FD-Z2
SMARTSWITCH
FD-Z2 Fire Monitor
Installation Manual

FD-Z2 Specifications
Minimum smoke current (alarm current) = 10mA Operate voltage = 9 - 30vdc Quiescent Current = 34mA @12vdc Maximum current per zone = 320mA (including EOL) Siren/Buzzer output = 12vdc @ 800mA All wire = UL Rated
Supply voltage @ 12vdc Maximum sensors = 14 per zone Must use 2k2 EOL resistor
Supply voltage @ 24vdc Maximum sensors = 8 per zone Must use 5k6 EOL resistor
FD-Z2 Operation: per zone
"OK" LED On = system is all ok..
"FAULT" LED On = either open or shorted smoke detection cable or sensor.
If there is a short on the line: If a short is detected on the line the "OK "LED will turn Off, the "FAULT" LED and alarm will be turned On, the Sensor Output will also be turned Off. When the "SILENCE / RESET " button is pushed the "FAULT" LED will turn Off and the zone "OK" LED will flash for one minute, after the one minute delay the Sensor Output will be turn On again to check the line. This procedure will repeat until the short is removed.
If the line is open circuit: If a open circuit is detected on the line the "OK "LED will turn Off, the "FAULT" LED and alarm will be turned On. When the "SILENCE / RESET " button is pushed the alarm will be muted. When the system detects the EOL resistor the "FAULT" LED will turn Off and the "OK" LED will turn On.
"FIRE" LED On = A sensor has detected smoke or heat.
SILENT / RESET Button: This button will mute the audible alarm and reset the sensors. The "OK" LED will flash for one minute, after the one minute delay the Sensor Output will be turn On again. This is to allow the smoke to clear the sensor.
TEST Button: If the TEST button is pressed for three seconds the unit will go into Test mode. All LED'S and the alarm will turn On for five seconds.

FD-Z2 Wiring

Black = Battery Yellow = Buzzer +
White = Zone + Blue = Zone +

FD-Z2

Red = Battery + Purple = Buzzer Black = Zone Black = Zone -

Zone Colours:
White = ENGINE ROOM Blue = ACCOM / CABIN

Connecting Multiple Sensors Per Zone (heat, smoke or both)
This diagram shows only one zone
White

FD-Z2

Black

Com -

In + Out +

R

Com -

In + Out +

R

In +

Com -

Out +

R

Note: Detector manufactures use different terminal designators, E.g. L1, L2 , L3 OR Com ­ , In + , Out +
Note: For HOCHIKI brand use terminals 1, 2, & 6

Supply voltage @ 12vdc Maximum sensors = 14 per zone Must use 2k2 EOL resistor
Supply voltage @ 24vdc Maximum sensors = 8 per zone Must use 5k6 EOL resistor

Connecting one Sensors (heat or smoke)
White

FD-Z2

Black

This diagram shows only one zone

In +

Com -

Out +

R

Supply voltage @ 12vdc Maximum sensors = 14 per zone Must use 2k2 EOL resistor
Supply voltage @ 24vdc Maximum sensors = 8 per zone Must use 5k6 EOL resistor

©