mic Plus 25 Ultrasonic Sensors with One Analogue Output
“
Specifications
- Model: mic+ Ultrasonic Sensors with one analogue output
- Variants: mic+25/IU/TC, mic+35/IU/TC, mic+130/IU/TC,
mic+340/IU/TC, mic+600/IU/TC - Measuring Range:
- mic+25: 0.35 m – 2.50 m
- mic+35: 0.40 m – 2.50 m
- mic+130: 1.10 m – 8.00 m
- mic+340: 2.00 m – 18.00 m
- mic+600: 4.00 m – 30.00 m
Product Usage
Installation Instructions
- Assemble the sensor at the installation location.
- Plug in the connector cable to the M12 connector following the
pin assignment and color coding.
Start-up Procedure
- Connect the power supply to the sensor.
- Set the parameters manually via TouchControl or use the
Teach-in procedure for adjusting detect points.
Usage Guidelines
- The mic+ sensors are used for non-contact detection of
objects. - Ensure proper synchronization if using multiple sensors with
assembly distances exceeding specified limits. - Maintain the sensor by removing thick layers of dirt that can
affect its function.
FAQ
Q: Can the mic+ sensors be used in wet environments?
A: The sensors can be used in wet environments if good
reflectors like calm water surfaces are used, ensuring proper
functionality.
Q: How do I adjust the window limits for the analogue
output?
A: The window limits can be adjusted manually using the
TouchControl interface or via the Teach-in procedure as described
in the user manual.
Q: Are there any safety considerations when installing the mic+
sensors?
A: Installation, connection, and adjustment works should only be
carried out by expert personnel to ensure safety compliance.
“`
Operating Manual
mic+ Ultrasonic Sensors with one analogue output
mic+25/IU/TC mic+35/IU/TC mic+130/IU/TC mic+340/IU/TC mic+600/IU/TC
Product description The mic+ sensor with one analogue
output measures the distance to an object within the detection zone contactless. A signal proportional to distance is created according to the adjusted window limits of the analogue characteristic curve. The sensor automatically detects the load put to the analogue output and switches to current output or voltage output respectively. All settings are done with two pushbuttons and a three-digit LED display (TouchControl). Three-colour LEDs indicate all operation conditions. Choosing between rising and falling output characteristic is possible. The sensors are adjustable manually via TouchControl or via Teach-in procedure.
Diagram 1: Set sensor parameters numerically using LED display
Useful additional functions are set in the Add-on menu.
Using the LinkControl adapter (optional accessory) and the LinkControl software for Windows®, all Teach-in and additional sensor parameter settings can be optionally undertaken.
The mic+ sensors have a blind zone in which distance measurement is not possible. The operating range indicates the distance of the sensor that can be applied with normal reflectors with sufficient function reserve. When using good reflectors, such as a calm water surface, the sensor can also be used up to its maximum range. Objects that strongly absorb (e.g. plastic foam) or diffusely reflect sound (e.g. pebble stones) can also reduce the defined operating range.
Start here
T1 + T2
Set analogue output
T1
T2
T1 + T2
T1
T2
Set sensor-close window limit in mm or cm.
T1 + T2
T1 T1 + T2
T1 T1 + T2
limit in mm or cm.
) falling (
)
output characetistic curve.
Safety Notes Read the operating instructions
prior to start-up. Connection, installation and ad-
justment works may only be carried out by expert personnel. No safety component in accordance with the EU Machine Directive, use in the area of personal and machine protection not permitted
Proper Use mic+ ultrasonic sensors are used for non-contact detection of objects.
Synchronisation If the assembly distances shown in Fig. 1 for two or more sensors are exceeded the integrated synchronisation should be used. Connect Sync/Comchannels (pin 5 at the units receptable) of all sensors (10 maximum).
mic+25… 0.35 m 2.50 m
mic+35… 0.40 m 2.50 m
mic+130… 1.10 m 8.00 m
mic+340… 2.00 m 18.00 m
mic+600… 4.00 m 30.00 m
Fig. 1: Assembly distances, indicating synchronisation/multiplex
Multiplex mode The Add-on-menu allows to assign an individual address »01« to »10« to each sensor connected via the Sync/ Com-channel (Pin5). The sensors perform the ultrasonic measurement sequentially from low to high address. Therefore any influence between the sensors is rejected. The address »00« is reserved to synchronisation mode and deactivates the multiplex mode. To use synchronised mode all sensors must be set to address »00«.
Installation Assemble the sensor at the installa-
tion location. Plug in the connector cable to the
M12 connector, see Fig. 2.
2
1
35 4
2
I/U
5
Sync/Com
Fig. 2: Pin assignment with view onto sensor plug and colour coding of the microsonic connection cable
Start-up Connect the power supply. Set the parameters of the sensor
manually via TouchControl (see Fig. 3 and Diagram 1) or use the Teach-in procedure to adjust the detect points (see Diagram 2).
cm mm %
Measuring Range
3-digit LED-display LED D1 and D2
T1 D1D2 T2
Push-buttons T1 and T2
Fig. 3: TouchControl/LED display
Factory setting mic+ sensors are delivered factory made with the following settings: Rising analogue characteristic Window limits for the analogue
output set to blind zone and operating range Measurement range set to maximum range
Maintenance mic+ sensors work maintenance free. Small amounts of dirt on the surface do not influence function. Thick layers of dirt and caked-on dirt affect sensor function and therefore must be removed.
Notes mic+ sensors have internal tempe-
rature compensation. Because the sensors heat up on their own, the temperature compensation reaches its optimum working point after approx. 30 minutes of operation. If an object is within the set window limits of the analogue output, then LED D1 lights up green, if the object is outside the window limits, then LED D1 lights up red. The load put to the analogue output is detected automatically when turning supply voltage on. During normal operating mode, the measured distance value is displayed on the LED-indicator in mm (up to 999 mm) or cm (from 100 cm). Scale switches automatically and is indicated by a point on top of the digits. Alternatively a percentage scale may be set in the add-on menu. In this connection 0 % and 100 % correspond to the set window limits of the analogue output. If no objects are placed within the detection zone the LED-indicator shows » «. The sensor can be set to its factory setting, see Diagram 3. If no push-buttons are pressed for 20 seconds during parameter setting mode the made changes are stored and the sensor returns to normal operating mode.
Show parameters In normal operating mode shortly
push T1. The LED display shows »PAr.« Each time you tap push-button T1 the actual settings of the analogue output are shown.
HM 2308
T1
T2
T1 + T2
Ready
Diagram 2: Set sensor parameters via Teach-in procedure
1
Teach-in analogue output 2
Set window limits
Set rising/falling output characteristic curve
Place object at position 1 .
Press T1 until »IU« is shown.
Current measuring value Place object at position 2 . Current measuring value Press T1 until »End« is shown.
Press T1 until countdown passed from »8 « to »0« and symbol for
rising/falling characteristicis displayed. rising/falling characteristis
falling/rising characteristis
To change output characteristic press T1.
Press T1 and T2 simultaneously until »End« is displayed.
Normal operating mode
Diagram 4: Useful additional functions in Add-on menu (for experienced users only, settings not required for standard applications)
Start here
T1 + T2
Diagram 3: Key lock and factory setting
Activate/deactivate TouchControl
Reset to factory setting
Turn supply voltage OFF.
Turn supply voltage OFF.
While pressing T1 turn supply voltage ON.
While pressing T1 turn supply voltage ON.
Keep T1 pressed for about 3 s until »on« or »off«
»on« or »off«
»off« or »on« To activate or deactivate press T1.
Keep T1 pressed for about 13 s until »rESEt« has
passed through the display.
Don´t press any push-button for 20 s.
Normal operating mode
T1
T2
T1
T2
T1
T2
T1
T2
T1
T2
T1
T2
T1
T2
T1
T2
T1
T2
T1
T2
T1
T2
T1
T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1
T2 T1
T2 T1
T2 T1
T2 T1
T2 T1
T2 T1
T2 T1
T2 T1
T2 T1
T2 T1
T2 T1
T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T1 + T2
T2
T1
T1 + T2
Ready
»C03«: Display off
«: Display in mum measured val-
«: Display in mum measured val-
»I«: current output
»F00«: no filter »F01«: standard filter »F02«: averaging filter
»F04«: background filter
»P09«: strong filter
mic+35/…, 999 cm for
mic+600/…
mic+ 25… and mic+35… and
»E01«: high »E02«: standard »E03«: slight
Lower power mode
Display mode
Choose current/ voltage output
Measurement filter
strength
Response time
Foreground suppression
Multiplex mode device addressing
highest address
Measurement range
Calibration display
Detection zone sensitivity
Technical data
mic+25…
mic+35…
mic+130…
mic+340…
mic+600…
M12x1 M12x1 M12x1 M12x1
Ø47.5 M12x1
Ø6 5
1
2
U
4
5
3
1 analogue output
+UB I/U
Sync/Com UB
TouchControl LED-Display
36 width A/F
2 Buttons M30x1.5
5
2 Duo-LEDs
51 84
blind zone 0 to 30 mm
operating range 250 mm
maximum range 350 mm
angle of beam spread see detection zone
transducer frequency 320 kHz
resolution 0.025 to 0.10 mm, depending on the
window limits
detection zones
for different objects:
The dark grey areas represent the
0 cm
zone where it is easy to recognise
the normal reflector (round bar).
This indicates the typical operating
5 cm
range of the sensors. The light
Plate
grey areas represent the zone where a very large reflector for instance a plate can still be recognised. The requirement here is
for an optimum alignment to the
10 cm Round bar ø 10 mm
15 cm
sensor. It is not possible to evalua-
te ultrasonic reflections outside this area.
20 cm
25 cm
30 cm
35 cm
10 cm 5 cm 0 cm 5 cm 10 cm 20 cm 10 cm 0 cm 10 cm 20 cm 0.8 m 0.4 m 0 m 0.4 m 0.8 m 1.6 m 0.8 m 0 m 0.8 m 1.6 m 2.4 m 1.2 m 0 m 1.2 m 2.4 m
TouchControl LED-Display
36 width A/F
2 Buttons M30x1.5
5
2 Duo-LEDs
51
84
0 bis 65 mm 350 mm 600 mm see detection zone 400 kHz 0.025 to 0.17 mm, depending on the window limits
0 cm
Plate
10 cm 20 cm
Round bar ø 10 mm
30 cm 35 cm 40 cm
50 cm 60 cm
TouchControl LED-Display
36 width A/F
2 Buttons M30x1.5
5
2 Duo-LEDs
TouchControl LED-Display
36 width A/F
2 Buttons M30x1.5
5
2 Duo-LEDs
51 84
0 to 200 mm 1,300 mm 2,000 mm see detection zone 200 kHz 0.18 to 0.57 mm, depending on the window limits
0 m
Plate
0.4 m
0.8 m Round bar ø 10 mm
1.2 m 1.3 m
1.6 m
2 m
69 102
19.5 33
0 to 350 mm 3,400 mm 5,000 mm see detection zone 120 kHz 0.18 to 1.5 mm, depending on the window limits
0 m
Plate
0.8 m
1.6 m Round bar ø 27 mm
2.4 m
3.2 m 3.4 m
4 m
4.8 m
5.6 m
TouchControl LED-Display
36 width A/F
2 Buttons M30x1.5
5
2 Duo-LEDs
72 105
0 to 600 mm 6,000 mm 8,000 mm see detection zone 80 kHz 0.18 to 2.4 mm, depending on the window limits
22.5 36
0 m
Plate
1.2 m
2.4 m Round bar ø 27 mm
3.6 m
4.8 m
6 m
7.2 m
8.4 m
reproducibility ±0.15 %
±0.15 %
±0.15 %
±0.15 %
±0.15 %
accuracy ±1 % (Temperature drift internal compensated, may ±1 % (Temperature drift internal compensated, may ±1 % (Temperature drift internal compensated, may ±1 % (Temperature drift internal compensated, may ±1 % (Temperature drift internal compensated, may
be deactivated 2), 0.17%/K without compensation) be deactivated 2), 0.17%/K without compensation) be deactivated 2), 0.17%/K without compensation) be deactivated 2), 0.17%/K without compensation) be deactivated 2), 0.17%/K without compensation)
operating voltage UB 9 to 30 V DC, short-circuit-proof, Class 2
9 to 30 V DC, short-circuit-proof, Class 2
9 to 30 V DC, short-circuit-proof, Class 2
9 to 30 V DC, short-circuit-proof, Class 2
9 to 30 V DC, short-circuit-proof, Class 2
voltage ripple ±10 %
±10 %
±10 %
±10 %
±10 %
no-load supply current 80 mA
80 mA
80 mA
80 mA
80 mA
housing Brass sleeve, nickel-plated, plastic parts: PBT, TPU; Brass sleeve, nickel-plated, plastic parts: PBT, TPU; Brass sleeve, nickel-plated, plastic parts: PBT, TPU; Brass sleeve, nickel-plated, plastic parts: PBT, TPU; Brass sleeve, nickel-plated, plastic parts: PBT, TPU;
Ultrasonic transducer: polyurethane foam,
Ultrasonic transducer: polyurethane foam,
Ultrasonic transducer: polyurethane foam,
Ultrasonic transducer: polyurethane foam,
Ultrasonic transducer: polyurethane foam,
epoxy resin with glass content
epoxy resin with glass content
epoxy resin with glass content
epoxy resin with glass content
epoxy resin with glass content
class of protection to EN 60529 IP 67
IP 67
IP 67
IP 67
IP 67
norm conformity EN 60947-5-2
EN 60947-5-2
EN 60947-5-2
EN 60947-5-2
EN 60947-5-2
type of connection 5-pin initiator plug, PBT
5-pin initiator plug, PBT
5-pin initiator plug, PBT
5-pin initiator plug, PBT
5-pin initiator plug, PBT
controls 2 push-buttons (TouchControl)
2 push-buttons (TouchControl)
2 push-buttons (TouchControl)
2 push-buttons (TouchControl)
2 push-buttons (TouchControl)
indicators 3-digit LED display, 2 three-colour LEDs
3-digit LED display, 2 three-colour LEDs
3-digit LED display, 2 three-colour LEDs
3-digit LED display, 2 three-colour LEDs
3-digit LED display, 2 three-colour LEDs
programmable with TouchControl and LinkControl
with TouchControl and LinkControl
with TouchControl and LinkControl
with TouchControl and LinkControl
with TouchControl and LinkControl
operating temperature 25 to +70 °C
25 to +70 °C
25 to +70 °C
25 to +70 °C
25 to +70 °C
storage temperature 40 to +85 °C
40 to +85 °C
40 to +85 °C
40 to +85 °C
40 to +85 °C
weight 150 g
150 g
150 g
210 g
270 g
response time 1) 32 ms
64 ms
92 ms
172 ms
240 ms
time delay before availability <300 ms
<300 ms
<300 ms
<380 ms
<450 ms
order No. mic+25/IU/TC current output 4 to 20 mA RL 100 at 9 V UB 20 V
RL 500 at UB 20 V Rising/falling output characteristic voltage output 0 to 10 V RL 100 k at UB 15 V, short-circuit-proof
Rising/falling output characteristic
1) Can be programmed via TouchControl and LinkControl. 2) Can be deactivated via LinkControl.
mic+35/IU/TC
RL 100 at 9 V UB 20 V RL 500 at UB 20 V Rising/falling output characteristic
RL 100 k at UB 15 V, short-circuit-proof Rising/falling output characteristic
mic+130/IU/TC
RL 100 at 9 V UB 20 V RL 500 at UB 20 V Rising/falling output characteristic
RL 100 k at UB 15 V, short-circuit-proof Rising/falling output characteristic
mic+340/IU/TC
RL 100 at 9 V UB 20 V RL 500 at UB 20 V Rising/falling output characteristic
RL 100 k at UB 15 V, short-circuit-proof Rising/falling output characteristic
mic+600/IU/TC
RL 100 at 9 V UB 20 V RL 500 at UB 20 V Rising/falling output characteristic
RL 100 k at UB 15 V, short-circuit-proof Rising/falling output characteristic
microsonic GmbH / Phoenixseestraße 7 / 44263 Dortmund / Germany / T +49 231 975151-0 / F +49 231 975151-51 / E info@microsonic.de / W microsonic.de The content of this document is subject to technical changes. Specifications in this document are presented in a descriptive way only. They do not warrant any product features.
Enclosure Type 1 The proximity switches shall be used with a For use only in industrial Listed (CYJV/7) cable/connector assembly ramachinery NFPA 79 applications. ted minimum 32 Vdc, minimum 290 mA, in
the final installation.
Registration no. 75330-19
Approved on June 25th, 2019
MV-DO-041945-762551
Documents / Resources
![]() |
microsonic mic Plus 25 Ultrasonic Sensors with One Analogue Output [pdf] Instruction Manual mic 25-IU-TC, mic 35-IU-TC, mic 130-IU-TC, mic 340-IU-TC, mic 600-IU-TC, mic Plus 25 Ultrasonic Sensors with One Analogue Output, mic Plus 25, Ultrasonic Sensors with One Analogue Output, One Analogue Output, Analogue Output |