġistra Ikkummenta
AI-01 AI1 Capacity Reference 0-10 V

0-5 V

2-10 V

0–20 mA

4–20 mA

0-10 V 17902 Max 13.5 V input voltage.

Tqabbadx voltage sources without current limitation (overall 80 mA) to analog inputs while unit is not powered

AI-02 AI2 ICAD Ejector Mode Feedback 0–20 mA

4–20 mA

4–20 mA 17903
AI-03 AI3 ICAD Bypass Mode Feedback 0–20 mA

4–20 mA

4–20 mA 17904
AI-04 AI4 Trasmettitur tal-Pressjoni 0-5 V

0-10 V

0–20 mA

4–20 mA

4–20 mA 17905
AI-05 AI5 Sensor tat-Temperatura 0–10 V NTC–10K PT1000 PT1000 17906
AI-06 N/A Not available for customer use N/A N/A Riżervat Riżervat
AI-07
AI-08
AI-09
AI-10
AI-11 AI11 Not used in logic. User configurable IO None NTC–10K PT1000 0–5 V

0-10 V

2-10 V

0–20 mA

4–20 mA

Xejn 17907 Max 13.5 V input voltage.

Tqabbadx voltagSorsi mingħajr limitazzjoni tal-kurrent (ġeneralment 80 mA) għal inputs analogi waqt li l-unità ma tkunx imħaddma

AI-12 AI12 17908
AI-13 AI13 17909
AI-14 AI14 17910
AI-15  

N/A

 

Not available for customer use

 

N/A

 

N/A

 

Riżervat

 

Riżervat

AI-16
A0 Tikketta Deskrizzjoni Sinjal tip għażla Default Modbus jirreġistra Ikkummenta
A0-01 AO1 ICAD Ejector Mode Request OD 0-10 V

2-10 V

0-10 V 18102 Analog Outputs galvanically isolated, minimum load 1K Ω (10 mA) for each output
A0-02 AO2 ICAD Bypass Mode Request OD 0-10 V

2-10 V

0-10 V 18103
A0-03 N/A Not available for customer use N/A Riżervat Riżervat
A0-04
A0-05
A0-06
DI Tikketta Deskrizzjoni Sinjal tip għażla Default Modbus jirreġistra Ikkummenta
DI-01 DI1 Not used in logic, User configurable IO 24 V or 230 V Depending on port used. See upper level diagram  

 

 

 

17498 24 V Opto isolated, 24 V AC 50/60 Hz or 24 V DC Rated current: 5 mA @ 24 V AC

230 V Opto isolated, 86–265 V AC / 50/60 Hz, Reinforced isolation, Rated current: 2,5 mA @ 265 V AC

DI-02 DI2 Not used in logic, User configurable IO 17499
DI-03 DI3 Not used in logic, User configurable IO 17500
DI-04 DI4 Not used in logic, User configurable IO 17501
DI-05 DI5 Suction Flow Control Dry contact and/or 24 V AC  

 

 

17503 As the inputs are not isolated, caution has to be used when applying 24 V AC: the same polarity of the supply MUST always be used on COM/GND connection. Counting function with max frequency of 16.6 Hz (30 ms minimum pulse time)
DI-06 DI6 Ejector Mode Signal Error 17504
DI-07 DI7 Bypass Mode Error Signal 17505
DI-08 N/A Not used in logic N/A N/A Riżervat Riżervat
DI-09
DI-10
DI-11
DI-12
DI-13
DI-14
DI-15
DI-16
DI-17
DI-18
DI-19
DI-20
DI-21
DI-22
DO Tikketta Deskrizzjoni Sinjal tip għażla Default Modbus jirreġistra Ikkummenta
DO-01 DO1 Ħruġ ta' allarm   17702 5 A 250 V AC għal tagħbijiet reżistivi – 100,000 ċiklu

3 A 250 V AC għal tagħbijiet induttivi – 100,000 ċiklu b'cos(phi) = 0.4

UL: 3 A resistive, 250 V AC, 100,000 cycles; 1/8 hp, 125/250 V AC, 30,000 cycles; C300 pilot duty, 125/250 V AC, 30,000 cycles

DO-02 N/A Not used in logic N/A N/A Riżervat  
DO-03 DO3 User-assigned Ejector  

 

 

 

 

 

Not assigned Ejector 1

Ejector 2

Ejector 3

Ejector 4

Ejector 5-8 expansion module only

Mhux assenjat 17703 Internal Solid State Relay for Industrial Ejector Coils:

15–280 Vrms, 0.5 A

UL: Making current: 7 A, Breaking current:

0.7 A, Pilot duty (cos θ 0.35), 240 V AC, N.O

IMPORTANTI: For a Multi-Ejector, an external Solid State Relay is necessary between the assigned DO and the

Multi-Ejector solenoid coils that meet the following specifications:

Leakage current suppression.

At least 2 A rating for both 110 V and 230 V Multi-Ejector coils.

IMPORTANTI: Ejectors 5 to 8 can only be assigned to an extension module. An extension module is the same controller device as this device except that it is user-configured/ defined as an extension module for control of extra Ejectors, i.e., When there are more than 4 Industrial Ejectors.

DO-04 DO4 User-assigned Ejector Mhux assenjat 17704
DO-05 DO5 User-assigned Ejector Mhux assenjat 17705
DO-06 DO6 User-assigned Ejector Mhux assenjat 17706
DO-07 N/A Not used in logic N/A N/A Riżervat N/A
DO-08
DO-09
DO-10
DO-11
DO-12
DO-13
DO-14
DO-15
DO-16
DO-17
DO-18
DO-19
DO-20

KUNTATT

  • Danfoss A/S
  • Soluzzjonijiet tal-Klima
  • danfoss.com
  • +45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals cataloques descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding it and to the extent, explicit reference is made in a quotation or order confrmation. Dantoss cannot accept any responsibility for possible errors in catalogues, brochures, videos, and other material. Janfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered, provided that such alterations can be made without changes to form, fit or function of the product.
It-trademarks kollha f'dan il-materjal huma proprjetà ta' Danfoss A/S jew kumpaniji tal-grupp Danfoss. Danfoss u l-logo Danfoss huma trademarks ta’ Danfoss A/S. Id-drittijiet kollha riżervati.

Danfoss-80G8280-Ejector-Controller-FIG-1

FAQ

Q: Can the EKE 80 Ejector Controller be used with third-party controllers?

A: The EKE 80 is designed to work with Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC. Compatibility with third-party controllers may vary, it is recommended to consult with Danfoss support for further information.

Q: What is the maximum wire length supported for Ethernet connection?

A: The maximum wire length for Ethernet connection is 100 meters.

Dokumenti / Riżorsi