MODINE PDP, BDP Power Vented Gas Fired Unit Heaters
Product Information
Specifications:
- Model: PDP and BDP
- Approval: California CEC and Massachusetts
- Application: Non-residential
- Unit Type: Power vented gas-fired unit heaters
Product Usage Instructions
Special Precautions:
The installation and maintenance instructions in this manual must be followed to provide safe, efficient, and trouble-free operation. Special care must be exercised regarding the following precautions:
- Danger: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
- Do not store gasoline or other flammable substances near the appliance.
- Avoid installing gas-fired units in areas with chlorinated, halogenated, or acidic vapors.
Before You Begin:
Before starting the installation process, consider the following:
- Inspect the unit upon arrival for any damage and report it immediately.
- Check the rating plate to ensure the power supply matches the installation requirements.
- Verify that the unit received matches the product ordered.
Unit Location:
Choose a suitable location for the unit based on the following guidelines:
- Ensure proper ventilation in the installation area.
- Avoid areas with potential exposure to corrosive substances.
- Follow all local and national codes for unit placement.
FAQ
What should I do if I smell gas?
If you detect a gas odor, follow these steps:
- Open windows to ventilate the area.
- Avoid lighting any appliances or switches.
- Do not use any electrical devices or phones.
- Extinguish any open flames.
- Contact your gas supplier immediately for further instructions. If unable to reach them, call the fire department.
Who should perform the installation and service of the unit?
All installation and service tasks must be carried out by a qualified installation and service agency to ensure safety and proper operation of the unit.
INSTALLATION
ower vented gas-fired unit heaters models PDP and BDP
All models approved for use in California by the CEC and in Massachusetts. Unit heater is certified for non-residential applications.
FOR YOUR SAFETY
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
WARNING
IMPORTANT
1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects, or other reproductive harm. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
2. Do not locate ANY gas-fired units in areas where chlorinated, halogenated, or acidic vapors are present in the atmosphere. These substances can cause premature heat exchanger failure due to corrosion, which can cause property damage, serious injury, or death.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS: 1. Open windows. 2. Do not try to light any appliance. 3. Do not touch any electrical switch; do not
use any phone in your building. 4. Extinguish any open flame. 5. Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions. If you can not reach your gas supplier, call your fire department.
THIS MANUAL IS THE PROPERTY OF THE OWNER. PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY result in a potential safety concern.
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
WARNING
1. Gas fired heating equipment must be vented – do not operate unvented.
2. A built-in power exhauster is provided – additional external power exhausters are not required or permitted.
3. If an existing heater is being replaced, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 (NFPA 54) or CSA B149.1 latest edition. Failure to follow these instructions can result in injury or death.
4. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of inner pipes.
5. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
6. Gas pressure to appliance controls must never exceed 14″ W.C. (1/2 psi).
7. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of dual rated units.
8. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
9. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
10. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
11. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than the rated voltage.
WARNING
12. When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacements parts list may be obtained by contacting the factory. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk.
CAUTION
1. All literature shipped with this unit should be kept for future use for servicing or service diagnostics. Do not discard any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any propeller unit heater.
4. Clearances to combustible materials are critical. Be sure to follow all listed requirements.
5. Heaters are designed for use in heating applications with ambient startup temperatures between -40°F and 90°F and ambient operating temperatures between 40°F and 90°F.
6. Do not install unit outdoors.
7. In garages or other sections of aircraft hangars such as offices and shops that communicate with areas used for servicing or storage, keep the bottom of the unit at least 7′ above the floor unless the unit is properly guarded to provide user protection from moving parts. In parking garages, the unit must be installed in accordance with the standard for parking structures ANSI/NFPA 88A – latest edition, and in repair garages the standard for repair garages NFPA 30A – latest edition (formerly NFPA 88B). In Canada, installation of heaters in airplane hangars must be in accordance with the requirements of the enforcing authority, and in public garages in accordance with the current CSA-B149 codes.
8. In aircraft hangars, keep the bottom of the unit at least 10′ from the highest surface of the wings or engine enclosure of the highest aircraft housed in the hangars and in accordance with the requirements of the enforcing authority and/or NFPA 409 – latest edition.
9. Installation of units in high humidity or salt water atmospheres will cause accelerated corrosion, resulting in a reduction of the normal life of the units.
10. Do not install units below 7′ measured from the bottom of the unit to the floor in commercial applications (unless unit is properly guarded to provide user protection from moving parts).
11. Be sure no obstructions block air intake and discharge of unit heaters.
12. The minimum distance from combustible material is based on the combustible material surface not exceeding 160°F. Clearance from the top of the unit may be required to be greater then the minimum specified if heat damage, other than fire, may occur to materials above the unit heater at the temperature described.
13. Allow 18″ of clearance at rear (or 12″ beyond end of motor at rear of unit, whichever is greater) and access side to provide ample air for proper operation of fan.
14. Installation must conform with local building codes or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition. In Canada installation must be in accordance with CSA-B149.1.
2
6-580.21
SPECIAL PRECAUTIONS / SI (METRIC) CONVERSION FACTORS
CAUTION
15. Purging of air from gas supply line should be performed as described in the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition. In Canada, installation must be in accordance with CSA-B149.1.
16. When leak testing the gas supply piping system, the appliance and its combination gas control must be isolated during any pressure testing in excess of 14″ W.C. (1/2 psi).
17. The unit should be isolated from the gas supply piping system by closing its field installed manual shut-off valve. This manual shut-off valve should be located within 6′ of the heater.
18. Turn off all gas before installing appliance. 19. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not less than 5% below the rated voltage. 20. Check the gas inlet pressure at the unit upstream of the combination gas control. The inlet pressure should be 6-7″ W.C. on natural gas or 11-14″ W.C. on propane. If inlet pressure is too high, install an additional pressure regulator upstream of the combination gas control. 21. Service or repair of this equipment must be performed by a qualified service agency. 22. Do not attempt to reuse any mechanical or electronic ignition controller which has been wet. Replace defective controller.
IMPORTANT
1. To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated, or acidic) are present in the atmosphere.
2. To prevent premature heat exchanger failure, the input to the appliance as indicated on the serial plate, must not exceed the rated input by more than 5%.
3. Start-up and adjustment procedures must be performed by a qualified service agency.
BEFORE YOU BEGIN
CAUTION
1. All literature shipped with this unit should be kept for future use for servicing or service diagnostics. Leave manual with the owner. Do not discard any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any propeller unit heater.
In the U.S., the installation of these units must comply with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition and other applicable local building codes. In Canada, the installation of these units must comply with local plumbing or waste water codes and other applicable codes and with the current code CSA-B149.1.
1. All installation and service of these units must be performed by a qualified installation and service agency only as defined in ANSI Z223.1 (NFPA 54) – latest edition or in Canada by a licensed gas fitter.
2. This unit is certified with the controls furnished. For replacements parts, please order according to the replacement parts list on serial plate. Always know your model and serial numbers. Modine reserves the right to substitute other authorized controls as replacements.
3. Unit is balanced for correct performance. Do not alter fan or operate motors at speeds below what is shown in this manual.
4. Information on controls is supplied separately.
5. The same burner is used for natural and propane gas.
SI (Metric) Conversion Factors
To Convert “W.C. °F BTU Btu/ft3 Btu/hr
CFH (ft3/hr) CFH (ft3/hr) CFM (ft3/min) CFM (ft3/min)
feet Gal/Hr. Gal/Hr. gallons Horsepower inches pound
psig psig
Multiply By 0.249
(°F-32) x 5/9 1.06 37.3
0.000293 0.000472 0.00000787
0.0283 0.000472
0.305 0.00379
3.79 3.79 746 25.4 0.454 6.89 27.7
To Obtain kPa °C kJ kJ/m3 kW
m3/min m3/s
m3/min m3/s m m3/hr l/hr l W mm kg kPa “W.C.
6-580.21
3
SI (METRIC) CONVERSION FACTORS / UNIT LOCATION
UNIT LOCATION
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
CAUTION
9. Do not install units in locations where gas ignition system is exposed to water spray, rain, or dripping water.
10. Do not install units below 7′, measured from the bottom of the unit to the floor, unless properly guarded to provide protection from moving parts.
Figure 4.1 – Combustible Material and Service Clearances
C
1. Clearances to combustible materials are critical. Be sure to follow all listed requirements.
2. Heaters are designed for use in heating applications with ambient startup temperatures between -40°F and 90°F and ambient operating temperatures between 40°F and 90°F.
3. Do not install unit outdoors. 4. In garages or other sections of aircraft hangars such
as offices and shops that communicate with areas used for servicing or storage, keep the bottom of the unit at least 7′ above the floor unless the unit is properly guarded. In parking garages, the unit must be installed in accordance with the standard for parking structures ANSI/NFPA 88A latest edition, and in repair garages the standard for repair garages NFPA 30A – latest edition (formerly NFPA 88B). In Canada, installation of heaters in airplane hangars must be in accordance with the requirements of the enforcing authority, and in public garages in accordance with the current CSA-B149 codes. 5. In aircraft hangars, keep the bottom of the unit at least 10′ from the highest surface of the wings or engine enclosure of the highest aircraft housed in the hangars and in accordance with the requirements of the enforcing authority and/or NFPA 409 latest edition. 6. Installation of units in high humidity or salt water atmospheres will cause accelerated corrosion resulting in a reduction of the normal life of the units.
To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acidic) are present in the atmosphere.
Location Recommendations 1. When locating the heater, consider general space and
heating requirements, availability of gas and electrical supply, and proximity to vent locations.
Combustion Air Requirements The National Fuel Gas Code defines an “unconfined space” as a space whose volume is greater than 50 cubic feet per 1,000 Btu/Hr input of the installed appliance(s). A confined space is 50 cubic feet or less per 1,000 Btu/Hr input of the installed appliance(s).
2. Avoid installing units in extremely drafty locations. Drafts can cause burner flames to impinge on heat exchangers which shortens life. Maintain separation between units so discharge from one unit will not be directed into the inlet of another.
3. Be sure the structural support at the unit location site is adequate to support the unit’s weight. For proper operation the unit must be installed in a level horizontal position.
4. Do not install units in locations where the flue products can be drawn into the adjacent building openings such as windows, fresh air intakes, etc.
5. Be sure that the minimum clearances to combustible materials and recommended service clearances are maintained. Units are designed for installation on noncombustible surfaces with the minimum clearances shown in Figure 4.1 and Tables 4.1 and 4.2.
6. Units exposed to inlet air temperatures of 40°F or less, may experience condensation, therefore, provisions should be made for disposal of condensate.
7. When locating units, it is important to consider that the exhaust vent piping must be connected to the outside atmosphere.
8. Maximum equivalent vent lengths are listed in “Section A General Instruction – All Units” of the Venting Instructions.
Units installed in tightly sealed buildings or confined spaces must be provided with two permanent openings, one near the top of the confined space and one near the bottom. Each opening should have a free area of not less than one square inch per 1,000 BTU per hour of the total input rating off all units in the enclosure, freely communicating with interior areas having, in turn adequate infiltration from the outside.
For further details on supplying combustion air to a confined (tightly sealed) space or unconfined space, see the National Fuel Gas Code ANSI Z223.1 (NFPA 54) or CSA-B149.1 Installation Code – latest edition.
Sound and Vibration Levels All standard mechanical equipment generates some sound and vibration that may require attenuation. Libraries, private offices and hospital facilities will require more attenuation, and in such cases, an acoustical consultant may be retained to assist in the application. Locating the equipment away from the critical area is desirable within ducting limitations. Generally, a unit should be located within 15′ of a primary support beam. Smaller deflections typically result in reduced vibration and noise transmission.
4
6-580.21
INSTALLATION
UNIT MOUNTING
1. Be sure the means of suspension is adequate to support the weight of the unit (see pages 25 and 26 for unit weights).
2. For proper operation and to assure that flames are directed into the center of the heat exchanger tubes, the unit must be installed in a level horizontal position. Use a spirit level to ensure that the unit is suspended correctly.
3. Clearances to combustibles as specified in Figure 4.1 and Tables 4.1 and 4.2 must be strictly maintained.
4. All standard units are shipped fully boxed. Larger units are also supplied with skid supports on the bottom of the box. The larger units may be lifted from the bottom by means of a fork lift or other lifting device only if the shipping support skids are left in place and the forks support the whole depth of the unit. If the unit must be lifted from the bottom for final installation without the carton in place, be sure to properly support the unit over its entire length and width to prevent damage. When lifting units, make sure the load is balanced.
5. Propeller models up to size 350 have 2 mounting holes, size 350 and above have 4 mounting holes and blower models up to size 350 have 4 mounting holes, size 350 and above have 6 mounting holes. Units with two point suspension incorporate a level hanging feature. Depending on what options and accessories are being used, the heater may not hang level as recieved from the factory. Do not hang heaters with deflector hoods until referring to the “Installation Manual for Deflector Hoods” and making the recommended preliminary adjustments on the heater, while the heater is resting on the floor. The units can be mounted with 3/8″-16 threaded rod as follows:
· On each piece of threaded rod used, screw a nut a distance of about 1″ onto the end of the threaded rods that will be screwed into the unit heater.
· Place a washer over the end of the threaded rod and screw the threaded rod into the unit heater weld nuts on the top of the heater at least 5 turns, and no more than 10 turns. Tighten the nut first installed onto the threaded rod to prevent the rod from turning.
· Drill holes into a steel channel or angle iron at the same center-line dimensions as the heater that is being installed. The steel channels or angle iron pieces need to span and be fastened to appropriate structural members.
· Cut the threaded rods to the preferred length, place them through the holes in the steel channel or angle iron and secure with washers and lock nuts or lock washers and nuts. A double nut arrangement can be used here instead of at the unit heater (a double nut can be used both places but is not necessary).
· Do not install standard unit heaters above the maximum mounting height shown in Table 20.1.
NOTE: A pipe hanger adapter kit, shown in Figure 5.2, is available as an accessory. One kit consists of drilled 3/4″ IPS pipe caps and 3/8″ – 16 x 1-3/4″ capscrews to facilitate threaded pipe suspension.
Figure 5.1 – Adjustable Mounting Brackets – To Adjust:
1. Remove outer side panels. 2. “Set screws” – loosen and
position bracket where needed then tighten set screws. 3. Re-attach outer side panels.
Figure 5.2 – Suspension Methods
(Suspension with Pipe Adapter Kit)
6-580.21
5
INSTALLATION – VENTING
WARNING
1. Gas fired heating equipment must be vented – do not operate unvented.
2. A built-in power exhauster is provided – additional external power exhausters are not required or permitted.
3. If an existing heater is being replaced, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 (NFPA 54) or CSA B149.1 – latest edition. Failure to follow these instructions can result in serious injury or death.
4. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of inner pipes.
CAUTION
Installation must conform with local building codes or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition. In Canada installation must be in accordance with CSA B149.1.
Model PDP and BDP unit heaters must be vented with the proper passageway as described in these instructions to convey flue gases from the unit or the vent connector to the outside atmosphere.
The venting instructions are organized in sections, based on installation type. The sections are identified as follows:
Instructions
Applicable Installation Instructions by Vent System Type
A
General Instructions for ALL Installations
B
VERTICAL CATEGORY I vent systems j
C
HORIZONTAL CATEGORY III vent systems k
The differences between vertical and horizontal vent systems will be identified in “Section A – General Instructions – All Units”.
Section A – General Instructions – All Units
A1. If the unit heater being installed is replacing existing equipment and using the existing vent system from that equipment, inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) or CSA B149.1 Installation Code latest edition and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
A2. The vent pipe should be galvanized steel or other suitable corrosion resistant material. Follow the National Fuel Gas Code for minimum thickness of vent material. The minimum thickness for connectors varies depending on the pipe diameter. Do not vent unit with PVC or other forms of plastic venting material.
A3. All heaters come with a vent adapter for attaching the vent pipe to the heater (see Table 6.1). Attach the vent pipe to the adapter with 3 corrosion resistant screws. (Drill pilot holes through the vent pipe and adapter prior to screwing in place). Vent pipe must not be smaller than the connector size.
A4. Limit the total equivalent vent pipe length to fall between the minimum and maximum equivalent vent lengths given
in Table 6.1, making the vent system as straight as possible. The equivalent length of a 5″ elbow is 6′ and for a 6″ elbow is 7′.
A5. A minimum of 12″ straight pipe is recommended from the flue outlet before turns in the vent pipe.
A6. Horizontal sections of vent pipe are to be installed with an upward or downward slope from the appliance of 1/4″ per foot and suspended securely from overhead structures at points not greater than 3′ apart.
A7. Fasten individual lengths of vent together with at least 3 corrosion resistant sheet metal screws.
A8. Keep single wall vent pipe at least 6″ from combustible materials. For double wall vent pipe, follow the vent pipe manufacturer’s clearances to combustibles. The minimum distance from combustible materials is based on the combustible material surface not exceeding 160°F. Clearance from the vent pipe (or the top of the unit) may be required to be greater than 6″ if heat damage other than fire could result (such as material distortion or discoloration).
A9. Avoid venting through unheated space when possible. When venting does pass through an unheated space or if the unit is installed in an environment that promotes condensation, insulate runs greater than 5′ to minimize condensation. Inspect for leakage prior to insulating and use insulation that is noncombustible with a rating of not less than 400°F. Install a tee fitting at the low point of the vent system and provide a drip leg with a clean out cap as shown in Figure 9.1.
Table 6.1 – Vent Pipe Diameters, Transitions, and Total Equivalent Vent Pipe Lengths for Horizontal Vent Systems
Model Vent Transition Vent Pipe
Size
Included Diameter
150, 175
4″ to 5″
5″
200
6″ to 5″
5″
250-400 Not required
6″
Minimum Eqv Length
2′ 2′ 2′
Maximum Eqv Length
60′ 60′ 70′
Figure 6.1 – Venting Through Combustible Roof or Wall
Single Wall Vent Pipe
Double Wall Vent Pipe
Specified Terminal
Specified Terminal
Flashing
Flashing
Listed Thimble
Clearance Specified by Type B Vent Mfg.
Single Wall
Single Wall Vent Pipe Terminating with Double wall vent pipe.
Double Wall
Specified Terminal
Clearance Specified by Type B Vent Mfg.
Single Wall Vent Pipe
Single Wall
Specified Terminal
Listed Thimble
See Instruction A12 for attaching single wall pipe to double wall pipe.
6
6-580.21
INSTALLATION – VENTING
A10. When the vent passes through a combustible INTERIOR wall or floor, a metal thimble 4″ greater than the vent diameter is necessary. If there is 6′ or more of vent pipe in the open space between the appliance and where the vent pipe passes through the wall or floor, the thimble need only be 2″ greater than the diameter of the vent pipe. If a thimble is not used, all combustible material must be cut away to provide 6″ of clearance. Where authorities have jurisdiction, Type B vent may be used for the last section of vent pipe to maintain clearance to combustibles while passing through wall or floor. See Figure 6.1. Any material used to close the opening must be noncombustible.
A11. Seal all seams and joints of un-gasketed single wall pipe with metal tape or Silastic suitable for temperatures up to 400°F. Wrap the tape 2 full turns around the vent pipe. One continuous section of double wall vent pipe may be used within the vent system to pass through the wall to the listed vent cap. Refer to instruction A12 in “Section A General Instructions All Units” for attaching double wall pipe to single wall pipe.
A12. The following are general instructions for double wall (Type B) terminal pipe installation.
How to attach a single wall vent terminal to double wall (Type B) vent pipe:
1. Look for the “flow” arrow on the vent pipe.
2. Slide the vent terminal inside the exhaust end of the double wall vent pipe.
3. Drill 3 holes through the pipe and the vent terminal. Using 3/4″ long sheet metal screws, attach the cap to the pipe. Do not over tighten.
How to connect a single wall vent system to a double wall (Type B) vent pipe:
1. Slide the single wall pipe inside the inner wall of the double wall pipe.
2. Drill 3 holes through both walls of the single and double wall vent pipes. Using 3/4″ sheet metal screws, attach the 2 pieces of pipe. Do not over tighten.
3. The gap between the single and double wall pipe must be sealed but it is not necessary to fill the full volume of the annular area. To seal, run a large bead of 400°F silastic around the gap.
A13. Vent termination clearances must be maintained:
Table 7.1 – Vent Termination Clearances
Vent Shall Terminate:
Structure
3 feet above
Forced air inlet within 10′ (US)
6 feet in all directions
Forced air inlet (Canada)
3 feet in all directions
Combustion Air inlet of another appliance
4 feet below, 4 feet horizontal, or 1 foot above
Door window, gravity air inlet, or any building opening (US)
3 feet in all directions
Door window, gravity air inlet, or any building opening (Canada)
Reference Standard NFPA 54 CSA B149.1 CSA B149.1
NFPA 54
CSA B149.1
3 feet horizontal
Electric meter, gas meter, gas regulator, and relief equipment
CSA B149.1
2 feet in all directions
Adjacent building, adjoining building, or parapet wall
Modine
7 feet in all directions
Adjacent public walkways
NFPA 54/CSA B149.1
1 foot above
Grade (ground level)
NFPA 54/CSA B149.1
1 foot below or 1 foot beyond Eave with 24″ overhang or less
Modine
3 feet below or 1 foot beyond Eave with greater than 24″ overhang
Modine
j Do not terminate the vent directly above a gas meter or regulator. Recommendations based on CSA B149.1 and NFPA 54. Venting must conform with applicable current revision of local and national installation codes.
6-580.21
7
INSTALLATION – VENTING
A14. Do NOT vent this appliance into a masonry chimney.
A15. Do NOT use dampers or other devices in the vent or combustion air pipes.
A16. The venting system must be exclusive to a single appliance and no other appliance is allowed to be vented into it.
A17. Precautions must be taken to prevent degradation of building materials by flue products.
A18. Single wall vent pipe must not pass through any unoccupied attic, inside wall, concealed space, or floor.
A19. Uninsulated single wall vent pipe must not be used outdoors for venting appliances in regions where the 99% winter design temperature is below 32°F.
A20. The vent terminal must be:
Table 8.1 – Vent Terminals
Model Size 150-200 250-400
Modine PN 5H0722850004 5H0722850002
A21. If left hand (facing front of heater with air blowing in face) power exhauster discharge is desired, the power exhauster may be rotated 180°. To do this, remove the screws in the vent collar, rotate the power exhauster, then replace the screws.
A22. In addition to following these general instructions, specific instructions for Vertical Category I or Horizontal Category III vent systems must also be followed. The following outlines the differences:
Table 8.2 – ANSI Unit Heater Venting Requirements
Category
Description
Venting Requirements
I
Negative vent pressure Non-condensing
Follow standard venting requirements.
II
Negative vent pressure Condensing
Condensate must be drained.
III
Positive vent pressure Non-condensing
Vent must be gas tight.
IV
Positive vent pressure Condensing
Vent must be liquid and gas tight. Condensate must be drained.
Note: Vent connectors serving Category I appliances shall not be connected into any portion of mechanical draft systems operating under positive pressure.
Vertical Category I Vent
· Vertical vent systems terminate vertically (up) (an example is shown in Figure 9.1).
· The horizontal portion of the vent run cannot exceed 75% of the vertical rise (Example: If the vent height is 10′, the horizontal portion of the vent system cannot exceed 7.5′).
· The vent terminates a minimum of 5′ above the vent connector on the unit.
· If the vent system to be installed meets ALL these criteria (an example is shown in Figure 9.1), proceed to “Section B – Vertical Vent System Installation”. For all other cases, proceed to the next section for Horizontal Category III Vent System Determination:
Horizontal Category III Vent
· Horizontal vent systems terminate horizontally (sideways) (an example is shown in Figure 10.2).
· A vent system that terminates vertically but has a horizontal run that exceeds 75% of the vertical rise is considered horizontal.
· Horizontal vent configurations are Category III. Additional requirements are covered in “Section C – Horizontal Category III Vent System Installation”.
8
6-580.21
INSTALLATION – VENTING
Section B Vertical Vent System Installation
B1. This section applies to vertically vented Category I vent systems and is in addition to “Section A General Instructions All Units”.
B2. Vertical vent systems terminate vertically and must be sized in accordance with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition.
B3. The horizontal portion of the vent run cannot exceed 75% of the vertical rise (Example: If the vent height is 10′, the horizontal portion of the vent system cannot exceed 7.5′).
B4. It is recommended to install a tee with drip leg and clean out cap as shown in Figure 9.1.
B5. The vent terminates a minimum of 5′ above the vent connector on the unit.
B6. All vertically vented heaters that are Category I must be connected to a vent complying with a recognized standard, with a material acceptable to the authority having jurisdiction. Venting into a masonry chimney is not permitted. Refer to the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition for instructions on common venting.
B7. Use a listed vent terminal to reduce down drafts and moisture in the vent.
B8. Double wall vent pipe is recommended, although single wall can be used if the requirements of the National Fuel Gas Code are followed.
B9. Vertical vents must terminate a minimum horizontal and vertical distance from roof lines and adjacent walls or obstructions. These minimum distances are outlined as follows (based on National Fuel Gas Code requirements for vents with diameters less than 12″):
· For double wall vent pipe and 8′ or greater horizontal distance to any vertical wall or similar obstruction, the vent must terminate above the roof in accordance with Figure 9.1 and Table 9.1.
· For double wall vent pipe and less than 8′ horizontal distance to any vertical wall or similar obstruction, the vent must terminate at least 2′ above the highest point where it passes through a roof of a building and at least 2′ higher than any portion of a building within a horizontal distance of 10′ (see Figure 9.1).
Table 9.1 – Minimum Height from Roof to Lowest Discharge Opening
Rise X (in)
Roof Pitch
0-6
Flat to 6/12
6-7
6/12 to 7/12
7-8
7/12 to 8/12
8-9
8/12 to 9/12
9-10
9/12 to 10/12
10-11
10/12 to 11/12
11-12
11/12 to 12/12
12-14
12/12 to 14/12
14-16
14/12 to 16/12
16-18
16/12 to 18/12
18-20
18/12 to 20/12
20-21
20/12 to 21/12
j Size according to expected snow depth.
Min Height H (ft) j 1.00 1.25 1.50 2.00 2.50 3.25 4.00 5.00 6.00 7.00 7.50 8.00
· For single wall vent pipe and 10′ or greater horizontal distance to any portion of a building, the vent must terminate at least 2′ above the highest point where it passes through a roof of a building and at least 2′ higher than any portion of a building within a horizontal distance of 10′.
· For single wall vent pipe and less than 10′ horizontal distance to any portion of a building, the vent must terminate at least 2′ higher than any portion of that building.
Figure 9.1 – Vertical Category I Vent System
LISTED TERMINAL
X
ROOF PITCH IS: X / 12 12
USE LISTED THIMBLE THROUGH ROOF AND CEILING
“H” MIN* ROOF FLASHING
BACK VIEW
4″ MIN
EXHAUST
12″ MIN RECOMMENDED
TEE WITH DRIP LEG AND CLEANOUT CAP
(SLOPE 1/4″ PER FOOT DOWNWARD TOWARD DRIP LEG)
6-580.21
9
INSTALLATION – VENTING
Section C Horizontal, Category III Vent System
Installation
C1. This section applies to horizontally vented Category III vent systems and is in addition to “Section A General Instructions All Units”.
C2. Horizontal vent systems terminate horizontally (sideways).
C3. Seal all seams and joints of un-gasketed single wall pipe with metal tape or Silastic suitable for temperatures up to 400°F. Wrap the tape 2 full turns around the vent pipe. For single wall vent systems, 1 continuous section of double wall vent pipe may be used within the vent system to pass through the wall to the listed vent cap. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of inner pipes. Category III vent systems listed by a nationally recognized agency and matching the diameters specified may be used. Different brands of vent pipe materials may not be intermixed. Refer to instruction A10 in “Section A General Instructions All Units” for attaching double wall pipe to single wall pipe.
C4. Refer to Table 6.1 for total minimum and maximum vent lengths, making the system as straight as possible. The equivalent length of a 90° elbow is 6′ for 5″ diameter and 7′ for 6″ diameter.
C5. All horizontal Category III vents must be terminated with a listed vent cap. The cap must terminate a minimum distance beyond the exterior wall surface as shown in Figure 10.2 and Table 10.1. The vent must be supported as shown in Figure 10.1. Precautions must be taken to prevent degradation of building materials by flue products.
Table 10.1 – Dimension Between Vent Cap and Exterior Wall
Vent Terminal Selkirk, Starkap, or Constant Air-Flo 2433
Modine 5H072285 Tjernlund VH1
“A” Min. 12″ 6″ 0″
Figure 10.2 – Horizontal Venting
with a drip leg and clean out near the exit of the vent as shown in Figure 9.2, or allow the condensate to drip out the end.
C9. For a vent termination located under an eave, the distance of the overhang must not exceed 24″. The clearance to combustibles above the exterior vent must be maintained at a minimum of 12″. Consult the National Fuel Gas Code for additional requirements for eaves that have ventilation openings.
C10. Once venting is complete, proceed to the section titled “Installation Gas Connections”.
Figure 10.1 – Exhaust Vent Construction Through Combustible Walls and Support Bracket
C6. When condensation may be a problem, the vent system shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief openings, or other equipment.
C7. The venting system must be exclusive to a single unit, and no other unit is allowed to be vented into it.
C8. When vented horizontally, maintain a 1/4″ per foot rise away from the heater and place a drip leg with clean out near the unit as shown in Figure 10.2. Where local authorities have jurisdiction, a 1/4″ per foot downward slope is acceptable
10
6-580.21
INSTALLATION
GAS CONNECTIONS
WARNING
1. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
2. Gas pressure to appliance controls must never exceed 14″ W.C. (1/2 psi).
3. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of dual rated units.
Figure 11.1 – Recommended Sediment Trap/Manual Shut-off Valve Installation for Gas Connection
j
CAUTION
1. Purging of air from gas lines should be performed as described in the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition or in Canada CSA-B149 codes.
2. When leak testing the gas supply piping system, the appliance and its combination gas control must be isolated during any pressure testing in excess of 14″ W.C. (1/2 psi).
3. The unit should be isolated from the gas supply piping system by closing its field installed manual shut-off valve. This manual shut-off valve should be located within 6′ of the heater.
4. Turn off all gas before installing appliance.
IMPORTANT
To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%.
1. Installation of piping must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – Latest Edition. In Canada, installation must be in accordance with CSA-B149.1.
2. Piping to units should conform with local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Refer to Table 11.1 to determine the cubic feet per hour (cfh) for the type of gas and size of unit to be installed. Using this cfh value and the length of pipe necessary, determine the pipe diameter from Table 11.2. Where several units are served by the same main, the total capacity, cfh and length of main must be considered. Avoid pipe sizes smaller than 1/2″. Table 11.1 allows for a 0.3″ W.C. pressure drop in the supply pressure from the building main to the unit. The inlet pressure to the unit must be 6-7″ W.C. for natural gas and 11-14″ W.C. for propane gas. When sizing the inlet gas pipe diameter, make sure that the unit supply pressure can be met after the 0.3″ W.C. has been subtracted. If the 0.3″ W.C. pressure drop is too high, refer to the Gas Engineer’s Handbook for other gas pipe capacities.
3. Install a ground joint union with brass seat and a manual shut-off valve adjacent to the unit for emergency shut-off and easy servicing of controls, including a 1/8″ NPT plugged tapping accessible for test gauge connection (see Figure 11.1).
4. Use 2 wrenches when connecting field piping to units. 5. Provide a sediment trap before each unit and in the line
where low spots cannot be avoided (see Figure 11.1). 6. When pressure/leak testing, pressures above 14″ W.C.
(1/2 psi), close the field installed shut-off valve, disconnect the appliance and its combination gas control from the gas supply line, and plug the supply line before testing. When testing pressures 14″ W.C. (1/2 psi) or below, close the manual shut-off valve on the appliance before testing.
j Manual shut-off valve is in the “OFF” position when handle is perpendicular to pipe.
Table 11.1 – Sea Level Manifold Pressure & Gas Consumption j
Model Size 150 175 200 250 300 350 400
Manifold Pressure (“W.C.)
CFH Gal/Hr. Propane Orifice Drill Size
CFH Gal/Hr. Propane Orifice Drill Size
CFH Gal/Hr. Propane Orifice Drill Size
CFH Gal/Hr. Propane Orifice Drill Size
CFH Gal/Hr. Propane Orifice Drill Size
CFH Gal/Hr. Propane Orifice Drill Size
CFH Gal/Hr. Propane Orifice Drill Size
Natural
3.5
138.1 21
166.7 28
190.5 25
238.1 18
285.7 21
333.3 23
381.0 25
Propane
10
58.0 1.64 39 70.0 1.86 43 80.0 2.19 42 100.0 2.74 36 120.0 3.29 39 140.0 3.84 41 160.0 4.38 42
# of Orifices
2 3 3 3 4 5 6
Table 11.2 – Gas Pipe Capacities – Natural Gas jk
Pipe
Length (ft) 1/2″
3/4″
Natural Gas
1″
1-1/4″ 1-1/2″
2″
10
132
278
520 1050 1600 3050
20
92
190
350
730 1100 2100
30
73
152
285
590
890 1650
40
63
130
245
500
760 1450
50
56
115
215
440
670 1270
60
50
105
195
400
610 1150
70
46
96
180
370
560 1050
80
43
90
170
350
530
930
100
38
79
150
305
460
870
125
34
72
130
275
410
780
150
31
64
120
250
380
710
j Capacities in cubic feet per hour through Schedule 40 pipe with maximum 0.3″ W.C. pressure drop with up to 14″ W.C. gas pressure. Specific gravity is 0.60 for natural gas and 1.50 for propane gas.
k For pipe capacity with propane gas, divide natural gas capacity by 1.6. Example: What is the propane gas pipe capacity for 60′ of 1-1/4″ pipe? The natural gas capacity is 400 CFH. Divide by 1.6 to get 250 CFH for propane gas.
6-580.21
11
INSTALLATION – HIGH ALTITUDE ACCESSORY KIT
HIGH ALTITUDE ACCESSORY KIT
Modine’s gas-fired equipment standard input ratings are certified by ETL. For elevations above 2,000′, ANSI Z223.1 requires ratings be reduced 4 percent for each 1000′ above sea level. For units in Canada, CSA requires that ratings be reduced 10 percent at elevations above 2,000′. The high altitude adjustment instructions and pressure switch kits listed in this manual are for use with units that will be installed over 2,000′ These methods and kits comply with both ANSI Z223.1 and CSA requirements.
If a unit is to be installed at higher elevations AND converted from natural gas to propane gas operation, a propane conversion kit must be used in conjunction with the pressure adjustment methods and pressure switch kits listed herein. For the Selection and Installation Instructions for propane conversion kits, please see the latest revision of Modine Manual 75-511.
Selection of the Proper Pressure and Kit
To determine the proper manifold pressure at altitude and if required, the proper combustion air pressure switch kit, the full model number of the heater, the fuel to be used, and the altitude the unit will be installed at must be known. Refer to the unit serial plate or carton label to obtain the necessary information about the unit.
After obtaining this information, refer to the gas pressure and selection charts shown in Tables 12.1 through 13.1. The pressure charts are differentiated by elevation, fuel type, and country the product is being installed in. The selection charts are differentiated by product type, altitude and fuel type. If converting from natural gas to propane gas and operation at high altitude, both a propane conversion kit and a pressure switch kit must be used (if applicable). Selection
charts include the proper kit suffix, when required.
Manifold Pressure Adjustment
The inlet pressure to the unit must be confirmed to be within acceptable limits (6-7″ W.C. for natural gas and 11-14″ W.C. for propane gas) before opening the shutoff valve or the combination gas valve may be damaged.
Heaters for use with natural gas have gas valves that need to be feild set at 3.5″ W.C. manifold pressure at 7.0″ W.C. inlet pressure.
Units for use with propane gas need to be feild set for 10.0″ W.C. manifold pressure at 14.0″ W.C. inlet pressure.
Installation above 2,000′. elevation requires adjustment of the manifold pressure as described.
Derated BTU Content Gas and Manifold Pressure Calculation
Some utility companies may derate the BTU content (heating value) of the gas provided at altitude to a value other than 1,050 BTU/ft3 for natural gas or 2,500 BTU/ft3 for propane gas to allow certain heating appliances to be used with no manifold pressure adjustments. For this reason it is necessary that the supplying utility be contacted for detailed information about the gas type and BTU content (heating value) before operating any heater. Tables 12.1 and 12.2 show the standard derated heating values (4% per 1,000′ of elevation in the USA and 10% between 2,001′ and 4,500′ elevation in Canada) of natural and propane gases at various altitudes. If the utility is supplying gas with heating values as shown in Tables 12.1 and 12.2, the manifold pressure should be set to 3.5″ W.C for natural gas and 10.0″ W.C. for propane gas.
NOTE: Only the high fire gas pressure need be adjusted, low fire gas pressure should remain the same.
Table 12.1 – Natural Gas Heating Values at Altitude j l m
Table 12.2 – Propane Gas Heating Values at Altitude k l m
Altitude (ft)
Gas Heating Values at Altitude (BTU/ft3)
USA
Canada
Altitude (ft)
Gas Heating Values at Altitude (BTU/ft3)
USA
Canada
0-2,000
1,050
1,050
0-2,000
2,500
2,500
2,001-3,000
929
2,001-3,000
2,212
3,001-4,000
892
945
3,001-4,000
2,123
2,250
4,001-4,500
874
4,001-4,500
2,080
4,501-5,000
856
856
4,501-5,000
2,038
2,038
5,001-6,000
822
822
5,001-6,000
1,957
1,957
6,001-7,000
789
789
6,001-7,000
1,879
1,879
7,001-8,000
757
757
7,001-8,000
1,803
1,803
8,001-9,000
727
727
8,001-9,000
1,731
1,731
9,001-10,000
698
698
9,001-10,000
1,662
1,662
10,001-11,000
670
670
10,001-11,000
1,596
1,596
11,001-12,000
643
643
11,001-12,000
1,532
1,532
12,001-13,000
618
618
12,001-13,000
1,471
1,471
13,001-14,000
593
593
13,001-14,000
1,412
1,412
j Values shown are for 3.5″ W.C. manifold pressure, for other BTU content values (available from local utility) use Equation 13.1 to calculate manifold pressure. k Values shown are for 10.0″ W.C. manifold pressure, for other BTU content values (available from local utility) use Equation 13.1 to calculate manifold pressure. l When installed at altitudes above 2,000′, a pressure switch may need to be changed. Refer to Table 13.1 to determine if a switch change is required. m Gas heating values are derated 4% per 1,000′ of elevation in the USA and 10% between 2,000′ and 4,500′ elevation in Canada in accordance with ANSI Z223.1
and CSA-B149, respectively.
12
6-580.21
INSTALLATION – HIGH ALTITUDE ACCESSORY KIT
If the heating value of the gas being supplied is different than the values shown in Tables 12.1 and 12.2, use the following equation to determine the appropriate manifold pressure for the altitude and gas heating value being supplied.
Equation 13.1 – Manifold Pressure for Derated Gas
WHERE:
MPACT = BTUTBL = BTUACT =
Manifold Pressure (in. W.C.) at Altitude Manifold pressure setting for the heater being installed
BTU/ft3 Content of Gas Obtained from Tables 12.1 or 12.2 (whichever is applicable)
BTU/ft3 Content of Gas Obtained from the local utility company
Table 13.1 – High Altitude Kits for PDP/BDP j
US and Canada Altitude (ft)
0-2,000
150
Item Code not required
175
Item Code not required
Model Size
200
Item Code not required
250
Item Code not required
300
Item Code not required
350
Item Code not required
400
Item Code not required
2,001-7,500 67248 67248 67248 67248 67248 67248 67248
7,501-8,500 68408 55941 67248 55942 67248 68406 68407
8,501-9,500 68408 55941 67248 55942 67248 68406 68407
9,501-10,000 68408 55941 67248 55942 68408 68406 68407
10,001-11,000 55948 55941 67248 77785 68408 68406 68407
11,001-12,000 55948 55941 67248 77785 68408 68406 55941
12,001-13,000 55948 55941 67248 77785 68408 68406 55941
13,001-14,000 55948 55941 55941 77785 68408 68406 55941
j For Label Only (67248) kits, Modine part number 5H0807146005 is required to be filled out and attached to the unit by the installer. Please contact the local Modine representative at 1.800.828.4328 (HEAT).
MPSL
= Manifold Pressure (in. W.C.), at Sea Level Use 3.5″ W.C. for natural gas and 10.0″ W.C. for propane gas
NOTE: Only the primary manifold pressure should be adjusted on units equipped with 2-stage or modulating gas controls. No adjustments to the low fire manifold pressure are necessary on these units.
6-580.21
13
INSTALLATION
ELECTRICAL CONNECTIONS
WARNING
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than rated voltage.
CAUTION
Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.
1. Installation of wiring must conform with local building codes, or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 – Latest Edition. Unit must be electrically grounded in conformance to this code. In Canada, wiring must comply with CSA C22.1, Part 1, Electrical Code.
2. Two copies of the unit wiring diagram are provided with each unit. One is located in the electrical junction box and the other is suppled in the literature packet. Refer to this diagram for all wiring connections.
3. Make sure all multi-voltage components (motors, transformers, etc.) are wired in accordance with the power supply voltage.
4. The power supply to the unit must be protected with a fused or circuit breaker switch.
5. The power supply must be within 10 percent of the voltage rating and each phase must be balanced within 2 percent of each other. If not, advise the utility company.
6. External electrical service connections that must be installed include:
a. Supply power connection (120, 208, 240, 480, or 575 volts).
b. Thermostats, summer/winter switches, or other accessory control devices that may be supplied (24 volts).
NOTE: Certain units will require the use of a field step-down transformer. Refer to the serial plate to determine the unit supply voltage required.
7. Refer to Figure 19.1 for the electrical junction box locations.
8. All supply power electrical connections are made in the electrical junction box of the unit. The low voltage (thermostat and accessory control devices) can be wired to the terminals on the electrical junction box. Refer to the wiring diagram for the terminal location of all low voltage wiring.
DUCT INSTALLATION
IMPORTANT
Do not attempt to attach ductwork of any kind to propeller models.
When installing the heater, always follow good duct design practices for even distribution of the air across the heat exchanger. Recommended layouts are shown in Figure 14.1. When installing blower units with ductwork the following must be done.
1. Provide uniform air distribution over the heat exchanger. Use turning vanes where required (see Figure 14.1).
2. Provide removable access panels in the ductwork on the downstream side of the unit heater. These openings should be large enough to view smoke or reflect light inside the casing to indicate leaks in the heat exchanger and to check for hot spots on exchanger due to poor air distribution or lack of sufficient air.
3. If ductwork is connected to the rear of the unit use a Modine blower enclosure kit or if using a field designed enclosure maintain dimensions of the blower enclosure as shown on page 26.
Figure 14.1 – Recommended Ductwork Installations
TURNING VANES 3″ MIN.
3″ MAX.
A
B
12″ MIN.
SIDE VIEW
3″ MAX. B
3″ MIN. 12″
12″ MIN.
A TURNING
VANES
BAFFLE
SIDE VIEW
B
A
12” B MIN.
BAFFLE
TURNING VANES
A
SIDE VIEW
BAFFLE
TOP VIEW
Dimension “B” Should Never Be Less than 1/2 of “A”
Additional Requirements for Blower Model BDP
Determining Blower Speed The drive assembly and motor on all blower units are factory assembled and adjusted for operation under average conditions of air flow and without any external static pressure. The motor sheave should be adjusted as required when the unit is to be operated at other than average air flows and/or with external static pressures. Adjustment must always be within the performance range shown on page 20 and the temperature rise range shown on the unit’s rating plate.
To determine the proper blower speed and motor sheave turns open, the operating conditions must be known. For example, a model BDP350 unit, operating with no external static pressure, (e.g. no ductwork, nozzles, etc.) is to deliver an air volume of 6481 cfm (cfm = cubic feet per minute). This requires the unit be supplied with a 5 hp motor, a -207 drive, and the drive sheave set at 2.5 turns open to achieve a blower speed of 960
14
6-580.21
INSTALLATION
rpm (see performance table for units with or without blower enclosure, page 21). See “Blower Adjustments” for setting of drive pulley turns open.
If a blower unit is to be used with ductwork or nozzles, etc., the total external static pressure under which the unit is to operate, and the required air flow must be known before the unit can be properly adjusted. Any device added externally to the unit, and which the air must pass through, causes a resistance to air flow called pressure loss.
If Modine filters are used, the pressure loss through the filters is included in the performance data on page 21. If Modine supplied discharge nozzles are used, the pressure drop of the nozzles can be found footnoted at the bottom of page 24. If filters, nozzles or ductwork are to be used with the unit, and they are not supplied by Modine, the design engineer or installing contractor must determine the pressure loss for the externally added devices or ductwork to arrive at the total external static pressure under which the unit is to operate.
Once the total static pressure and the required air flow are known, the operating speed of the blower can be determined and the correct motor sheave adjustments made. As an example, a model BDP350 is to be used with a Modine supplied blower enclosure and filters attached to ductwork by others. The unit is to move 6481 cfm of air flow against an external static pressure of 0.2″ W.C, which must be added for the filter pressure drop for a total of 0.4″ W.C. total pressure drop. The performance table on page 21 for a BDP350, at 6481 cfm and 0.4″ W.C. static pressure, shows that the unit will require a 5 hp motor using a -207 drive, and the motor sheave should be set at .5 turns open to achieve a blower speed of 1050 rpm.
To Install 1. Remove and discard the motor tie down strap and the
shipping block beneath the belt tension adjusting screw (Not used on all models.)
2. For 3 and 5 HP motors, affix sheave to the motor shaft and install motor on the motor mounting bracket. Install belt on blower and motor sheaves.
Figure 15.1 – Blower Model
THREADED MOUNTING BRACKETS ON BLOWER ASSEMBLY
MOTOR MOUNTING BRACKET
3. Adjust motor adjusting screw for a belt deflection of approximately 3/4″ with five pounds of force applied midway between the sheaves (see Figure 15.3). Since the belt tension will decrease dramatically after an initial run-in period, it is necessary to periodically re-check the tension. Excessive tension will cause bearing wear and noise.
4. The blower bearings are lubricated for life; however, before initial unit operation the blower shaft should be lubricated at the bearings with SAE 20 oil. This will reduce initial friction and start the plastic lubricant flowing.
5. Make electrical connections as outlined in the section “Electrical Connections” on page 14.
Blower Adjustments
Following electrical connections, check blower rotation to assure blow-through heating. If necessary interchange wiring to reverse blower rotation. Start fan motor and check blower sheave RPM with a hand-held or strobe-type tachometer. RPM should check out with the speeds listed in “Performance Data” shown on page 21. A single-speed motor with an adjustable motor sheave is supplied with these units. If blower fan speed changes are required, adjust motor sheave as follows:
NOTE: Do not fire unit until blower adjustment has been made or unit may cycle on limit (overheat) control.
1. Shut-off power before making blower speed adjustments. Refer to “Determining Blower Speed” on page 14 and to “Performance Data” on page 20 to determine proper blower RPM.
2. Loosen belt and remove from motor sheave.
3. Loosen set screw on outer side of adjustable motor sheave (see Figure 15.2).
4. To reduce the speed of the blower, turn outer side of motor sheave counterclockwise.
5. To increase the speed of the blower, turn outer side of motor sheave clockwise.
6. Retighten motor sheave set screw, replace belt and retighten motor base. Adjust motor adjusting screw such that there is 3/4″ belt deflection when pressed with 5 pounds of force midway between the blower and motor sheaves (see Figure 15.3). Since the belt tension will decrease dramatically after an initial run-in period, it is necessary to periodically re-check the tension to assure proper belt adjustment.
7. Check to make certain motor sheave and blower sheave are aligned. Re-align if necessary.
8. Re-check blower speed after adjustment.
9. Check motor amps. Do not exceed amps shown on motor nameplate. Slow blower if necessary.
10. Check air temperature rise across unit. Check temperature rise against values shown in Performance Tables on page 20 to assure actual desired air flow is being achieved.
11. If adjustments are required, recheck motor amps after final blower speed adjustment.
Figure 15.2 –
Figure 15.3 –
Motor Sheave Adjustment Belt Tension Adjustment
TOWARD MOTOR
SET SCREW
BLOWER SHEAVE
BLOWER HOUSING
MOTOR SHEAVE
(MOVEABLE
MOTOR ADJUSTMENT
FACE TO OUTSIDE)
SCREW
6-580.21
ADJUSTABLE HALF OF SHEAVE
3/4″ DEFLECTION WITH 5# FORCE
15
START-UP PROCEDURE
IMPORTANT
1. To prevent premature heat exchanger failure, observe heat exchanger tubes. If the bottom of the tubes become red while blower and furnace are in operation, check to be sure the blower has been set to the proper rpm for the application. Refer to page 15 for blower adjustments.
2. Start-up and adjustment procedures must be performed by a qualified service agency.
1. Turn off power to the unit at the disconnect switch. Check that fuses or circuit breakers are in place and sized correctly. Turn all hand gas valves to the “OFF” position.
2. Remove electrical junction box cover. 3. Check that the supply voltage matches the unit supply
voltage listed on the Model Identification Plate. Verify that all wiring is secure and properly protected. Trace circuits to insure that the unit has been wired according to the wiring diagram. If installed at altitudes above 2,000′ and the high altitude kit includes a combustion air proving switch, replace the switch in the unit with the switch provided in the kit. Take care to ensure that the tubing and electrical connections are securely fastened. 4. Check to insure that the venting system is installed correctly and free from obstructions. 5. Check to see that there are no obstructions to the intake and discharge of the unit. 6. For blower units, check the belt tension and sheave alignment. Refer to “Blower Adjustments” for proper belt tension. 7. Check bearings for proper lubrication (if applicable). 8. Check to make sure that all filters are in place and that they are installed properly according to direction of air flow (if applicable). 9. Perform a visual inspection of the unit to make sure no damage has occurred during installation. Lower bottom pan and visually inspect all components in the burner compartment. Check to ensure all fasteners are in place and the burner openings are properly aligned with the heat exchanger tubes and that the gas orifices are centered in the burner inspirator tube opening, as shown in Figure 17.2. 10. Check that all horizontal deflector blades are open a minimum of 30° as measured from vertical. 11. Turn on power to the unit at the disconnect switch. Check to insure that the voltage between electrical junction box terminals T1 and G is 24V. 12. Check the thermostat, ignition control, gas valve, and supply fan blower motor for electrical operation. If these do not function, recheck the wiring diagram. Check to insure that none of the Control Options have tripped. 13. Check the blower wheel for proper direction of rotation when compared to the air flow direction arrow on the blower housing (if applicable). Blower wheel rotation, not air movement, must be checked as some air will be delivered through the unit with the blower wheel running backwards. 14. For blower units, check the blower speed (rpm). Refer to “Blower Adjustments” for modification. 15. Check the motor speed (rpm). 16. Check the motor voltage. On three phase systems, check to make sure all legs are in balance. 17. Check the motor amp draw to make sure it does not exceed the motor nameplate rating. On three phase systems, check all legs to insure system is balanced. 18. Recheck the gas supply pressure at the field installed manual shut-off valve. The minimum inlet pressure should be 6″ W.C. on natural gas and 11″ W.C. on propane gas. The maximum inlet pressure for either gas is 14″ W.C. If inlet pressure exceeds 14″ W.C., a gas pressure regulator must be added upstream of the combination gas valve.
19. Open the field installed manual gas shut-off valve. 20. Open the manual main gas valve on the combination gas
valve. Call for heat with the thermostat and allow the pilot to light for intermittent pilot ignition. If the pilot does not light, purge the pilot line. If air purging is required, disconnect the pilot line at outlet of pilot valve. In no case should line be purged into heat exchanger. Check the pilot flame length (See “Pilot Flame Adjustment”). 21. Once the pilot has been established, check to make sure that the main gas valve opens. Check the manifold gas pressure (see “Main Gas Adjustment”) and flame length (see “Air Shutter Adjustment”) while the supply fan blower is operating. Inspect the condition of the main flame and if necessary, resolve flame appearance problems (see “Burner Flame Adjustment” and Figures 29.1 through 29.4). 22. Check to insure that gas controls sequence properly (see “Control Operating Sequence”). Verify if the unit has any additional control devices and set according to the instructions in the “Control Options”. 23. Once proper operation of the unit has been verified, remove any jumper wires that were required for testing. 24. Replace the electrical junction box cover. 25. If installed at altitudes above 2,000′, affix label included with high altitude kit and fill in all fields with a permanent marker.
Pilot Burner Adjustment
The pilot burner is orificed to burn properly with an inlet pressure of 6-7″ W.C. on natural gas and 11-14″ W.C. on propane gas, but final adjustment must be made after installation. If the pilot flame is too long or large, it is possible that it may cause soot and/or impinge on the heat exchanger, causing failure. If the pilot flame is shorter than shown, it may cause poor ignition and result in the controls not opening the combination gas control. A short flame can be caused by a dirty pilot orifice. Pilot flame condition should be observed periodically to assure trouble-free operation.
To Adjust the Pilot Flame 1. Create a call for heat from the thermostat.
2. Remove the cap from the pilot adjustment screw. For location, see the combination gas control literature supplied with unit.
3. Adjust the pilot length by turning the screw in or out to achieve a soft steady flame 3/4″ to 1″ long and encompassing 3/8″-1/2″ of the tip of the thermocouple or flame sensing rod (see Figure 16.1).
4. Replace the cap from the pilot adjustment screw.
Figure 16.1 – Correct Pilot Flame
3/4″ to 1″
16
6-580.21
START-UP PROCEDURE
Main Burner Adjustment
The gas pressure regulator (integral to the combination gas control) is adjusted at the factory for average gas conditions. It is important that gas be supplied to the unit heater in accordance with the input rating on the serial plate. Actual input should be checked and necessary adjustments made after the unit heater is installed. Over-firing, a result of too high an input, reduces the life of the appliance and increases maintenance. Under no circumstances should the input exceed that shown on the serial plate.
Measuring the manifold pressure is done at the outlet pressure tap of the gas valve (see Figure 17.1).
To Adjust the Manifold Pressure
1. Move the field installed manual shut-off valve to the “OFF” position.
2. Remove the 1/8″ pipe plug in the pipe tee or gas valve and attach a water manometer of “U” tube type which is at least 12″ high.
3. Move the field installed manual gas shut-off valve to the “ON” position.
4. Create a high fire call for heat from the thermostat. 5. Determine the correct high fire manifold pressure (3.5″ W.C.
for natural gas, 10″ W.C. for propane gas). (Pressures at 0-2,000′ elevation are 3.5″ W.C. for natural gas, 10″ W.C. for propane gas, for elevations above 2,000′ refer to the instructions in “Gas Connections – High Altitude Accessory Kit” on page 12). Adjust the main gas pressure regulator spring to achieve the proper manifold pressure (for location, see the combination gas control literature supplied with unit). 6. After adjustment, move the field installed manual shut-off valve to the “OFF” position and replace the 1/8″ pipe plug. 7. After the plug is in place, move the field installed manual shut-off valve to the “ON” position and recheck pipe plugs for gas leaks with soap solution.
It may also be necessary to adjust the manifold position in addition to adjusting air shutters to obtain proper flame. Follow the instructions under “Natural Gas Flame Control” for adjusting the manifold.
Figure 17.1 – Typical Combination Gas Control
GAS CONTROL KNOB
PRESSURE REGULATOR ADJUSTMENT SCREW (UNDER CAP SCREW)
INLET PRESSURE
TAP
OUTLET PRESSURE
TAP
INLET
OUTLET
RESET BUTTON
PILOT TUBING CONNECTION
PILOT ADJUSTMENT SCREW
Figure 17.2 – Manifold Adjustment, Natural Gas
MANIFOLD
MAIN BURNER ORIFICES
MANIFOLD MOUNTING SCREW AND PIN
Burner Flame Adjustment
Proper operation provides a soft blue flame with a well-defined inner core. A lack of primary air will reveal soft yellow-tipped flames. Excess primary air produces short, well-defined flames with a tendency to lift off the burner ports. For both natural and propane gas, the flame may be adjusted by sliding the manifold. Also, for units with the air shutters, they can be adjusted to control the burner flame height. The air shutters can be accessed by lowering the bottom pan of the unit heater.
Natural Gas Flame Control Control of burner flames on unit heaters utilizing natural gas is achieved by resetting the manifold position to either increase or decrease primary combustion air. Prior to flame adjustment, operate unit heater for about fifteen minutes. The main burner flame can be viewed after loosening and pushing aside the flame observation disc on the back of the unit.
To increase primary air, loosen the manifold mounting screws and move the manifold away from the burner until the yellowtipped flames disappear (see Figure 17.2). To decrease primary air, move manifold closer to the burner until flames no longer lift from burner ports, but being careful not to cause yellow tipping. Retighten manifold mounting screws after adjustment.
Propane Gas Flame Control An optimum flame will show a slight yellow tip. Prior to flame adjustment, operate heater for at least 15 minutes. Loosen air shutter set screws and move the air shutters away from the manifold to reduce the primary air until the yellow flame tips appear (see Figure 17.3). Then increase the primary air until yellow tips diminish and a clean blue flame with a well-defined inner cone appears.
MIXER TUBES
BURNER RETAINING PIN
Figure 17.3 – Air Shutter Adjustment, Propane Gas
MANIFOLD
AIR SHUTTER
MAIN BURNER ORIFICES
MIXER TUBES
6-580.21
17
START-UP PROCEDURE
Control Operating Sequence
All units are supplied with intermittent pilot systems with continuous retry control as standard. For intermittent pilot systems, both the main burner and pilot are turned off 100% when the thermostat is satisfied. For all units, the system will attempt to light the pilot for 70 seconds. If the pilot is not sensed, the ignition control will wait approximately 6 minutes with the combination gas control closed and no spark. After 6 minutes, the cycle will begin again. After 3 cycles, some ignition controllers lockout for approximately 1 hour before the cycle begins again. This will continue indefinitely until the pilot flame is sensed or power is interrupted to the system. Refer to Table 19.1 for control code descriptions. Specific descriptions of the control sequence for different control codes are listed below.
1. The thermostat calls for heat.
2. The power exhauster relay is energized, starting the power exhauster motor. Once the motor has reached full speed, the differential pressure switch closes.
3. The pilot valve opens and the ignitor sparks for 70 seconds in an attempt to light the pilot.
4. Once the pilot is lit, the flame sensor proves the pilot and stops the ignitor from sparking.
5. On single stage units, the main gas valve is opened and the main burner is lit to 100% full fire. On two stage units, the gas valve may open at either 50% or 100%, depending on what the two stage thermostat is calling for.
6. The air mover starts after 30 to 90 seconds to allow the heat exchanger to warm up.
7. The unit continues to operate until the thermostat is satisfied, at which time both the main and pilot valves close 100%.
8. The air mover stops after 30 to 90 seconds to remove residual heat from the heat exchanger.
18
6-580.21
UNIT AND CONTROL OPTIONS
Figure 19.1 – Factory Mounted Option Location
q
o
r
kp
nl
j
m
All units include the standard (STD) features. The unit must be reviewed to determine the optional (OPT) features that may have been supplied with the unit.
j Gas Valve
a) Single Stage Gas Valve – (STD) The main gas valve provides the pilot, regulator, main gas, and manual shutoff functions. For additional information, see the supplier literature included with the unit.
b) Two Stage Gas Valve – (OPT) The two stage gas valve provides the pilot, regulator, main gas (100% and 50% fire), and manual shutoff functions. For additional information, see the supplier literature included with the unit.
k Ignition controller – (STD)
The ignition controller is factory installed on the back of the unit heater with the spark igniter and sensor located on the burner. For additional information, refer to “Control Operating Sequence” on page 18 and the supplier literature included with the unit.
l Time Delay Relay – (STD)
The time delay relay is factory installed in electrical junction box and controls propeller/blower motor function. For singlephase units below 2 Hp, the time delay relay controls the motor directly. For single-phase units 2 Hp and greater and all three phase units, the time delay relay controls the motor starter. For additional information, refer to “Control Operating Sequence” on page 18.
m Low Voltage Terminal Board – (STD)
The low voltage terminal board is located in the electrical junction box. The terminal board is labeled to match the electrical wiring diagram provided with the unit. All low voltage field wiring connections should be made to the exposed side of the terminal board (exterior of electrical junction box) to prevent miswiring by modifying the factory wiring, which is inside the electrical junction box.
n Control Step Down Transformer – (STD)
The control step down transformer is located in the electrical junction box. The transformer is used to step down the supply power (115V, 208V, 230V, 460V, 575V) to 24V. This transformer is used to control the gas controls, fan delay relay, field supplied motor starter, etc. All unit heaters are supplied with a 40VA control step down transformer. To determine the control transformer supplied as well as any accessory/field supplied transformers required, reference the supply voltage listed on the serial plate.
o High Limit Switch – (STD)
The automatic reset high limit switch is factory installed on the left side (air blowing at you) of the unit heater. If the limit temperature is exceeded, the gas controls are de-energized until the switch is cooled.
p Pressure Switch (STD)
An automatic reset vent pressure switch is designed to prevent operation of the main burner if there is restricted venting of flue products. This restriction may occur due to an improper vent diameter, long vent runs, unapproved vent terminal, high winds, high negative pressure within space, etc. After the cause of the restriction has been corrected, the pressure switch will reset automatically. See the troubleshooting section for more information.
q Power Exhauster (STD)
All power vented unit heaters are supplied with a round vent pipe connection. Some models may require the use of a vent transition from the power exhauster outlet to the vent pipe (see Table 6.1). The power exhauster may be rotated 180° to allow for various venting directions.
r Blower Motor – (STD on BDP models only)
The blower motor can be provided in a variety of supply voltages and motor horsepowers. Refer to the model nomenclature to determine the motor provided. The blower motor is supplied with an adjustable sheave that can be used to increase/decrease the blower RPM. For instructions on changing the blower RPM, refer to “Blower Adjustments.”
Table 19.1 – Control Descriptions – Models PDP & BDP
Control System Description
Control Code
Natural Gas
Propane Gas
Service Thermostat Voltage Voltage
30
85
115V
25V
Single-Stage j
31 32
86
208/230V 25V
93
460V k
25V
33
94
575V k
25V
Two-Stage j
63
87
115V
25V
64
88
208/230V 25V
j All controls are intermittent pilot ignition, 100% shut-off with continuous retry. k Factory wired 460/575 available on blower models. Field installed step down
transformer may be used for 460/575 propeller applications.
6-580.21
19
GENERAL PERFORMANCE DATA
Table 20.1 – Performance – Propeller (PDP) jkl
Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM)
CFM Range Air Temp. Rise (F)
PDP 150 150,000 124,500
2180 51
PDP 175 175,000 145,250
2550 51
PDP200 200,000 166,000
2870 52
Model Number PDP 250 250,000 207,500 3700 50
PDP 300 300,000 249,000
4460 50
Max. Mounting Hgt. (Ft.)
16
17
15
19
21
PDP 350 350,000 290,500
4870 53
20
PDP 400 400,000 332,000
5440 54
19
Heat Throw (Ft.) @ Maximum Mgt. Height
Motor Type
HP
115/60/1 (PC01)
55
PSC 1/8
59
PSC 1/6
51
PSC 1/6
67
PSC 1/3
74
PSC 1/2
70
PSC 3/4
69
PSC 3/4
Ratings shown are for elevations up to 2,000′. For elevations above 2,000′, ratings should be reduced at the rate of 4%
for each 1,000′ above sea level (in Canada see rating plate.) Reduction of ratings requires use of a high altitude kit. Data taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured
from bottom of unit, and without deflector hoods. For units equipped with deflector hoods, see page 24. All motors used are produced, rated and tested by reputable manufacturers in accordance with NEMA standards and
carry the standard warranty of both the motor manufacturer and Modine. All motors are totally enclosed and all single
phase motors have built-in thermal overload protection.
Blower (BDP) Models
Model Number Btu/Hr. Input Btu/Hr. Output
Entering Airflow (CFM)
BDP150
BDP175
BDP200
BDP250
BDP300
BDP350
BDP400
150,000
175,000
200,000
250,000
300,000
350,000
400,000
123,000
143,500
164,000
205,000
246,000
287,000
328,000
Low Mid High Low Mid High Low Mid High Low Mid High Low Mid High Low Mid High Low Mid High CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
1587 2020 2778 1852 2357 3241 2116 2694 3704 2646 3367 4630 3175 4040 5556 3704 4714 6481 4233 5387 6584
Max Mounting Height. (Ft.)
10 14 23 10 15 24 9 12 22 12 17 27 13 18 30 13 19 30 13 19 25
Air Temp. Rise (F)
70 55 40 70 55 40 70 55 40 70 55 40 70 55 40 70 55 40 70 55 45
Heat Throw (Ft.) @ Max Mounting Height.
34 49 80 37 52 85 33 48 77 41 59 96 45 65 105 46 67 107 46 66 89
Heat Throw (Ft.) 45 71 120 49 76 128 43 68 115 57 87 145 64 97 160 66 99 164 66 99 136
@ 7′ Minimum Mounting Height.
* See pages 21 and 22 for motor information
20
6-580.21
GENERAL PERFORMANCE DATA
Table 20.1 – Models With or Without Blower Enclosure – Blower Model BDP j k
Model Size
ATR
40 45
50 150 55
60 65 70
40 45 50 175 55 60 65 70
40 45 50 200 55 60
65 70
40 45
50 250 55
60 65 70
40 45 50
300 55 60 65 70
40 45 50 350 55 60 65 70
40 45 50 400 55
60 65 70
CFM
2778 2469 2222 2020 1852 1709 1587 3241 2881 2593 2357 2160 1994 1852 3704 3292 2963 2694 2469 2279 2116 4630 4115 3704 3367 3086 2849 2646 5556 4938 4444 4040 3704 3419 3175 6481 5761 5185 4714 4321 3989 3704
6584 5926 5387 4938 4558 4233
0.0″ Static Press.
RPM HP Drive Turns
515 1/2 96 4.0
455 1/3
0.0
410
1.5
375
2.5
191
345 1/4
3.5
315
4.0
295
5.0
805 1-1/2 193 3.5
715 1
4.0
192
645 3/4
5.0
585 1/2 96 2.5
540
3.5
495 1/3 95 4.5
460
5.0
420 3/4 16 5.0
375 1/2 101
335 1/3
1.0
305
2.0
280
212 3.0
1/4
260
4.0
240
5.0
605 1-1/2 105 4.5
535 1
3.5
205
485 3/4
4.5
440
2.0
1/2 204
405
3.0
370
4.0
1/3 203
345
4.5
825 3 111 3.0
735 2 108
660 1-1/2 106 5.0
600 1
2.5
550
3.5
205
510 3/4
4.0
470
5.0
960 5 207 2.5
850 3 111
765 2 210 4.5
695
2.0
1-1/2 105
640
3.5
590
4.5
1 107
550
5.0
–
–
–
–
885 5 207 4.0
800 3 111 3.5
725 2 210 5.0
665
2.5
615 1-1/2 105 4.0
570
4.5
0.1″ Static Press.
RPM HP Drive Turns
565 3/4 38 4.5
515 1/2 96 4.0
475 1/3 95 5.0
445
0.5
420
1.0
1/4 191
400
2.0
380
2.5
840 1-1/2 193 2.5
755 1
3.5
192
690 3/4
4.5
635
1.5
1/2 96
590
2.5
550
3.5
1/3 95
520
4.0
465 3/4 16 4.0
420
3.5
1/2 101
390
4.5
365 1/3 102 5.0
345
0.5
325 1/4 212 1.5
310
2.0
635 1-1/2 105 3.5
570 1
3.0
520
205 4.0
3/4
480
5.0
450
1.5
1/2 204
420
2.5
395 1/3 203 3.0
850 3 111 2.5
760 2 108 2.0
690
4.0
1-1/2 106
635
5.0
590 1
2.5
550
205 3.5
3/4
515
4.0
980 5 207 2.0
880
1.5
3 111
795
3.5
730 2 210 5.0
675 1-1/2 105 2.5
630
3.5
1 107
590
4.5
–
–
–
–
915 5 207 3.5
825
3.0
3 111
760
4.5
700 2 210 6.0
650
3.0
1-1/2 105
610
4.5
0.2″ Static Press.
RPM HP Drive Turns
615 3/4 38 4.0
570
3.0
1/2 96
535
3.5
505
4.0
485 1/3 95 4.5
470
5.0
455 1/4 191 0.0
875 1-1/2 193 2.0
795 1
3.0
730
192 4.0
3/4
680
4.5
640
1.5
1/2 96
605
2.5
575 1/3 95 3.0
505 1
3.0
16
465 3/4
3.5
440
3.0
1/2 101
415
3.5
400
4.0
385 1/3 102 4.5
375
5.0
665
3.0
1-1/2 105
605
4.5
555 1
3.0
520
205 4.0
3/4
490
4.5
465
1.0
1/2 204
445
1.5
875 3 111 2.0
790 2 108 1.5
720
3.0
1-1/2 106
665
4.5
625 1
2.0
585
205 2.5
3/4
555
3.5
1005 5 207 1.5
905
1.0
3 111
825
3.0
760 2 210 4.5
710
1.5
1-1/2 105
665
3.0
625 1 107 3.5
–
–
–
–
940 5 207 3.0
855
2.0
3 111
790
4.0
735 2 210 5.0
685
2.0
1-1/2 105
650
3.5
0.3″ Static Press.
RPM HP Drive Turns
665
3.0
3/4 38
620
3.5
590
2.5
565 1/2 96 3.0
545
3.5
530 1/3 95 4.0
520
910
1.0
1-1/2 193
830
3.0
770 1
3.5
720
192 4.0
3/4
685
4.5
655
1.5
1/2 96
630
2.0
540 1
2.0
510
16 2.5
3/4
485
3.5
465
2.5
450 1/2 101 3.0
440
430 1/3 102 3.5
690 2 108 4.0
635 1-1/2 105 3.5
590 1
2.5
555
3.0
205
530 3/4
4.0
510
490 1/2 204 0.5
900
1.0
3 111
815
3.0
750 2 108 2.5
700
4.0
1-1/2 106
655
5.0
620 1
2.0
205
595 3/4
2.5
1030 5
930
1.0 207
3.0
850 3 111 2.5
790 2 210 3.5
740
0.5
1-1/2 105
695
2.0
660 1 107 3.0
–
–
–
–
965
2.5
5 207
880
4.0
815 3 111 3.0
765
4.5
2 210
720
5.0
680 1-1/2 105 2.5
0.4″ Static Press.
RPM HP Drive Turns
705 1
2.0
670
38 3.0
3/4
640
3.5
615
2.0
600 1/2 96 2.5
585
575 1/3 95 3.0
940
0.0
1-1/2 193
865
2.0
810 1
3.0
765
192 3.5
3/4
730
4.0
700
0.5
1/2 96
680
1.0
580
1.0
1
550
2.0
16
525
3/4
2.5
510
500
1.5
490 1/2 101 2.0
485
720 2 108 3.0
665
2.5
1-1/2 105
625
4.0
595 1
2.5
570
3.0
205
550 3/4
3.5
535
–
–
–
–
840 3 111 2.5
780 2 108 1.5
730
3.0
1-1/2 106
690
4.0
655
1.0
1 205
630
2.0
1050 5
955
0.5 207
2.5
880 3 111 1.5
820
3.0
2 210
770
4.0
730
1.0
1-1/2 105
695
2.0
–
–
–
–
985
2.0
5 207
910
3.5
845
2.5
3 111
795
3.5
750 2 210 4.5
715 1-1/2 105 1.5
0.5″ Static Press.
RPM HP Drive Turns
750
1.5
1
715
2.0
38
685
2.5
3/4
665
3.0
650 1.5
640 1/2 96
630
2.0
970 2
80 2.5
900 1-1/2 193 1.0
845
2.5
1
805
3.0
192
770
3/4
3.5
745
725 1/2 96 0.0
615 1-1/2 105 4.0
590 1
1.0
570
1.5
555
16
3/4
545
2.0
540
535 1/2 101 0.5
750 2 108 2.5
695
2.0
1-1/2 105
660
3.0
630
1
2.0
605
205
590
2.5
3/4
575
3.0
–
–
–
–
865 3 111 2.0
805 2 108 1.0
760
2.5
720 1/2 106 3.5
690
4.0
660 1 205 1.0
1070 5
975
0.5 207
2.0
905
1.0
3 111
845
2.5
800 2 210 3.5
760
0.0
1-1/2 105
725
1.0
–
–
–
–
1010 5
935
1.5 207
3.0
870
2.0
3 111
820
3.0
780 2 210 4.0
745 1-1/2 105 0.5
Data for use with filters only
0.6″ Static Press.
0.7″ Static Press.
RPM HP Drive Turns RPM HP Drive Turns
–
–
–
–
–
–
–
755 1
1.5
–
–
–
–
730
–
–
–
–
2.0
715
38
–
–
–
–
3/4
700
–
–
–
–
2.5
690
–
–
–
–
680 1/2 96 1.0
–
–
–
–
1005 2
80 1.5 1035
1.0
2
80
935
0.5 970
2.5
1-1/2 193
885
1.5 920 1-1/2 193 0.5
845 1
880
1.5
2.5
1
815
855
2.0
192
192
790 3/4
3.0 830
3/4
2.5
770
3.5 815
650
3.0
–
–
–
–
1-1/2 105
625
4.0
–
–
–
–
610 1
595
–
–
–
–
0.5
–
–
–
–
590
16
–
–
–
–
585 3/4
1.0
–
–
–
–
580
–
–
–
–
775
2.0
–
–
–
–
2 108
725
3.0 755 2 108 2.5
690
2.0 720
1.0
1-1/2 105
1-1/2 105
665
3.0 695
2.0
645
0.5 680
1
630
205
665 1 205 1.0
2.0
615 3/4
655
–
–
–
–
–
–
–
890 3 111 1.5 915
1.0
3 111
830
0.5 860
2.0
2 108
785
1.5 815 2 108 1.0
750
2.5 780
1.5
1-1/2 106
720
3.5 750 1-1/2 106 2.5
695 1 205 0.5 725
3.0
1095 5
1000
0.0
–
–
207
1.5 1025 5
–
–
207 1.5
930
0.5 955
0.0
3 111
3 111
870
2.0 900
1.0
825 2 210 3.0 855
2.5
2 210
790
100 4.0 815
3.0
1-1/2
755
105 0.0 785 1-1/2 100 4.0
–
–
–
–
–
–
–
1035 5
955
1.0 1055
207
5
2.5 980
0.5 207
2.0
895
1.0 920
0.5
3 111
3 111
850
2.5 875
2.0
805
3.5 835
2.5
2 210
2 210
775
4.0 800
3.5
6-580.21
Alternate Drives for 575V l
Model 150 175
200
250 300 350 400
Drive for Under 575V
1/4 – 191 1/3 – 191 1/3 – 95
1 – 38 1/3 – 95 1 – 192 1-1/2 – 193 1/4 – 212 1/3 – 212 1/3 – 102 1 – 16 1-1/2 – 105 1/3 – 203 1 – 205 1-1/2 – 105 1 – 205 1-1/2 – 106
1-1/2 – 105 1 – 205
1-1/2 – 105 1-1/2 – 100
1-1/2 – 105
Alternate Drives for 208-230/460V l
Model
150
HP & Drive Listed
1 – 38
Drive for 575V
= 1/4 – 197 = 1/3 – 197 = 1/3 – 96 = 1 – 254 = 1/3 – 96 = 1 – 256 = 1-1/2 – 198 = 1/4 – 213 = 1/3 – 213 = 1/3 – 101 = 1 – 178 = 1-1/2 – 180 = 1/3 – 204 = 1 – 157 = 1-1/2 – 180 = 1 – 157 = 1-1/2 – 108
= 1-1/2 – 180 = 1 – 157 = 1-1/2 – 180 = 1-1/2 – 210 = 1-1/2 – 180
HP & Drive Needed
= 1 – 254
1 – 192 = 1 – 256
175 1-1/2 – 193 = 1-1/2 – 198
1-1/2 – 79 = 1-1/2 – 80
1 – 16
200 1-1/2 – 105 = 1-1/2 – 180
= 1 – 178
1-1/2 – 23 = 1-1/2 – 177
1 – 205 = 1 – 157
250 1-1/2 – 105 = 1-1/2 – 180
1-1/2 – 23 = 1-1/2 – 177
1 – 205 = 1 – 157
300 1-1/2 – 105 = 1-1/2 – 180
1-1/2 – 23 = 1-1/2 – 177
1 – 205 = 1 – 157 350 1-1/2 – 106 = 1-1/2 – 108
1-1/2 – 105 = 1-1/2 – 180
400 1-1/2 – 105 = 1-1/2 – 180
Filters
For blower units with enclosure and filter, add the following static pressures to the static pressure determined by the system designer for total external static pressure.
BDP 150 BDP 175 BDP 200 BDP 250 BDP 300 BDP 350 BDP 400
j Outputs shown are for elevations up to 2000′. For elevations over 2000′, output needs to be
reduced 4% for each 1000′ above sea level.
(Does not apply in Canada – see rating plate) k Sheave turns open are approximate.
For proper operation, check blower rpm. l Models not shown use same HP and drive
numbers as cataloged. m Performance is the same; motor sheave
accommodates larger shaft. When ordering
230/460V (1 & 1-1/2 HP) or 575V, specify the
listed 230/460V (1 & 1-1/2 HP) or 575V drive.
0.1″ W.C. 0.2″ W.C. 0.1″ W.C. 0.2″ W.C. 0.2″ W.C. 0.2″ W.C. 0.2″ W.C.
21
GENERAL PERFORMANCE DATA
Table 22.1 – Power Code Description – Blower Model BDP j
Power Code Voltage Phase
01
115
1
02
230
1
07
575
3
08
208-230/460 3
09
115
1
10
230
1
15
575
3
16
208-230/460 3
17
115
1
18
230
1
23
575
3
24
208-230/460 3
25
115
1
26
230
1
31
575
3
32
208-230/460 3
33
115
1
34
230
1
39
575
3
40
208-230/460 3
41
115
1
42
230
1
47
575
3
48
208-230/460 3
49
115
1
50
230
1
55
575
3
56
208-230/460 3
57
115
1
58
230
1
63
575
3
64
208-230/460 3
65
115
1
66
230
1
71
575
3
72
208-230/460 3
73
115
1
74
230
1
79
575
3
80
208-230/460 3
81
115
1
82
230
1
87
575
3
88
208-230/460 3
89
115
1
90
230
1
95
575
3
96
208-230/460 3
150
HP Drive
1/4 191
1/4 191
1/4 197
1/4 191
1/3 191
1/3 191
1/3 197
1/3 191
1/3
95
1/3
95
1/3
96
1/3
95
1/2
96
1/2
96
1/2
96
1/2
96
3/4
38
3/4
38
3/4
38
3/4
38
1
38
1
38
1
254
1
254
1/4
13
1/4
13
1/4
14
1/4
13
3/4
96
3/4
96
3/4
96
3/4
96
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
175
HP Drive
–
–
–
–
–
–
–
–
1/3
95
1/3
95
1/3
96
1/3
95
1/2
96
1/2
96
1/2
96
1/2
96
3/4 192
3/4 192
3/4 192
3/4 192
1
192
1
192
1
256
1
256
1-1/2 193
1-1/2 193
1-1/2 198
1-1/2 198
–
–
–
–
2
80
2
80
3/4
96
3/4
96
3/4
96
3/4
96
1-1/2 79
1-1/2 79
1-1/2 80
1-1/2 80
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
200
HP Drive
1/4 212
1/4 212
1/4 213
1/4 212
1/3 212
1/3 212
1/3 213
1/3 212
1/3 102
1/3 102
1/3 101
1/3 102
1/2 101
1/2 101
1/2 101
1/2 101
3/4
16
3/4
16
3/4
16
3/4
16
1
16
1
16
1
178
1
178
1-1/2 105
1-1/2 105
1-1/2 180
1-1/2 180
1/4
24
1/4
24
1/4
25
1/4
24
1/3
24
1/3
24
1/3
25
1/3
24
1/2
25
1/2
25
1/2
25
1/2
25
3/4 101
3/4 101
3/4 101
3/4 101
1-1/2 23
1-1/2 23
1-1/2 177
1-1/2 177
j For selection of correct Power Code, refer to the tables on page 22.
250
HP Drive
–
–
–
–
–
–
–
–
1/3 203
1/3 203
1/3 204
1/3 203
1/2 204
1/2 204
1/2 204
1/2 204
3/4 205
3/4 205
3/4 205
3/4 205
1
205
1
205
1
157
1
157
1-1/2 105
1-1/2 105
1-1/2 180
1-1/2 180
–
–
–
–
2
108
2
108
3/4 204
3/4 204
3/4 204
3/4 204
1-1/2 23
1-1/2 23
1-1/2 177
1-1/2 177
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
300
HP Drive
–
–
–
–
–
–
–
–
3/4 205
3/4 205
3/4 205
3/4 205
1
205
1
205
1
157
1
157
1-1/2 106
1-1/2 106
1-1/2 108
1-1/2 108
–
–
–
–
2
108
2
108
–
–
–
–
3
111
3
111
1-1/2 105
1-1/2 105
1-1/2 110
1-1/2 180
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
350
HP Drive
–
–
–
–
–
–
–
–
1
107
1
107
1
255
1
255
1-1/2 105
1-1/2 105
1-1/2 180
1-1/2 180
1-1/2 100
1-1/2 100
1-1/2 210
1-1/2 33
–
–
–
–
2
210
2
210
–
–
–
–
3
111
3
111
–
–
–
–
5
207
5
207
–
–
–
–
2
180
2
180
–
–
–
–
5
181
5
181
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
400
HP Drive
–
–
–
–
–
–
–
–
1-1/2 105
1-1/2 105
1-1/2 180
1-1/2 180
–
–
–
–
2
210
2
210
–
–
–
–
3
111
3
111
–
–
–
–
5
207
5
207
–
–
–
–
2
180
2
180
–
–
–
–
3
112
3
112
–
–
–
–
5
111
5
111
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
22
6-580.21
PERFORMANCE DATA – HOODS
Table 23.1 – Performance Data – 30°, 60° and 90° Downward Deflector Hoods
Mounting Height to Bottom of Heater
8′ 10′ 12′ 14′ 16′ 18′ 20′ 22′ 24′ 26′ 28′ 30′
PDP j
PDP 150 PDP 175 PDP 200 PDP 250 XYZ XYZ XYZ XYZ
16 36 49 18 38 52 15 33 45 21 44 60 15 34 47 17 37 51 14 31 43 20 43 59 14 33 45 15 35 49 12 30 41 19 42 58 12 30 42 14 33 46 11 27 37 17 40 56 10 27 38 12 31 43 8 22 31 16 38 53 6 20 29 9 26 37 6 18 26 14 36 50
12 32 45 8 24 35
30° Downward Hood For Propeller Units
BDP k
PDP 300 PDP 350 PDP 400 BDP 150 BDP 175 BDP 200 BDP 250 XYZ XYZ XYZ XYZ XYZ XYZ XYZ
24 49 67 22 46 63 22 45 62 26 53 72 28 56 76 24 50 68 31 63 86 23 48 66 21 45 62 21 44 61 25 52 71 26 55 75 23 49 67 30 62 85 21 47 65 20 44 61 19 43 59 23 51 70 25 54 74 22 48 66 29 62 84 20 46 63 19 43 59 18 42 57 22 50 68 24 53 73 21 47 64 28 61 83 19 44 61 17 41 56 16 40 55 21 48 66 23 52 71 19 45 62 27 59 81 17 42 58 15 38 53 15 37 52 19 46 64 21 50 69 18 43 59 25 58 80 15 39 54 13 35 49 13 33 47 18 44 61 20 48 66 16 40 56 24 56 77 13 35 49 10 29 42 8 25 37 16 41 57 18 45 63 14 36 51 22 54 75 8 26 38 8 24 36 8 24 35 13 36 51 16 42 59 10 29 42 21 52 72
19 48 68 16 44 62 12 36 52
BDP 300 BDP 350 BDP 400 XYZ XYZ XYZ
35 69 94 37 73 99 30 61 84 34 69 94 36 72 98 29 61 83 33 68 93 34 71 97 28 60 82 31 67 92 33 71 96 27 59 80 30 66 90 32 69 95 26 57 79 29 65 89 31 68 93 24 56 77 28 63 87 30 67 92 23 54 75 26 62 85 28 65 90 21 52 72 25 59 82 27 63 87 20 49 69 23 57 79 25 61 85 18 46 64 21 54 75 23 58 81 15 41 58 19 50 70 21 55 77 10 32 47
Mounting Height to Bottom of Heater
8′ 10′ 12′ 14′ 16′ 18′ 20′ 22′ 24′ 26′ 28′ 30′
PDP 150 X Y Z
0 38 52 0 36 49 0 33 46 0 30 41 0 25 35 0 13 19
PDP 175 X Y Z
0 40 55 0 39 53 0 36 50 0 33 46 0 29 41 0 23 32
PDP j
PDP 200 PDP 250 XYZ XYZ
0 35 47 0 33 45 0 30 41 0 26 36 0 19 27 0 12 17
0 47 65 0 46 63 0 44 60 0 41 57 0 38 53 0 35 48 0 29 40 0 16 23
60° Downward Hood For Propeller Units
PDP 300 X Y Z
0 52 72 0 51 70 0 50 68 0 48 65 0 45 62 0 42 58 0 38 52 0 32 45 0 19 28
PDP 350 X Y Z
0 49 68 0 48 66 0 46 64 0 44 61 0 41 57 0 38 52 0 33 46 0 25 35 0 16 24
PDP 400 X Y Z
0 48 66 0 47 64 0 45 62 0 43 59 0 40 55 0 36 50 0 31 43 0 21 30 0 16 23
BDP 150 X Y Z
0 56 77 0 55 76 0 54 74 0 52 71 0 50 68 0 47 64 0 43 60 0 39 54 0 33 45
BDP 175 X Y Z
0 60 82 0 59 81 0 57 79 0 56 76 0 54 74 0 51 70 0 48 66 0 44 61 0 39 54
BDP 200 X Y Z
0 53 73 0 52 71 0 50 69 0 48 67 0 46 63 0 43 59 0 39 54 0 34 47 0 24 34
BDP k
BDP 250 BDP 300 BDP 350 XYZ XYZ XYZ
0 68 93 0 67 91 0 65 90 0 64 88 0 62 85 0 60 82 0 58 79 0 55 75 0 51 70 0 46 64 0 40 56 0 30 43
0 74 102 0 78 107 0 74 101 0 77 106 0 72 99 0 76 104 0 71 97 0 75 102 0 69 95 0 73 100 0 68 93 0 72 98 0 65 90 0 70 95 0 63 86 0 67 92 0 60 82 0 64 89 0 56 78 0 61 84 0 52 72 0 57 79 0 46 65 0 53 73
BDP 400 X Y Z
0 66 90 0 65 88 0 63 87 0 62 85 0 60 82 0 58 79 0 55 76 0 52 72 0 48 66 0 43 60 0 36 50 0 22 31
Mounting Height to Bottom of Heater
8′ 10′ 12′ 14′ 16′ 18′ 20′ 22′ 24′ 26′ 28′ 30′ 32′ 34′ 36′ 38′ 40′ 42′
PDP 150 S
38 34 31 29 27 25 24 23
PDP 175 S
42 37 34 32 29 28 26 25
PDP j
PDP 200 PDP 250
S
S
36
54
32
48
29
44
27
41
25
38
24
36
23
34
22
33
31
30
29
90° Downward Hood For Propeller Units
BDP k
PDP 300 S
62 56 51 47 44 42 40 38 36 35 33 32
PDP 350 S
58 52 47 44 41 38 36 35 33 32 31 30
PDP 400 S
56 50 46 42 39 37 35 34 32 31 30 29
BDP 150 BDP 175
S
S
72
79
65
70
59
64
55
60
51
56
48
53
46
50
44
48
42
45
40
44
39
42
37
41
36
39
35
38
BDP 200 S
70 63 58 53 50 47 45 42 41 39 38 36 35 34
BDP 250 S
98 88 80 74 70 66 62 59 57 55 53 51 49 48 46 45 44 43
BDP 300 BDP 350
S
S
113
121
101
108
92
99
85
91
80
85
75
81
71
76
68
73
65
70
63
67
60
65
58
62
56
60
55
59
53
57
52
55
50
54
49
53
BDP 400 S
94 84 77 71 67 63 60 57 55 52 50 49 47 46 45 43 42 41
j Data based on units fired at full rated input with an entering air temperature of 60°-80°F. Maximum mounting heights higher versus units without outlet devices.
k Data based on unit fired at full rated input, 60°-80°F entering air temperature, and a 40°F temperature rise through unit. Maximum mounting heights higher versus units without outlet devices.
THROW-FLOOR COVERAGE
30 DOWNTURN HOOD 60 DOWNTURN HOOD
30
MOUNTING
60
H
HEIGHT
30° HOOD
60° HOOD
X
60 NOZZLE Y
Z
X
30 NOZZLE
Y
6-580.21
S
S
Z
90° HOOD
23
PERFORMANCE DATA NOZZLES
Figure 24.1 – Mounting Height, Heat Throw, Heat Spread (in feet)
90° VERTICAL NOZZLE
H H
T S
40° DOWNWARD NOZZLE
T
H
T S
40° SPLITTER NOZZLE
S
S
5-WAY NOZZLES
S S
Table 24.1 – Mounting Height, Heat Throw, Heat Spread (in feet)
Nozzle Type
Model Number BDP 150 BDP 175 BDP 200 BDP 250 BDP 300 BDP 350 BDP 400
40°
Max. Mounting Ht. (ft.) H 26
25
27
29
31
32
32
Downward Nozzle
Heat Throw (ft.) T
79
76
81
86
94
96
96
Heat Spread (ft.) S
26
25
27
29
31
32
32
Max. Mounting Ht. (ft.) H 26
26
24
29
31
32
32
90° Vertical
Nozzle
Heat Spread (ft.) S
26
26
24
29
31
32
32
Max. Mounting Ht. (ft.) H 24
24
23
25
28
30
32
40° Splitter Nozzle
Heat Throw (ft.) T Heat Spread (ft.) S
60
59
59
62
70
75
80
120
118
117
124
140
151
160
5-Way
Max. Mounting Ht. (ft.) H
22
21
20
25
26
23
26
Nozzle
Heat Spread (ft.) S
31
29
28
35
36
32
36
The above table is based on an inlet air temperature of 70°F and an air temperature rise of 55°F. Air deflectors on, 40° and 90° discharge nozzles set perpendicular to the face of the air discharge opening. On 5-way nozzles all air deflectors set perpendicular to floor. Static pressure measured at 0.1″ W.C. for 90° nozzle, 0.2″ W.C. for 40° downward and 5-way nozzle, and 0.3″ W.C. for 40° splitter nozzle. Outlet velocities are approximately 1,750 FPM for the 40° nozzles, 1,000 FPM for the 90° nozzle and 1,300 FPM for 5-way. For motor size, drive and blower rpm refer to page 21. Mounting height measured from bottom of unit.
24
6-580.21
DIMENSIONAL DATA
Figure 25.1 – Dimensional Drawings – Propeller Units (Model PDP)
A H
K AA
EB
BB D (OPENING)
M C
F
W
X
G
K
DD J LL
EE
L (MIN. DISTANCE TO WALL)
Table 25.1 – Dimensions (inches) – PDP j
Dimension Symbol
Model Number PDP 150 PDP 175 PDP 200 PDP 250 PDP 300 PDP 350 PDP 400
A
21
B
35-1/4
C
22
D
18-9/16
E
20
F
13.00
G
6-9/16
H
17-3/8
J
5 k
K (Mounting Holes) l
3/8-16
L m
35-13/16
M
29-13/16
W
X
AA
8
BB
7-1/4
DD
2-3/4
EE
30-1/2
LL
31-1/8
Gas Connections n 1/2
Fan Diameter
16
Approx. Weight
168
23-1/2 35-1/4
22 21-1/16
20 12.75 6-9/16 19-7/8 5 k
3/8-16
35-9/16 29-9/16
8 7-1/4 2-3/4 30-1/2 31-1/8 1/2 18 175
25-5/8 40-1/4
25 23-3/16
24 14.38 7-1/2
22 5 k
3/8-16
40-3/4 34-3/4
9 7-1/4 3-3/8 32-7/8 34-7/8 1/2 20 239
25-5/8 40-1/4
25 23-3/16
24 14.38 7-1/2
22 6
3/8-16
40-3/4 34-3/4
9 7-1/4 3-3/8 32-7/8 34-7/8 3/4 20 239
28-5/8 40-1/4
25 26-3/16
24 14.75 7-1/2
25 6
3/8-16
40-3/4 34-3/4
9 7-1/4 3-3/8 32-7/8 36-1/4 3/4 22 269
33-5/8 40-1/4
25 31-3/16
24 7-1/2 30 6
40 40-1/4
25 37-1/2
24 7-1/2 36-3/8 6
3/8-16 3/8-16
40-3/4 34-11/16
5 16 9 7-1/4 3-3/8 32-7/8 35-1/2 3/4 22 338
44-3/16 38-3/16
5 16 9 7-1/4 6-13/16 32-7/8 40-1/2 3/4 24 418
j Do not use propeller units with duct work. k Vent connection is 5″, connected to a factory supplied vent transition. For model sizes 150 and 175,
the factory supplied transition is 4″ (to the power exhauster outlet) to 5″ (to the vent system). For model size 200, the factory supplied transition is 6″ (to the power exhauster outlet) to 5″ (to the vent system). l PDP 150 through PDP 300 – 2 holes (and the level hanging adjustment feature). PDP 350 through PDP 400 – 4 holes. (Listed is the hole diameter and threads per inch to accept threaded rod). m Dimension equals overall plus 6″.
n For natural gas; may vary depending on control availability.
6-580.21
25
DIMENSIONAL DATA
Figure 26.1 – Dimensional Drawings – Blower Units (Model BDP)
M
A
C
H
F
DD
K
W
X
AA
G
EB BB D (OPENING)
J K
LL
EE L (MIN. DISTANCE TO WALL)
Table 26.1 – Dimensions (inches) – BDP
Dimension Symbol
Model Number BDP 150 BDP 175 BDP 200 BDP 250 BDP 300 BDP 350 BDP 400
A
21
B
35-1/4
C
22
D
18-9/16
E
20
F
12
G
6-9/16
H J K Mounting Holes k
17-3/8 5 j 3/8-16
L w/ Blwr Encl & Filt Rk 62-5/8
L w/o Blwr Encl & Filt Rk 53-1/8
M l
47-1/8
N m
21-1/2
O
7-1/4
P
30
Q Blower Encl Ht
21-3/8
R Inlet Duct Height
20
S Center to Center Blower Mtg. Holes
17-5/16
T Inlet Duct Width
27-1/2
V Blower Encl Width
29
W
X
AA
8
BB
7-1/4
DD
2-3/4
EE Gas Connections n
56-5/8 1/2
Blower Wheel Diameter 13
Approx. Weight
152
23-1/2 35-1/4
22 21-1/16
20 12 6-9/16 19-7/8 5 j 3/8-16 62-5/8 53-1/8 47-1/8 21-1/2 7-1/4 30 21-3/8 20
17-3/8
27-1/2 29 8
7-1/4 2-3/4 56-5/8 1/2
13 152
25-5/8 40-1/4
25 23-3/16
24 13-1/2 7-1/2
22 5 j 3/8-16 69-5/8 61 55 25-7/16 8-1/2 34 25-1/8 23-3/4
20-3/8
32-3/4 34-1/4
9 7-1/4 2-3/4 63-5/8 1/2 15 315
25-5/8 40-1/4
25 23-3/16
24 13-1/2 7-1/2
22 6 3/8-16 69-5/8 61 55 25-7/16 8-1/2 34 25-1/8 23-3/4
28-5/8 40-1/4
25 26-3/16
24 14 7-1/2 25 6 3/8-16 69-5/8 61 55 24-15/16 8-1/2 34 25-1/8 23-3/4
33-5/8 40-1/4
25 31-3/16
24 7-1/2 30 6 3/8-16 69-5/8 61 55 17-15/16 8-1/2 34 25-1/8 23-3/4
40 40-1/4
25 37-1/2
24 7-1/2 36-3/8 6 3/8-16 69-5/8 65 59 22 8-1/2 34 25-1/8 23-3/4
20-3/8 20-3/8 20-3/8 20-3/8
32-3/4 34-1/4
9 7-1/4 3-3/8 63-5/8 3/4 15
315
32-3/4 34-1/4
9 7-1/4 3-3/8 63-5/8 3/4 15
339
42-7/8 44-3/8
5 16 9 7-1/4 3-3/8 63-5/8 3/4 15
428
42-7/8 44-3/8
5 16 9 7-1/4 6-13/16 63-5/8 3/4 15
498
j Vent connection is 5″, connected to a factory supplied vent transition. For model sizes 150 and 175, the factory supplied transition is 4″ (to the power exhauster outlet) to 5″ (to the vent system). For model size 200, the factory supplied transition is 6″ (to the power exhauster outlet) to 5″ (to the vent system).
k BDP 150 thru BDP 300 — 4 holes (2 on blower and 2 on unit). BDP 350 and BDP 400 —6 holes (2 on blower and 4 on unit). (Listed is the hole diameter and threads per inch to accept threaded rod).
l This is an approximate dimension for standard motors, allow 3″ for sheave and optional motors.
m Distance between mounting hole in unit casing and mounting hole on blower. On the BDP 350 and BDP 400, the distance is from rear mounting hole in casing to the mounting hole on blower.
n For natural gas; may vary depending on control availability.
26
6-580.21
MAINTENANCE
WARNING
When servicing or repairing this equipment, use only factoryapproved service replacement parts. A complete replacement parts list may be obtained by contacting the factory. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk.
CAUTION
1. Service or repair of this equipment must be performed by a qualified service agency.
2. Do not attempt to reuse any mechanical or electrical controllers which have been wet. Replace defective controller.
NOTE: To check most of the possible remedies in the troubleshooting guide listed in Table 28.1, refer to the applicable sections of the manual.
General Maintenance The unit and venting system must be checked once a year by a qualified service technician. All installation and service of these units must be performed by a qualified installation and service agency. Before any service, BE SURE TO TURN OFF GAS AT THE MANUAL SHUT-OFF VALVE AHEAD OF THE COMBINATION GAS CONTROL AND TURN OFF ALL ELECTRIC POWER TO THE HEATER.
General Unit When providing annual maintenance for the unit heater, keep the unit free from dust, dirt, grease and foreign matter. Pay particular attention to: 1. The combustion air and exhaust vent piping. 2. The burner ports and pilot burner orifices (avoid the use of
hard, sharp instruments capable of damaging surfaces for cleaning these ports). To check the burner port and pilot burner orifice, see “Burner and Pilot Assembly Removal”. 3. The air shutters and main burner orifices (avoid the use of hard, sharp instruments capable of damaging surfaces for cleaning these orifices). To check the air shutters and main burner orifices, see for “Manifold Assembly Removal.” 4. The heat exchanger. Clean tubes from the bottom with a stiff non-wire brush. 5. The heat exchanger should be checked annually for cracks and discoloration of the tubes. If a crack is detected, the heat exchanger should be replaced before the unit is put back into service. If the tubes are dark gray, airflow across the heat exchanger should be checked to insure that a blockage has not occurred or the blower is operating properly.
Electrical Wiring The electrical wiring should be checked annually for loose connections or deteriorated insulation.
Gas Piping & Controls The gas valves and piping should be checked annually for general cleanliness and tightness.
The gas controls should be checked to ensure that the unit is operating properly.
Propeller Assembly
Check the motor for lubrication if the motor is not permanently lubricated. Inspect the fan for damage and fit on motor shaft. Clean any dust, dirt or foreign matter from the fan blades.
Blower Assembly The blower assembly includes the bearings, drive sheaves and belts. Blower bearings should be checked and lubricated based on the blower manufacturer’s recommendations. Bearings should also be checked for any unusual wear and replaced if needed.
Drive sheaves should be checked at the same time the bearings are inspected. Check to make sure the sheaves are in alignment and are securely fastened to the blower and motor shafts.
Belt tension should be rechecked shortly after the unit has been installed to check for belt stretching. After the initial start-up, monthly checks are recommended.
Manifold Assembly Removal To remove the manifold:
1. Shut off gas and electric supply. 2. Lower bottom pan to expose burner and manifold (see
Figure 17.2). 3. Disconnect pilot tubing and thermocouple lead (or ignition
cable) at the combination gas control (and ignition control). 4. Disconnect control wires for the combination gas control. 5. Disconnect gas manifold at ground union joint. 6. Remove the 2 screws holding the manifold to the heat
exchanger support. 7. Clean the orifices and adjust the air shutters as necessary. 8. Follow steps 2-6 in reverse order to install the manifold
assembly. 9. Turn on the electric and gas supply. 10. Check the ground union joint for leaks with a soap
solution. Tighten if necessary.
Burner and Pilot Assembly Removal To remove the burner:
1. Shut off gas and electric supply. 2. Lower bottom pan to expose burner and manifold (see
Figure 17.2). 3. Disconnect pilot tubing and thermocouple lead (or ignition
cable) at the combination gas control (and ignition control). 4. Remove the 2 burner retaining pins holding the burner in
place. The burner can then be easily lowered from the unit. 5. Examine the burner and pilot assembly for cleanliness
and/or obstructions as necessary (see “General Unit” for cleaning instructions). 6. Replace the burner assembly in reverse order. In replacing the burner, be certain that the slots at the front of the burner are located properly on their shoulder rivets and that the burner retaining pins are put back into their proper locations. 7. Reconnect the ignition cable and pilot gas supply line. 8. Turn on the electric and gas supply.
6-580.21
27
SERVICE & TROUBLESHOOTING
Table 28.1 – Troubleshooting
Trouble Pilot does not light
Possible Cause 1. Main gas is off. 2. Power supply is off. 3. Air in gas line. 4. Dirt in pilot orifice.
5. Gas pressure out of proper range.
6. Pilot valve does not open. a. Defective ignition controller. b. Blown fuse on control board c. Defective gas valve.
7. No spark at ignitor. a. Loose wire connections. b. Pilot sensor is grounded. c. Blown fuse on control board d. Defective ignition controller.
8. Safety device has cut power.
9. Pilot valve is off. 10. Dirty thermocouple contact. 11. Excessive drafts. 12. Pilot orifice Fitting leak.
Main burners do not light (Pilot is lit)
Lifting Flames (See Figure 29.2) Yellow Tipping (With propane gas, some yellow tipping is always present.) Wavering Flames (See Figure 29.1) Flashback
Floating Flames (see Figure 29.3)
Flame Rollout (see Figure 29.4)
1. Defective valve. 2. Loose wiring. 3. Defective pilot sensor 4. Defective ignition controller. 5. Improper thermostat wiring. 1. Too much primary air. 2. Main pressure set too high. 3. Orifice too large.
1. Insufficient primary air. 2. Dirty orifice. 3. Misaligned orifice.
1. Drafts across burner 2. Misalignment of burner 3. Cracked heat exchanger
1. Too much primary air 2. Main pressure set too high. 3. Orifice too large.
1. Insufficient primary air. 2. Main pressure set too high. 3. Orifice too large.
4. Blocked vent.
1. Main pressure set too high. 2. Orifice too large.
3. Blocked vent.
28
6-580.21
Possible Remedy
1. Open manual gas valve. 2. Turn on main power. 3. Purge gas line. 4. Check for plugged pilot orifice and clean
with compressed air if necessary. 5. Adjust to a maximum of 14″ W.C.
Minimum for natural gas – 6″ W.C. Minimum for propane gas – 11″ W.C. 6. Check wiring for 24 volts to valve. a. Replace ignition controller. b. Replace Fuse c. Replace gas valve. 7. a. Check all ignition controller wiring. b. Replace sensor if cracked or worn c. Replace fuse d. Replace ignition controller. 8. Check all safety devices (High limit, pressure switch, blocked vent safety switch, etc.) Determine and correct problem. Reset if necessary. 9. Turn gas control knob or lever on combination gas control to pilot position. 10. Be sure thermocouple contact is clean. If problem persists replace thermocouple. 11. Find source and re-direct airflow away from unit. 12. Tighten pilot orifice. Flame impingement on thermocouple may cause thermocouple to become inoperative.
1. Replace valve. 2. Check wiring to gas valve. 3. Replace pilot sensor. 4. Replace ignition controller. 5. Verify wiring compared to wiring diagram.
1. Reduce primary air. 2. Adjust to a maximum of 14″ W.C. 3. Check orifice size with those listed on
the serial plate.
1. Increase primary air. 2. Check orifices and clean with
compressed air if necessary. 3. Check manifold, replace if necessary.
1. Eliminate drafts 2. Align burner on locator pins 3. Replace heat exchanger
1. Reduce primary air. 2. Adjust to maximum of 14″ W.C. 3. Check orifice size with those listed on the
serial plate.
1. Increase primary air. 2. Adjust to a maximum of 14″ W.C. 3. Check orifice size with those listed on the
serial plate. 4. Clean/correct venting system.
1. Adjust to a maximum of 14″ W.C. 2. Check orifice size with those listed on
the serial plate. 3. Clean/correct venting system.
SERVICE & TROUBLESHOOTING
Trouble Not Enough Heat
Possible Cause
1. Unit cycling on high limit. j a. Obstructions/leaks in duct system. b. Main pressure set too high. c. Blower motor not energized.
d. Loose belt e. Blower speed too low.
f. Blocked/damaged venting system. g. Air distribution baffle removed (high
temperature rise units only). h. Defective high limit switch. 2. Main pressure set too low.
3. Too much outside air.
4. Thermostat malfunction. 5. Gas controls wired incorrectly.
6. Unit undersized.
Too Much Heat
1. Thermostat malfunction. 2. Gas controls do not shut-off.
a. Gas controls wired incorrectly.
b. Short circuit. 3. Main gas pressure set too high. 4. Defective gas valve.
Possible Remedy
1. a. Clean/correct duct system. b. Adjust to a maximum of 14″ W.C. c. Check/correct to insure blower motor operates within 45 seconds of when gas controls are energized. d. Adjust belt tension. e. Check/correct blower drive settings for proper rpm. f. Check/correct venting system. g. Replace air distribution baffle.
h. Replace high limit switch. 2. Adjust main gas pressure.
Minimum for natural gas — 6″ W.C. Minimum for propane gas — 11″ W.C. 3. Adjust outside air damper to decrease outside air percentage (if possible). 4. Check/replace thermostat. 5. Check unit wiring against the wiring diagram. 6. Check design conditions. If unit is undersized, an additional unit(s) or other heat source must be added.
1. Check/replace thermostat. 2.
a. Check unit wiring against the wiring diagram.
b. Check for loose or worn wires. 3. Adjust to a maximum of 14″ W.C. 4. Replace gas valve.
j Automatic Reset High Limit
The unit heater comes standard with an automatic reset high limit switch that will shut off the gas should the discharge air temperature become excessive. See Figure 19.1, indicator 7 for the location of either the standard automatic high limit switch. The switch should operate only when something is seriously wrong with the unit operation. Anytime the switch operates, correct the difficulty immediately or serious damage may result. If the switch cuts off the gas supply during normal operation, refer to the “Not Enough Heat” section of Service & Troubleshooting.
Figure 29.3 – Floating Flame Condition
Figure 29.1 – Wavering Flame or Misalignment
GOOD
BAD
Figure 29.4 – Flame Rollout Appearance
Figure 29.2 – Lifting Flame Condition
6-580.21
29
MODEL NUMBER / RATING PLATE IDENTIFICATION
Figure 30.1 – Serial Number Designations
S 01 10 09 17 09 23 09 1234 10000
Serial Number Prefix <blank> if standard “S” if Special Product Order
Motor Supplier 01 – Century
03 – General Electric 05 – Universal 30 – Fasco 15 – Marathon 18 – Franklin 29 – Emerson 35 – Baldor
38 – Regal Beloit EPC 39 – McMillan 43 – Nidec
Fan/Blower Vendor Code 20 – Morrison 01 – Revcor 10 – Lau 08 – Brookside 19 – Air Drive
Series Identity Number
SPO Number
Number varies from 0000 to 9999. Each unit within same week of manufacture is to have unique number
Year of Manufacture
Week of Manufacture
Gas Valve Supplier 01 – RobertShaw 05 – Honeywell 09 – White Rogers
Control Supplier 01 – RobertShaw 09 – White Rogers 05 – Honeywell 17 – United Tech 08 – Fenwal
Figure 30.2 – Model Number Designations
PDP 150 A E 01 30 S B A N
PDP – Propeller Unit BDP – Blower Unit
MBH Input 150 – 150,000 Btu/hr input 175 – 175,000 Btu/hr input 250 – 250,000 Btu/hr input
etc.
Heat Exchanger/Burner A – Aluminized Steel / Aluminized Steel
S – Stainless Steel / Aluminized Steel T – Stainless Steel / Stainless Steel
Ignition Type E – Intermittent Pilot
Power Code 01 02 etc.
Complete Power Code descriptions are
shown on pages 20 and 22
Factory Installed Option Digit N – None C – BMS – (Building Management Systems)
Future A – All
Dev Digit
Fan Guard Digit N – None (all blower models) S – Standard F – Fingerproof
Control Code Type 30 Complete Control Code descriptions are shown on page 19
30
6-580.21
WARRANTY
This Warranty (the “Warranty”) shall apply to Products (as defined below) sold by Modine Manufacturing Company, a Wisconsin corporation (“Seller”) to you (“Buyer”).
Seller hereby warrants that during the Applicable Warranty Period (as defined below) its Products shall be free from defects in material and factory workmanship under normal use and service, subject to the EXCLUSIONS described below and according to the terms outlined in this Warranty.
If Seller receives written notice of a breach of this Warranty prior to the end of the Applicable Warranty Period (which such notice shall include the model and serial numbers of the Product, as well as the date and a reasonably detailed description of the Product’s alleged failure), Buyer shall with Seller’s prior written approval, return the applicable Product or component thereof to Seller with shipping charges prepaid; if upon examination by Seller such Product or component thereof is disclosed to have been defective, then Seller will, without charge to Buyer, at Seller’s option, either repair the Product, replace defective parts in the Product, or offer an entire replacement unit of the Product; provided that the warranty period for a Product that has been repaired or provided with replacement parts shall not extend beyond the original Applicable Warranty Period, nor shall any replacement parts provided for a Product be under any warranty beyond the original Applicable Warranty Period for the Product; similarly, if Seller provides an entire replacement unit of the Product, the warranty period for the replacement unit is limited to the remainder of the original Applicable Warranty Period. Seller shall have no responsibility for installation, service, field labor, shipping, handling, or other costs or charges, except as expressly provided in this Warranty. Buyer shall have no remedy hereunder for any defective part returned without proper written authorization from Seller, as described above.
For purposes of this Warranty and subject to the exclusions described below, the term “Products” shall mean parts or equipment manufactured by Seller, sold to Buyer pursuant to a purchase contract between Buyer and Seller (most often initiated by a purchase order issued by Buyer and accepted by Seller), and expressly described in such contract. The term “Products” shall not include third-party parts or equipment furnished by Seller, except that, to the extent assignable, Seller will assign to Buyer the benefits (together with all limitations and exclusions) of the thirdparty manufacturer’s warranty for such parts or equipment. This Warranty extends only to the original purchase contract between Buyer and Seller and is nontransferable, except that this Warranty may be assigned to an Authorized End User (as defined below). All replaced parts or equipment shall become Seller’s property. For purposes of this Warranty, the term “Applicable Warranty Period” shall mean the warranty period set forth in the table below for each type or class of Product described on the table; provided that, when the Product is to be used as a component part of equipment manufactured by Buyer, the Applicable Warranty Period shall be limited to one (1) year after the date of shipment from Seller, notwithstanding anything in the table below to the contrary. For purposes of this Warranty, the term “Authorized End User” shall mean any third-party that purchases the Product directly or indirectly from Buyer for the Authorized End User’s own use upon the first installation of the Product and not for resale.
BUYER HEREBY ACKNOWLEDGES THAT ITS REMEDIES FOR BREACH OF THIS WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, ARE LIMITED AS DESCRIBED ABOVE.
EXCLUSIONS AND LIMITATIONS: This Warranty is subject to the following exclusions and limitations:
The term “Products” shall not include and this Warranty shall not apply to any of the following items: refrigerant gas, belts, filters, fuses and other items consumed or worn out by normal wear and tear.
In addition, this Warranty shall not apply to:
(1) Products or components thereof that are damaged or adversely affected by conditions beyond Seller’s control, including but not limited to polluted or contaminated or foreign matter contained in the air or water utilized for heat exchanger (condenser) cooling or if the failure of the part is caused by improper air or water supply, or improper or incorrect sizing of power supply;
(2) Any Products or components thereof which have been repaired or altered outside the factory of Seller in any way, or otherwise subject to unauthorized repairs or alterations, so as, in the judgment of Seller, to affect the Product’s durability or performance;
(3) Materials or labor of any kind not furnished by Seller, or any charges for any such labor or materials, whether such labor, materials or charges thereon are due to replacement of parts, adjustments, repairs, or any other work done by any party other than Seller;
(4) Labor or other costs incurred for diagnosing, repairing, removing, installing, shipping, servicing, or handling of either defective or replacement parts;
(5) Any Products removed from their original location for reinstallation in another location;
(6) Any Products or components thereof which have been operated, maintained, or serviced contrary to Seller’s written installation, operation, and/or servicing instructions or owner’s manual;
(7) Damages resulting from operation with an inadequate or interrupted supply of air or water;
(8) Any Products or components thereof which have been subjected to misuse, negligence, faulty installation, improper servicing, accident, excessive thermal shock, excessive humidity, physical damage, impact, abrasion, improper operation, or other operating conditions in excess of or contrary to those for which such equipment was designed;
(9) With respect to gas-fired or oil-fired units, any Products or components thereof if the input to the Product exceeds the rated input (as indicated on the Product’s serial plate) by more than five percent (5%);
(10) Any Products or components thereof which, in the judgment of Seller, have been installed in a corrosive atmosphere, marine, or coastal application, subjected to corrosive fluids or gases, or damaged or adversely affected by the effects of the physical or chemical properties of water or steam or other liquids or gases used in the Products or any component thereof;
(11) Damage or failure to start resulting from improper voltage conditions, blown fuses, open circuit breakers, or other
6-580.21
31
inadequacy or interruption of electrical service or fuel supply; or
(12) Any Products or components thereof from which the serial number has been altered, defaced or removed.
BUYER AGREES THAT THE WARRANTIES AND REMEDIES DESCRIBED HEREIN ARE THE ONLY WARRANTIES AND REMEDIES PROVIDED BY SELLER WITH RESPECT TO THE PRODUCTS AND TO THE MAXIMUM EXTENT PERMITTED UNDER APPLICABLE LAW SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER WARRANTIES AND REMEDIES WHATSOEVER, EITHER EXPRESS OR IMPLIED, WHETHER ARISING FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, AND NON-INFRINGEMENT, EACH OF WHICH SELLER HEREBY EXPRESSLY DISCLAIMS. SELLER NEITHER ASSUMES (NOR HAS AUTHORIZED ANY PERSON TO ASSUME) ANY OTHER WARRANTY OR LIABILITY IN CONNECTION WITH ANY PRODUCTS. REPRESENATATIONS AND CONDITIONS, EXPRESS OR IMPLIED BY STATUTE, TRADE USAGE, OR OTHERWISE, ARE EXCLUDED AND WILL NOT APPLY TO THE PRODUCTS UNDER THIS WARRANTY, EXCEPT FOR WARRANTIES WHICH BY LAW CANNOT BE EXCLUDED
OR LIMITED. Without limiting the foregoing, Seller makes no and specifically disclaims all representations and/or warranties that the Products will detect the presence of, or eliminate, prevent, treat, or mitigate the spread, transmission, or outbreak of any pathogen, disease, virus, or other contagion, including but not limited to COVID 19.
BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR COSTS OF PROCESSING, LOST REVENUES OR PROFITS, INJURY TO GOODWILL, OR ANY OTHER SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGES OF ANY KIND RESULTING FROM THE PURCHASE OF THE PRODUCTS, OR FROM BUYER’S USE OF ANY PRODUCT, WHETHER ARISING FROM BREACH OF WARRANTY, NONCONFORMITY TO ORDERED SPECIFICATIONS, DELAY IN DELIVERY, OR ANY OTHER LOSS SUSTAINED BY THE BUYER.
OPTIONAL SUPPLEMENTAL WARRANTY
Buyer may purchase from Seller a supplemental warranty with respect to Products which shall extend the Applicable Warranty Period as set forth in the express terms and conditions described in the supplemental warranty agreement. Such supplemental warranty terms may include an additional four (4) years on certain compressors, an additional five (5) years “all parts” warranty, an additional four (4) or nine (9) years on certain heat exchangers, and/ or such additional supplemental warranty terms as Seller chooses to make available to its customers from time to time.
COMPONENT Heat Exchangers and/or Coils
APPLICABLE MODELS
APPLICABLE WARRANTY PERIOD (WHICHEVER OCCURS FIRST)
Time from Date of First Beneficial Use by Buyer or
Authorized End User
Time from Date of Shipment from Seller
Gas Fired Unit Heaters with Tubular Style Heat Exchangers
(e.g. HD, HDS, PTX, BTX, etc)
Aluminized or Stainless Steel
10 YEARS
126 MONTHS
Gas Fired Unit Heaters with Clam-Shell Style Heat
Exchangers
(e.g. PDP, BDP, etc.)
Aluminized Steel (not in highhumidity
applications)
Aluminized Steel (in high-humidity
applications)
10 YEARS (must be Stainless Steel in high-humidity applications)
1 YEAR
126 MONTHS 18 MONTHS
Stainless Steel
10 YEARS
126 MONTHS
Low Intensity Infrared Units
5 YEARS
66 MONTHS
Indoor and Outdoor Duct Furnaces and System Units, Steam/Hot Water Units, Oil-Fired Units, Electric Units, Cassettes, Vertical Unit Ventilators, Geothermal Units
1 YEAR
18 MONTHS
Burners and Elements
Low Intensity Infrared Units High Intensity Infrared and Electric Infrared Units
2 YEARS 1 YEAR
30 MONTHS 18 MONTHS
Compressors
Condensing Units for Cassettes Vertical Unit Ventilators, Geothermal Units
5 YEARS 1 YEAR
66 MONTHS 18 MONTHS
Sheet Metal Parts
All Products
1 YEAR
18 MONTHS
Components, excluding Heat Exchangers, Coils, Condensers,
Burners, Sheet Metal
All Products
2 YEARS
30 MONTHS
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.
© Modine Manufacturing Company 2024
32
6-580.21
Modine Manufacturing Company 1500 DeKoven Avenue Racine, WI 53403 Phone: 1.800.828.4328 (HEAT) www.modinehvac.com
(12) aux Produits ou composants de ces derniers dont le numéro de série a été modifié, dégradé ou retiré.
L’ACHETEUR CONVIENT QUE LES GARANTIES ET LES RECOURS DÉCRITS AUX PRÉSENTES SONT LES SEULES GARANTIES ET LES SEULS RECOURS FOURNIS PAR LE VENDEUR EN CE QUI CONCERNE LES PRODUITS, ET DANS LA PLUS GRANDE MESURE PERMISE PAR LA LOI EN VIGUEUR, ILS REMPLACENT ET EXCLUENT TOUTES LES AUTRES GARANTIES ET TOUS LES AUTRES RECOURS QUI SOIENT, EXPLICITES OU IMPLICITES, DÉCOULANT DE LA LOI, D’UNE TRANSACTION, DE L’USAGE DU COMMERCE OU AUTREMENT, Y COMPRIS, SANS S’Y LIMITER, LES GARANTIES DE VALEUR MARCHANDE, D’ADAPTATION À UN USAGE PARTICULIER ET DE NON-CONTREFAÇON, AUXQUELS LE VENDEUR RENONCE EXPRESSÉMENT PAR LES PRÉSENTES. LE VENDEUR N’ASSUME PAS (ET N’A PAS AUTORISÉ QUICONQUE À ASSUMER) TOUTE AUTRE GARANTIE OU RESPONSABILITÉ RELATIVEMENT AUX PRODUITS. LES REPRÉSENTATIONS ET LES CONDITIONS, EXPRESSES OU IMPLICITES PAR STATUT, USAGE DU COMMERCE OU AUTREMENT, SONT EXCLUES ET NE S’APPLIQUENT PAS AUX PRODUITS EN VERTU DE LA PRÉSENTE GARANTIE, À L’EXCEPTION DES GARANTIES QUI NE PEUVENT PAS ÊTRE EXCLUES OU LIMITÉES SELON LA LOI.
Sans limiter ce qui précède, le Vendeur n’effectue aucune déclaration et renonce spécifiquement à toute garantie que les Produits détecteront la présence, élimineront, traiteront ou atténueront la propagation, la transmission ou l’éruption de pathogènes, maladies, virus ou autres contagions, y compris, sans s’y limiter, la COVID-19.
L’ACHETEUR CONVIENT QUE LE VENDEUR SERA EN AUCUN CAS RESPONSABLE DES COÛTS DE TRAITEMENT, DES PERTES DE REVENUS OU DE PROFITS, DES PERTES D’ACHALANDAGE OU D’AUTRES DOMMAGES SPÉCIAUX, INDIRECTS OU CONSÉCUTIFS DE TOUTE SORTE DÉCOULANT DE L’ACHAT DES PRODUITS OU DE L’UTILISATION DE TOUT PRODUIT PAR L’ACHETEUR, QU’ILS SOIENT LE RÉSULTAT DU NON-RESPECT DE LA GARANTIE, D’UNE NONCONFORMITÉ AUX SPÉCIFICATIONS DE COMMANDE, DE RETARDS DE LIVRAISON OU DE TOUTE AUTRE PERTE SUBIE PAR L’ACHETEUR.
GARANTIE SUPPLÉMENTAIRE EN OPTION
L’Acheteur peut se procurer auprès du Vendeur une garantie supplémentaire relative aux Produits qui prolongera la Période de garantie applicable qui est établie dans les conditions expresses décrites dans l’accord de garantie supplémentaire. Les conditions d’une telle garantie supplémentaire peuvent comprendre une période supplémentaire de quatre (4) ans sur certains compresseurs, une garantie supplémentaire de cinq (5) ans sur « toutes les pièces », une période supplémentaire de quatre (4) ou neuf (9) ans sur certains échangeurs de chaleur ou d’autres conditions de garantie supplémentaires que le Vendeur peut accepter d’offrir à ses clients de temps à autre.
COMPOSANT
Échangeurs thermiques ou serpentins
MODÈLES APPLICABLES
Appareils de chauffage au gaz avec échangeurs de chaleur de style tubulaire (par ex., HD, HDS, PTX,
BTX, etc.)
Acier aluminisé ou inoxydable
Appareils de chauffage au gaz avec échangeurs de chaleur de style grappin (par ex., PDP, BDP, etc.)
Acier aluminisé (pas dans des applications à
humidité élevée)
Acier aluminisé (dans les applications à humidité
élevée)
PÉRIODE DE GARANTIE APPLICABLE (SELON LA PREMIÈRE ÉVENTUALITÉ)
Période à compter de la première Période à compter de
utilisation par l’Acheteur ou
la date d’expédition
l’Utilisateur final autorisé
par le Vendeur
10 ANS
126 MOIS
10 ANS (doit être en acier inoxydable
dans les applications à humidité élevée)
1 AN
126 MOIS 18 MOIS
Acier inoxydable
10 ANS
126 MOIS
Modèles infrarouges à faible intensité
5 ANS
66 MOIS
Systèmes et chaudières canalisés pour l’intérieur et l’extérieur, modèles à vapeur/eau chaude, modèles au mazout, modèles électriques, cassettes, ventilateurs
verticaux, appareils géothermiques
1 AN
18 MOIS
Brûleurs et éléments
Modèles infrarouges à faible intensité Modèles infrarouges à haute intensité et infrarouges électriques
2 ANS 1 AN
30 MOIS 18 MOIS
Compresseurs
Condenseurs pour cassettes Ventilateurs verticaux, appareil géothermiques
5 ANS 1 AN
66 MOIS 18 MOIS
Pièces en tôle
Tous les produits
1 AN
18 MOIS
Composants, excluant les échangeurs thermiques, les serpentins, les condenseurs,
les brûleurs, la tôle
Tous les produits
2 ANS
30 MOIS
Puisque Modine Manufacturing Company a un programme d’amélioration permanente de ses produits, elle se réserve le droit de modifier la conception et les caractéristiques techniques sans préavis.
© Modine Manufacturing Company 2024
Modine Manufacturing Company 1500 DeKoven Avenue Racine, WI 53403 Téléphone : 1 800 828-4328 (HEAT) www.modinehvac.com
GARANTIE COMMERCIALE
La présente garantie (la « Garantie ») s’applique aux Produits (tels qu’ils sont définis ci-dessous) vendus par Modine Manufacturing Company, une entreprise du Wisconsin (le « Vendeur ») à vous
(l’« Acheteur »).
Durant la Période de garantie applicable (telle que définie ci-dessous), le Vendeur garantit par les présentes que ses Produits seront exempts de défauts de matériaux et de fabrication en usine dans des conditions normales d’utilisation et d’entretien, assujettie aux EXCLUSIONS décrites ci-dessous et conformément aux conditions établies dans la présente Garantie.
Si le Vendeur reçoit un avis écrit
Documents / Resources
![]() |
MODINE PDP, BDP Power Vented Gas Fired Unit Heaters [pdf] Installation Guide PDP Series, BDP, PDP BDP Power Vented Gas Fired Unit Heaters, PDP BDP, Power Vented Gas Fired Unit Heaters, Vented Gas Fired Unit Heaters, Gas Fired Unit Heaters, Fired Unit Heaters, Unit Heaters, Heaters |