SMARTSWITCH TD-4000 Tank Monitor

Ver 9.6 Installation Manual

This document provides installation and programming instructions for the SMARTSWITCH TD-4000 Tank Monitor.

TD-4000 Master Display Unit (MDU)

The TD-4000 Master Display Unit (MDU) provides the following functions:

Electrical Specifications TD-4000

Supply Voltage10 to 30 Volts DC (Auto-Sensing)
Quiescent Current0.03 Amps
Data Retention50 years (without power)

Outputs

The TD-4000 has two (open collector) outputs, which can be used to turn a relay ON or OFF. These outputs can be used to control pumps (e.g., Black discharge pump) or, with output 2, to activate a relay when the Black tank reaches a set alarm point to disable the toilet.

Wiring Diagram for TD-4000

The TD-4000 unit connects to the following:

Pump Circuit Connection

Connect to the Blue or White wire on the TD-4000. Blue = Output 1, White = Output 2. This connects to a Relay, Battery, and Pump.

Disable Toilet Circuit Connection (NOTE: Output 2 ONLY)

Connect to the White wire on the TD-4000 (White = Output 2). This connects to a Relay, Battery, and Toilet Switch.

RJ-11 to three core cable

Part # RJ-STD. Used for Pressure sensor connection (phone cable connector to plug in green connector). Connections: Black = GND, White = Signal In, Red = + 5vdc.

Connector Wiring

Back View:

Model:
Serial No:
D.O.M:

Inputs are labeled 4, 3, 2, 1, each with terminals for +12 vdc, +5 vdc, Signal In, GND.

Connector Wiring For Ultra-Sonic Sender

Connector Wiring For Pressure Sender

WARNING: DO NOT CONNECT TO + 12 vdc

Connector Wiring For RJ-11 Adaptor

WARNING: DO NOT CONNECT TO + 12 vdc

Display Functions

The display shows tank information, battery voltage, and pump status. Key functions are accessed via buttons:

Example display: "Port Fuel", "240 Lts", "P 62 %". The unit has 2 display modes. See page 10 for instructions on how to change them.

Programming Instructions

NOTE: Program Input & Calibrate must be performed for each tank.

Step 1: Placing the unit in Program Mode

Press and hold down the [Backlight Button] then press and hold the [Scroll Button]. Hold together for 3 seconds. This will bring you to the Set-Up Menu.

The Set-Up Menu includes options such as:

Use the [Scroll Button] or [Backlight Button] to scroll through the Set-Up Menu or press the [Pump Button] to program an Input.

Step 2: Selecting an Input to program

Once in program mode, each Input can be individually programmed. The display will show:

Select Input 1

Use the [Scroll Button] or [Backlight Button] to scroll to the Input requiring programming. Press the [Pump Button] once the input to be programmed has been found.

Step 3: Selecting Tank or Battery Name

The display will now show:

GREY TANK
Select Name

NOTE: There is a list of pre-programmed names. If you want to change a name, see Step 3a. Once a name has been used, DO NOT use the same name again when programming another tank; choose another name from the list.

Use the [Scroll Button] or [Backlight Button] to scroll through the pre-programmed tank names. Press the [Pump Button] once the required tank name has been found. If you want the name selected, press the [Pump Button] again; otherwise, if you want to change the name, see next Step 3a.

Step 3a: Changing Tank Name Text

The tank name text may be changed. After selecting the Tank (name), use the [Backlight Button] to move the cursor to each individual letter and the [Scroll Button] to scroll through the alphabet. When finished, press the [Pump Button] to enter.

Step 4: Selecting Type

The display will now show:

< Grey Water INPUT TYPE >

Use the [Scroll Button] or [Backlight Button] to scroll through the various Input Types (e.g., Grey Water, Black Water, Fresh Water, Fuel). Press the [Pump Button] once the appropriate tank type has been found. Note: The tank type only sets where the alarm point starts and the pump default start or stop points.

If the Battery is selected, see Step 5a. If Transfer is selected, see page 12.

Step 5: Setting the Alarm point for Tank

The display will now show:

Set Alarm Point

The alarm point is the point where the tank will alarm you (e.g., almost empty, almost full). Use the [Scroll Button] or [Backlight Button] to move the alarm point to the desired level. Press the [Pump Button] to set this as your alarm point.

Step 5a: Setting the Alarm point for Low Battery

The display will now show:

Set Alarm Point
Set Alarm = 10

The alarm point is the point where the battery will alarm you when it's low. This can be set at any level. Use the [Scroll Button] or [Backlight Button] to move the alarm point to the desired level. Press the [Pump Button] to set this as your alarm point.

Step 6: Audible Alarm

The display will now show:

< No Audible Alarm Yes >

Press the [Scroll Button] to select "Yes" or the [Backlight Button] to select "No". If "Yes" is selected, the audible alarm will sound based on the alarm point set. If "No" is selected, there will be no audible alarm, only a visual bell icon (?).

Note: If this is a battery, the system will return you to the Set-Up Menu. If this is a tank, go to Step 7.

Step 7: Tank Volume

The display will now show:

Set Tank Volume
< No Yes >

This allows for displaying the tank volume in either Litres or Gallons. If this feature is required, press the [Scroll Button] to select "Yes". Next select "Lts" for Litres or "Gals" for Gallons.

The display will now show " Set Volume 00000 ". Use the [Backlight Button] and [Scroll Button] to change the value and the [Pump Button] to enter and move to the next digit. When the last digit is reached and the [Pump Button] is pressed, the system will return to the Set-Up Menu.

Otherwise, press the [Backlight Button] to select "No". If "No" is selected, the system will return to the Set-Up Menu. Repeat this process for all additional Inputs.

Note: After a tank has been programmed, individual settings may be changed. From the Set-Up Menu, scroll to the option you wish to change and press the [Pump Button].

Set Outputs

The TD-4000 has two outputs and can be associated with any of the inputs. To set up this feature, scroll down to "Set Output" (in the Set-Up Menu) and press the [Pump Button].

The display will now show:

Tank Name ?
Select Input 1

Press the [Scroll Button] or [Backlight Button] to scroll to the Input you want to select and press the [Pump Button].

The display will now show:

< No Program Output Yes >

This allows you to exit if you have made a mistake. If you would like to escape, press the [Backlight Button]. This will return you to the Set-Up Menu. Otherwise, press the [Scroll Button] to continue.

The display will now show:

Program Output
Output Number 1

Press the [Scroll Button] or [Backlight Button] to move between Output 1 & 2. Once the desired Output is displayed, press the [Pump Button]. This has now been set and the system will return to the Set-Up Menu.

This setting can be changed at any time by selecting this option from the menu and following the on-screen directions.

Pump Output

(also see Pump Start / Stop: page 10)

The TD-4000 has two Pump Output controls and works as follows:

Special Pump

If the Black tank has a charcoal filter fitted and you are using a pressure sensor, you will need to use this feature.

Explanation: When the pump is turned on, liquid is removed from the tank quicker than air can replace it due to the constrictive nature of the air filter. This will cause a pressure drop, making the system think the tank is empty and turn the pump off.

The Special Pump feature will allow the pump to run for a pre-set time without looking at the tank level. The pump will then turn Off for 20 seconds, allowing the tank to equalize its pressure. The system will then look at the tank level and turn the pump back On for a time period based on the tank level. If the tank level is low, the time period will be short. This will continue until the tank is empty.

If this feature is selected, when the pump is On, the display will show "------PUMPING------". When the pump is Off, during the equalizing time, the display will show "------EQUALIZING------".

Scroll down to "Special Pump" and press the [Pump Button].

The display will now show:

Special PumpOut
< No Yes >

Press the [Scroll Button] to select "Yes" or the [Backlight Button] to select "No". If "No" is selected, the feature will not be turned on and the system will return to the Set-Up Menu.

If "Yes" is selected, the display will now show:

Set Time
< Default Set >

This is the time period the pump will run (if full) before looking at the tank level. Either "Default" or "Set" may be selected.

If "Default" is selected, the time period will be set to 3 minutes and the system will return to the Set-Up Menu.

If "Set" is selected, the display will now show:

Set Time
Set Minutes = 1

Use the [Scroll Key] to scroll through the times 1 to 5 minutes. Press the [Pump Key] to enter. The system will now return to the Set-Up Menu.

Pump Start / Stop

Day Tank: If a tank has been set as a Day Tank in the Tank TYPE set-up, this feature allows you to set when the transfer pump will automatically be turned On and Off. This can be set up by selecting the "Pump Start/Stop" option from the Set-Up Menu and selecting the tank you wish to set this up on. Use the [Scroll Button] or [Backlight Button] to set the pump Start and Stop point. Once this is complete, press the [Pump Key] and you will return to the Set-Up Menu.

Grey, Black, Fresh or Fuel: If a tank has been set as either a Grey, Black or Fresh Tank in the Tank TYPE set-up, this feature allows you to set when the pump will automatically be turned Off. This can be set up by selecting the "Pump Start/Stop" option from the Set-Up Menu and selecting the tank you wish to set this up on. Use the [Scroll Button] or [Backlight Button] to set the pump stop point. Once this is complete, press the [Pump Key] and you will return to the Set-Up Menu. Note: Set the stop point for Grey, Black or Water at a very low setting and Fuel at a top setting.

Transfer: If a tank has been set as a Transfer in the Tank TYPE set-up, this feature allows for both low and high pump stop points (see page 12).

Disable Toilet:

From the Set-Up Menu, scroll down to "DISABLE TOILET" then press the [Pump Button].

The display will now show:

Disable Toilet
< No Yes >

If "Yes" is selected (by pressing the [Scroll Key]), this will set Output two (white wire) to short to GND when the Black Tank reaches the alarm point and turn Off 12 display bars below this point.

If "No" is selected, you will return to the main MENU.

Copy Calibrate:

This function allows you to copy the calibration settings from one input to another. NOTE: Please ensure you have calibrated the input you are copying FROM.

From the Set-Up Menu, scroll down to "COPY CALIBRATE" then press the [Pump Button].

The display will now show:

Copy From
Select Input 1

Use the [Scroll Key] to scroll to the input you want to copy FROM and press the [Pump Key] to enter.

The display will now show:

Copy to
Select Input 1

Use the [Scroll Key] to scroll to the input you want to copy TO and press the [Pump Key] to enter. You will now be returned to the main MENU.

External Alarm

Using Output 2 (white) for external alarm:

Note: External alarm can be used for both low and high or just high.

Step 1:

From the Set-Up Menu, scroll down to "External Alarm" then press the [Pump Button]. The display will now show:

Tank Name ?
Select Input 1

Use the [Scroll Button] or [Backlight Button] to find the Input to associate with the external alarm (only one input may be associated). When the input is found, press the [Pump Button] to accept.

Step 2:

The display will now show:

< No Set Low Alarm Yes >

Both low and high alarm points OR just the high alarm point can be set. If "Yes" is selected (by pressing the [Pump Button]), this will activate and allow the low alarm points to be set. If "No" is selected, go to Step 5.

Step 3:

The display will now show:

Set Low Start

Use the [Scroll Button] or [Backlight Button] to set the point where the Low alarm comes on (trigger point).

Step 4:

The display will now show:

Set Low Stop

Use the [Scroll Button] or [Backlight Button] to set the point where the Low alarm comes off (alarm reset point). Note: this point MUST be greater than the Start point.

Step 5:

The display will now show:

Set High Start

Use the [Scroll Button] or [Backlight Button] to set the point where the High alarm comes on (trigger point).

Step 6:

The display will now show:

Set High Stop

Use the [Scroll Button] or [Backlight Button] to set the point where the High alarm comes off (alarm reset point). Note: this point MUST be smaller than the Start point.

Transfer Fuel Feature

This feature allows for the pump output to have both low and high stop points.

Step 1:

When programming a tank and the INPUT TYPE screen is displayed, the display will now show:

Transfer Fuel
< INPUT TYPE >

Use the [Scroll Button] or [Backlight Button] to scroll to the option "Transfer Fuel" and press the [Pump Button] to accept. Set the alarm (Step 5) and Tank Vol (Step 7) settings.

Step 2:

At the main menu, scroll down to the "PUMP START/STOP" option.

The display will now show:

Tank Name ?
Select Input 1

Use the [Scroll Button] or [Backlight Button] to find the Input to associate with the output, when the input is found press the [Pump Button] to accept.

Step 3:

The display will now show:

Set Stop Low

Use the [Scroll Button] or [Backlight Button] to set the low point where the pump will turn OFF and press the [Pump Button] to accept.

Step 4:

The display will now show:

Set Stop High

Use the [Scroll Button] or [Backlight Button] to set the high point where the pump will turn OFF and press the [Pump Button] to accept.

Erasing Inputs

From the Set-Up Menu, scroll down to "ERASE INPUT" then press the [Pump Button].

The display will now show:

Erase Input
< No Yes >

If "Yes" is selected (by pressing the [Scroll Key]):

The display will now show:

Tank Name ?
Select Input 1

Use the [Scroll Button] or [Backlight Button] to find the Input to erase, and then press the [Pump Button] to erase that Input's data. The system will then return to the Set-Up Menu.

If "No" is selected (by pressing the [Backlight Button]), the inputs data will NOT be erased and the system will return to the Set-Up Menu.

Exit Menu

Once all required inputs have been calibrated and programmed, you can exit from the Set-Up Menu by pressing the [Scroll Button] until "Exit Menu" is displayed, then press the [Pump Button]. This will save all associated data that has been set and take the system out of Set-Up mode and into Monitoring mode. The TD-4000 is now ready for use!

Operating Instructions:

  1. Pressing the [Backlight Button] will turn the backlight ON; press again to turn OFF.
  2. Press the [Scroll Button] to alternate between tanks.
  3. Press and hold the [Scroll Button] for 4 seconds to alternate between display modes.
  4. Pressing the [Pump Button] will turn the pump (power) ON; press again to turn OFF. If a pump is turned ON, a "P" will be displayed in the top right section of the display.

The [Pump Button] will also act as the Mute key if an alarm is on. E.g., if the alarm is ON, the first press will mute the alarm, the second press will turn the pump ON or OFF.

Audio Alarm:

The audio alarm can be turned ON or OFF by holding down the [Backlight Button] for 3 seconds. You will hear a bleep after every second. After 3 bleeps, you may release the key. If the audible alarm is turned off, there will still be a visual alarm (bell icon ?).

The bell icon will flash when the tank with the alarm is scrolled to, otherwise it will remain on solid. A solid bell indicates there is an alarm, but not for the tank being displayed.

Sensor Installation

! WARNING !

PLEASE NOTE: For sensor Model SEN-50 The Maximum Tank Height is .5 Meter
PLEASE NOTE: For sensor Model SEN-100 The Maximum Tank Height is 1 Meter
PLEASE NOTE: For sensor Model SEN-250 The Maximum Tank Height is 2.5 Meter

The maximum surge and safe pressure is 28psi.

For more information see "Calibration Tips & Tricks" on our web site www.smartswitch.co.nz

Mounting Adaptors Available:

A range of mounting adaptors are available which includes flat sidewall, top mount, 1.5" pipe, 2" pipe, 3" pipe and drain valve. Ask your dealer for details.

Sensor Installation:

The sensor should be mounted as low in the sidewall as possible using a ¼" spin-in or the flat sensor adaptor. If the sensor adaptor is used, it will require drilling a 5/8" hole in the sidewall. Apply silicon glue liberally to the bottom of the adaptor. Using #10 x 1½" stainless steel self-tapping screws, attach the adaptor to the sidewall. Once the adaptor is attached, make sure that the hole in the adaptor is clear of any excess glue. Allow drying as per the instructions for the glue. Wrap the threads of the sensor using Teflon plumbers tape and install the sensor. Tighten by hand. It is not recommended to install the sensor in the bottom of the tank. Although the sensor will operate correctly, it will provide an area for debris to collect which would be difficult to flush out.

Top mount adaptor (tube not supplied): The top-mounting adaptor requires 3/4" ABS or PVC pipe cut to the proper length so that the pipe is about 1/2" from the bottom of the tank. This pipe glues into the adaptor and the sensor screws into the top of the adaptor. It is held on with 2 self-tapping screws. Care must be taken that the sensor threads are sealed with Teflon tape and screwed in tight to ensure no air leaks, as the tube must remain pressurized.

Pipe adaptor: The sensor will be damaged if subject to over pressure during installation, caused by compressing the small air gap between the sensor and the ball valve.

Sidewall adaptor

WARNING: DO NOT PRESSURIZE TANK WITH SENSOR FITTED

Sensor Programming Instructions

Placing the unit in Calibrate Mode

Press and hold down the [Backlight Button] then press and hold the [Scroll Button]. Hold together for 3 seconds. This will bring you to the Set-Up Menu.

Use the [Scroll Button] or [Backlight Button] to scroll to "Calibrate" and press the [Pump Key]. This will bring you to the Calibrate Menu.

The display will now show:

Tank Name ?
Select Input 1

Use the [Scroll Button] or [Backlight Button] to scroll to the tank input requiring calibration. Press the [Pump Key] once the input to be calibrated has been found.

The display will now show:

CALIBRATE MENU
PRESSURE
ULTRA-SONIC
10-180 OHM
33-240 OHM
OTHER SENDER
TOP ONLY
BOTTOM ONLY
EXIT MENU

Use the [Scroll Button] or [Backlight Button] to scroll through the list of sensor options. Once you have found the appropriate sensor type, press the [Pump Key].

If Pressure is selected, the display will now show:

Calibration Mode
< 2 Pt 5 Pt >

Two different methods of tank programming are available if using the pressure sensor:

Press the [Scroll Button] or [Backlight Button] to select either 2 or 5 Point Calibration.

2 Point Calibration: (Bottom & Top)

The display will now show:

Set Empty Point
Input = ?.?? v

Voltage from Sensor (see table 1 page 19)

Fill the tank to the required TANK LOW LEVEL, minimum suggested is liquid just covering the sensor. Wait for approx. 60 seconds for the fluid to settle and press the [Pump Key]. The display will show "Setting Empty Please Wait".

The display will now show:

Set Full Point
Input = ?.?? v

Voltage from Sensor (see table 1 page 19)

Fill the tank to the TANK HIGH LEVEL. Wait for approx. 60 seconds for the fluid to settle and press the [Pump Key]. The display will show "Setting Full Please Wait". When the system has finished calculating (could take a few moments), the display will show " Calibration Finished " and the system will return you to the Set-Up Menu.

Once back at the Set-Up Menu, repeat this process. This must be repeated for all additional Inputs.

If no fluid is added, the display will show:

Value Not Larger
Please Try Again

For more information see "Calibration Tips & Tricks" on our web site www.smartswitch.co.nz

5 Point Calibration: (Bottom, ¼, ½, ¾ & Top)

The display will show:

Set Empty Point
Input = ?.?? v

Voltage from Sensor (see table 1 page 19)

Fill the tank to the required TANK LOW LEVEL, minimum suggested is liquid just covering the sensor. Wait for approx. 60 seconds for the fluid to settle and press the [Pump Key]. The display will show "Setting Empty Please Wait".

The display will now show:

Set ¼ Point
Input = ?.?? v

Voltage from Sensor (see table 1 page 19)

Fill the tank to the ¼ LEVEL. Wait for approx. 60 seconds for the fluid to settle and press the [Pump Key]. The display will show "Setting ¼ Please Wait".

The display will now show:

Set ½ Point
Input = ?.?? v

Voltage from Sensor (see table 1 page 19)

Fill the tank to the ½ LEVEL. Wait for approx. 60 seconds for the fluid to settle and press the [Pump Key]. The display will show "Setting ½ Please Wait".

The display will now show:

Set ¾ Point
Input = ?.?? v

Voltage from Sensor (see table 1 page 19)

Fill the tank to the ¾ LEVEL. Wait for approx. 60 seconds for the fluid to settle and press the [Pump Key]. The display will show "Setting ¾ Please Wait".

The display will now show:

Set Full Point
Input = ?.?? v

Voltage from Sensor

Fill the tank to the FULL LEVEL. Wait for approx. 60 seconds for the fluid to settle and press the [Pump Key]. The display will show "Setting Full Please Wait". When the system has finished calculating (could take a few moments), the display will show " Calibration Finished " and the system will return to the Set-Up Menu.

Once back at the Set-Up Menu, repeat this process. This must be repeated for all additional Inputs.

If no fluid is added between each step, the display will show:

Value Not Larger
Please Try Again

For more information see "Calibration Tips & Tricks" on our web site www.smartswitch.co.nz

If Ultra-Sonic is selected: the display will show " Calibration Finished " and the system will return to the Set-Up Menu. This is because the Ultra-Sonic sensor is pre-calibrated with its own hardware/software. NOTE - Please see Programming Instructions for Ultra-Sonic sensor in the manual supplied with the sensor.

If 10-180 Ohm is selected: the display will show " Calibrating Please Wait ". When the system has finished calculating (could take a few moments), the display will show " Calibration Finished " and the system will return to the Set-Up Menu.

If 33-240 Ohm is selected: the display will show " Calibrating Please Wait ". When the system has finished calculating (could take a few moments), the display will show " Calibration Finished " and the system will return to the Set-Up Menu.

If Other Sender is selected: this is the same as selecting Pressure; see instructions for Pressure on page 15.

After calibrating the bottom and top settings of a tank, you may wish to go back and change either of these settings individually.

If Top Only is selected: the system will read the current level of the tank and calibrate this as the top level for that particular tank. The system will then return to the Set-Up Menu.

If Bottom Only is selected: the system will read the current level of the tank and calibrate this as the bottom level for that particular tank. The system will then return to the Set-Up Menu.

To Exit from the Calibrate Menu: scroll down to "Exit Menu" and press the [Pump Key]. This will take you out of the Calibrate Menu and return you to the Set-Up Menu.

Table 1:

Smart Switch strongly recommends that Table 1 be filled out at the time of tank calibration when a Pressure sender is being used. These voltages will be displayed during the calibration setup.

Reason: Should the TD-4000 ever need to be replaced, all tanks will need to be re-calibrated, but if Table 1 has been filled out, then creating these input voltages can be done without even the tank sender connected, making the process very simple.

InputsTank NameEmpty1/41/23/4Full
Input 1
Input 2
Input 3
Input 4
Models: TD-4000, TD-4000 Tank Monitor, Tank Monitor, Monitor

File Info : application/pdf, 20 Pages, 417.04KB

PDF preview unavailable. Download the PDF instead.

TD-4000 Manual

References

Microsoft Word for Microsoft 365

Related Documents

Preview TD-1000 Tank Monitor Installation and Programming Manual
This manual provides installation, wiring, and programming instructions for the TD-1000 Tank Monitor by SmartSwitch. Learn how to set up tank names, alarm points, pump off points, and perform sensor calibration for various tank geometries.
Preview Smartswitch TM-4000 Tank Monitor/Controller Ver 9.5 Installation Manual
Comprehensive installation manual for the Smartswitch TM-4000 Tank Monitor/Controller system (Ver 9.5), detailing setup, wiring, and operation for marine applications. Learn how to monitor and control fluid levels in up to four tanks.
Preview SmartSwitch FD-Z2 Fire Monitor Installation Manual
Detailed installation manual for the SmartSwitch FD-Z2 Fire Monitor, covering specifications, operation, wiring, and sensor connection diagrams for marine and industrial applications.