MRCOOL-logo

MRCOOL HCMP Series Multi Position Cased Coils

MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- product

Specifications:
  • Product Name: PRODIRECTTM Series Multi-Position Cased Coils
  • Models: HCMP3036AFOA, HCMP3036BFOA, HCMP3036CFOA, HCMP3642BFOA,HCMP3642CFOA, HCMP3642DFOA, HCMP4248BFOA, HCMP4248CFOA, HCMP4248DFOA, HCMP4860CFOA, HCMP4860DFOA
  • Version Date: 10/02/2024
  • For the latest version of the manual, visit www.mrcool.com/documentation

Product Usage Instructions

Safety:
Read the safety precautions in the manual before using the product to prevent any damage or injury.

Unit Overview:
The coil can be positioned for bottom return air in the upflow and horizontal right applications. For downflow and horizontal left applications, it should be positioned for top return. Install the coil downstream of the furnace for furnace applications.

Installation:

  1. Replacement Parts: Use genuine replacement parts as specified in the manual to ensure proper functioning.
  2. Pre-Installation Instructions: Follow the pre-installation instructions provided in the manual carefully.
  3. Installation & Trap Connection: Install the cased coils as per the instructions provided in the manual and ensure proper trap connection.

 Drain Application:

  1. Condensate Drain Piping: Properly install condensate drain piping as described in the manual to prevent leakage.
  2. Plastic Drain Pan Installation: Follow the instructions for installing the plastic drain pan correctly to collect condensate.

Refrigerant Connections:
Refer to the manual for detailed instructions on how to make proper refrigerant connections.

Piston/TXV Installation:

  1. Piston Installation: Install the piston according to the guidelines provided in the manual.
  2. Optional TXV Kit Installation: If applicable, follow the instructions for installing the optional TXV kit.

Airflow Performance:
Ensure proper airflow performance by following the guidelines in the manual.

Frequently Asked Questions (FAQ):

  • Q: What should I do if I encounter a problem with airflow performance?
    A: Check for any blockages in the air pathways and ensure that the coil is positioned correctly for the specific application as outlined in the manual.

Safety Precautions

Read Before Using
Incorrect usage may cause serious damage or injury. The symbols below are used throughout this manual to indicate instructions that should be followed closely or actions that should be avoided to prevent death, injury, and/or property damage.

WARNING
Indicates the possibility of personal injury or loss of life.

CAUTION
Indicates the possibility of property damage or serious consequences.

WARNING

  • These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjustment, and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service, or maintenance possibly resulting in fire, electric shock, property damage, personal injury, or death.
  • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  • Children should be supervised to ensure that they do not play with the appliance.
  • Proposition 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to the state of California to cause cancer. For more information, go to www.P65Warnings.ca.gov.
  • Disconnect all power to the unit before starting any service and maintenance. Failure to do so could cause severe electrical shock resulting in personal injure or death.
  • Installation or servicing of this unit can be hazardous due to parts, components and system pressure.
  • Qualified and proper trained service personnel should perform installation and repair. Failure to do so could cause severe electrical shock resulting in personal injury or death.
  • This is a safety alert symbol indicating a potential hazardous situation ,which could result in personal injury, property and/or product damage or death.

 UNIT OVERVIEW

The coil can be positioned for bottom return air in the upflow and horizontal right applications. It must be positioned for top return when in downflow and horizontal left applications. For furnace applications, the coil must be installed downstream (in the air outlet) of the furnace.

NOTE:
This coil comes with a factory-installed heat shield on the drain pan.

Unit Dimensions

MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (1)

 UNIT OVERVIEW

Unit Dimensions
Model Height “H” (in. [mm]) Width “W” (in. [mm]) Supply Duct “A” (in. [mm]) “W1”

(in. [mm])

Liquid Line/ Vapor Line Weight (lbs.[kg])
HCMP3036AFOA 20″ [508] 14-1/2″ [368] 13″ [330] 13-1/2″ [343] 3/8″ / 3/4″ 46 [21]
HCMP3036BFOA 20″ [508] 17-1/2″ [445] 16″ [407] 16-1/2″ [419] 3/8″ / 3/4″ 49 [22]
HCMP3036CFOA 20″ [508] 21″ [533] 19-1/2″ [495] 20″ [508] 3/8″ / 3/4″ 51 [23]
HCMP3642BFOA 26″ [660] 17-1/2″ [445] 16″ [407] 16-1/2″ [419] 3/8″ / 7/8″ 60 [27]
HCMP3642CFOA 26″ [660] 21″ [533] 19-1/2″ [495] 20″ [508] 3/8″ / 7/8″ 62 [28]
HCMP3642DFOA 26″ [660] 24-1/2″ [622] 23″ [584] 23-1/2″ [597] 3/8″ / 7/8″ 66 [30]
HCMP4248BFOA 30″ [762] 17-1/2″ [445] 16″ [407] 16-1/2″ [419] 3/8″ / 7/8″ 73 [33]
HCMP4248CFOA 30″ [762] 21″ [533] 19-1/2″ [495] 20″ [508] 3/8″ / 7/8″ 73 [33]
HCMP4248DFOA 30″ [762] 24-1/2″ [622] 23″ [584] 23-1/2″ [597] 3/8″ / 7/8″ 77 [35]
HCMP4860CFOA 30″ [762] 21″ [533] 19-1/2″ [495] 20″ [508] 3/8″ / 7/8″ 81 [37]
HCMP4860DFOA 30″ [762] 24-1/2″ [622] 23″ [584] 23-1/2″ [597] 3/8″ / 7/8″ 86 [39]

Codes & Regulations
This product is designed and manufactured to comply with national codes and regulations.  Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the installer. MRCOOL® assumes no responsibility for equipment installed in violation of any codes or regulations.

The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Should you have any questions, contact your local EPA office.

Initial Inspection
As soon as the unit is received, it should be inspected and noted for possible shipping damage during transportation. It is the carrier’s responsibility to cover the costs of shipping damage. MRCOOL® will not accept a claim from contractors for any transportation damage.

Clearances
During installation, maintain clearance for maintenance and service access, including coil cleaning and coil assembly removal, refrigerant piping and connections, and the condensate drain line. To ensure a proper installation, select a solid and level location site, and ensure there is enough space for installation and maintenance.

MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (1)

 

 INSTALLATION

Replacement Parts
Contact MRCOOL® for authorized replacement parts.

 Pre-Installation Instructions
Carefully read all instructions for installation prior to installing the unit. Ensure each step or procedure is understood and take into account any special considerations before starting the installation process. Assemble all tools, hardware, and supplies needed to complete the installation. Some items may need to be purchased locally. Make sure everything needed to install the unit is on hand before starting.

Installation & Trap Connection
See the figures below for coil installation and drain connection.

 Installation steps for cased coil:

  1. Shut off or disconnect gas furnace’s power and remove the gas pipe if necessary.
  2. Disconnect and remove a sufficient portion of the supply ductwork to provide clearance for the cased coil.
  3. Ensure that the coil is leveled well and seal the gap between the coil and the furnace. (If the coil and furnace sizes do not match, use the proper size of sheet metal or other material to fill the gap, then seal the gap to prevent air leakage.)
  4. Reconnect the power line on the gas furnace. Turn on the furnace to check for any sign of leakage.

MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (2) MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (3)

MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (4)

Transition for Horizontal Left Orientation
If the coil is used in connection with an upflow furnace in horizontal left orientation, a sheet metal transition can be installed between the furnace supply air outlet and the evaporator coil supply air inlet to create clearance between the coil lineset and the furnace flue outlet for A-cabinet non-condensing furnaces and for all cabinet size condensing furnaces.

For A-cabinet non-condensing furnaces, a 6″ transition is needed. For all cabinet size condensing furnaces, a 6.5″ transition is needed. If space is a constraint, the lines/flue interference can be removed by rotating the coil so the lineset is facing the opposite direction and air flows through the bottom of the A-coil, thus optimizing airflow.

 DRAIN APPLICATION

Condensate Drain Piping
Consult local codes for special requirements. To provide extra protection from water damage, it is always recommended to install an additional drain pan, provided by the installer, under the entire unit with a separate drain line. MRCOOL® will not be responsible for any damages due to the failure to follow these recommendations.

Plastic Drain Pan Installation

WARNING
Do not use the coil pan shipped with the unit on oil furnaces or any application where the temperature of the drain pan may exceed 275°F. A field-fabricated metal drain pan can also be used for these types of applications.
Failure to follow this warning may result in property damage and/or personal injury.

NOTE:
Use Teflon tape on the drain line connections. Do not use pipe joint compound or PVC/CPVC cement on the drain nipple.

  • The coil drain pan has a primary and an optional secondary drain pan with 3/4″ NPT female connections; use either PVC or copper pipe and hand-tighten to a torque of approximately 37 in-lbs. to prevent damage to the drain pan connection. An insertion depth between 0.355 to 0.485 inches (3-5 turns) should be expected at this torque setting.
  • Use male 3/4″ NPT threaded fitting for outside connection and make sure the drain holes are not blocked.
  • Insulation may be needed for the drain line to prevent sweating.
  • The drain pan has two drain connections on each side to provide flexibility of connection and drainage. Make sure the pan has a proper pitch and is plugged if the second connection is not used.
  • If the secondary drain line is required, run the line separately from the primary drain and terminate it where it can be easily seen.

NOTE: Water coming from this line means the coil’s primary drain is plugged and needs cleaning.

Install a trap in the drain line below the bottom of the drain pan. If using a copper drain line, solder a short piece of pipe to the connector before installing a drain fitting. DO NOT over-torque the 3/4″ copper connector to the plastic drain connection. Use a wet rag or heat-sink material on the short piece to protect the plastic drain pan, and complete the drain line installation. Use the figures below as a template for a typical drain pipe routing.
This figure shows how to avoid an interference with vent piping.

MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (5) MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (6) MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (7)

 Refrigerant Connections

CAUTION
When using the unit with an electrical heater, the switch is used only for the electrical heater on the front of the panel. To prevent a refrigerant leak, use proper tools to ensure a clean, burr-free cut.

CAUTION
TXV bulb MUST be protected (wrapped with wet cloth) or removed while brazing the tubing. Overheating of the sensing bulb will affect the functional characteristics and performance of the comfort coil.

Piston/TXV Installation

Use brazing shield when brazing close to the cabinet surface and wet rag to protect rubber grommet. Brazing alloy should be at least 5% silver content.

NOTE: A piston does come pre-installed. The piston must be removed before installing a TXV.

 Piston Installation

NOTE: A piston does come pre-installed. The piston must be removed before installing a TXV.

  1. Using a wrench to loosen the nut. Remove the nut and sealing flange.
  2. Check the piston sizes for each outdoor/coil combination in Table 6.1 and choose the correct orientation.
  3. If a different-sized piston is needed for your specific system combination, remove the pre-installed piston.
    NOTE: Avoid pulling the piston sleeve out when removing the pre-installed piston.
  4. Choose the correct size piston and insert it with the correct orientation.
  5. Replace the outer O-ring with the O-ring provided.
  6. Attach the connection pipe with the nut and hand-tighten, plus an additional 1/6th turn. IMPORTANT: Wrap the nut with a wet rag before brazing.MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (2) MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (3) MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (4)

This coil comes with a factory-installed piston metering device. See table 6.1 for factory-installed piston sizes. Some system combinations will require a different sized piston to be field-installed.

  • Use the piston size recommended by the outdoor unit, if available.
  • Reference table 6.2 if the outdoor unit does not list a piston size.
  • Additional R-410A pistons for most applications are shipped with the unit. Contact MRCOOL to order the appropriate piston if needed.

INSTALLATION

 Optional TXV Kit Installation
Reference the TXV kit literature for installation instructions.

  1. Use a wrench to loosen the nut and remove the sealing flange and sealing gasket.
  2. Take out the connecting pipe and braze it onto the refrigeration-out pipe.
  3. Install the sealing washers, TXV, and flange connection tube.
  4. Use a wrench to fasten the nut and connecting pipe (18±2N•m).
  5. Connect TXV equalizer pipe to the port on the connecting pipe.
  6. Attach bulbs on the connecting pipe using materials included with the TXV kit. MRCOOL-HCMP-Series-Multi- Position-Cased-Coils- (5)

A TXV may be required to achieve minimum efficiency ratings or for long refrigerant line set applications. Reference AHRI for system combination ratings.
Reference Table 6.2 to charge the system by superheat when using the piston.
Reference the outdoor unit installation guide to charge the system when using a TXV.

MCPM Piston/Orifice Sizes
Model 50 52 56 58 60 64 68 70 73 75 80 83 90
3036A X X X X* X
3036B X X X X* X
3036C X X X X* X
3642B X X X X X*
3642C X X X X*
3642D X X X X*
4248B X X X X X*
4248C X X X X*
4248D X X X*
4860C X X X X*
4860D X X X X*

WARNING
Failure to install the proper piston can lead to poor system performance and possible compressor damage.

CAUTION
When using the unit with an electrical heater, the switch is used only for the electrical heater on the front of the panel.

Outdoor Temp (°F) Indoor Temperature (°F) Dry Bulb/Wet Bulb
50 52 56 58 60 64
Superheat
115 23 16 7 5 5 5
110 24 17 9 5 5 5
105 26 19 11 5 5 5
100 27 21 13 7 5 5
95 29 23 16 9 5 5
90 30 25 18 12 5 5
85 35 26 20 14 8 5
80 34 28 22 17 11 5
75 35 30 24 19 13 6
70 37 32 26 21 16 10
65 38 34 29 24 19 13
60 40 36 31 27 22 17
55 41 37 33 29 25 21

Table 6.2

NOTE: The chart is based on 400CFM/Ton indoor airflow and 50% relative humidity. If indoor relative humidity is above 70% or below 20%, use indoor wet bulb temperature only.

AIRFLOW PERFORMANCE

Pressure Drop Characteristics for Cooling and Heat Pump Coils
Pressure Drop (inches of water)
Model 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4*
HCMP3036AFOA 307 485 618 729 823 911 991 1063
HCMP3036BFOA 327 527 682 810 925 1024 1122 1217
HCMP3036CFOA 360 585 748 893 925 1024 1122 1217
HCMP3642BFOA 401 600 773 916 1045 1160 1256 1357
HCMP3642CFOA 457 663 856 1019 1156 1277 1394 1502
HCMP3642DFOA 496 718 924 1102 1259 1398 1530 1651
HCMP4248BFOA 456 638 810 953 1077 1191 1284 1390
HCMP4248CFOA 505 726 932 1098 1244 1375 1494 1604
HCMP4248DFOA 533 857 1105 1319 1509 1675 1824 1956
HCMP4860CFOA 439 699 906 1071 1224 1362 1487 1589
HCMP4860DFOA 466 764 978 1157 1313 1466 1590 1695

Data based on wet coil with entering air at 80°F DB / 67°F WB without air filter. The maximum allowable pressure drop is 0.4 IWG.
The maximum CFM is the data at 0.4 IWG pressure.

NOTE: Water blow-off could occur in certain installation positions if the airflow setting exceeds the maximum values listed.

Maximum Airflow Setting (CFM)
Model Upflow Horizontal Left Downflow Horizontal Right
HCMP3036AFOA 1200 1050 1050 1200
HCMP3036BFOA 1250 1200 1050 1250
HCMP3036CFOA 1250 1200 1050 1250
HCMP3642BFOA 1575 1400 1400 1575
HCMP3642CFOA 1575 1400 1400 1575
HCMP3642DFOA 1575 1450 1450 1575
HCMP4248BFOA 1800 1800 1700 1500
HCMP4248CFOA 1800 1800 1700 1700
HCMP4248DFOA 1800 1800 1700 1700
HCMP4860CFOA 1850 1750 1750 1850
HCMP4860DFOA 2000 1850 1850 2000

PRODIRECT™ Series Multi-Position
Cased Coils
The design and specifications of this product and/or manual are subject to change without prior notice. Consult with the sales agency or manufacturer for details.

Documents / Resources

MRCOOL HCMP Series Multi Position Cased Coils [pdf] Owner's Manual
HCMP3036AFOA, HCMP3036BFOA, HCMP3036CFOA, HCMP3642BFOA, HCMP3642CFOA, HCMP3642DFOA, HCMP4248BFOA, HCMP4248CFOA, HCMP4248DFOA, HCMP4860CFOA, HCMP4860DFOA, HCMP Series Multi Position Cased Coils, HCMP Series, Multi Position Cased Coils, Position Cased Coils, Cased Coils

References

Leave a comment

Your email address will not be published. Required fields are marked *