RAXN-4000LCDGC Network Remote Graphic Color Annunciator and Main Display
“
Specifications and Features
Product Name: RAXN-4000LCDGC Network Remote Graphic Color
Annunciator and Main Display
- Model: RAXN-4000LCDGC
- Display Type: Graphic Color LCD
- Remote Connectivity: Network-enabled
- Main Features: Annunciator and Main Display functions
Installation Instructions
Dimensions of Enclosures
Enclosure Model | Height (in.) | Width (in.) | Horizontal Mounting Hole dim. A (in.) | Vertical Mounting Hole dim. B (in.) | Number of Chassis it holds |
---|---|---|---|---|---|
BB-1001D/DR/DS | 9.0 | 12.75 | 9.95 | 7.5 | 1 |
FAQ
Frequently Asked Questions
Q: How do I set the address for the RAXN-4000LCDGC?
A: Each unit must be assigned a unique address using the dials
SW4 and SW5 on the back of the unit. Turn SW4 to the desired ONES
digit and SW5 to the desired TENS digit within the valid range of
33 to 39.
Q: How many display frames can be connected to the
RAXN-4000LCDGC?
A: The unit supports up to 41 frames in total. P5 connects to
the first set of display modules, P4 is for expansion up to 14
frames, and P6 for additional 14 frames beyond that.
“`
RAXN-4000LCDGC
Network Remote Graphic Color Annunciator
and Main Display
Installation and Wiring Manual
LT-6738MP Rev. 1.1 July 2025
Table of Contents
1.0 Introduction
4
2.0 Installation Instructions
4
3.0 Connectors, Jumpers, and Switches
6
4.0 Address Settings
7
5.0 Cable Connections
8
6.0 Wiring Instructions
9
7.0 Specifications and Features
10
8.0 Applications
12
9.0 Warranty and Warning Information
14
3
1.0
Introduction
The RAXN-4000LCDGC is MGC’s network remote graphic color annunciator and main display. It provides an exact replica of the main FleX-NetTM FX-4000 and MMXTM-4000 Fire Alarm Panel display (except with an 8-event 16-line color graphical display) at a remote location or as a main display. It is equipped with a simple menu system complete with a directional keypad and switches for Enter, Menu, Cancel and Info. The RAXN-4000LCDGC supports up to a maximum of 41 frames: 13 for the first header P5, and 14 frames for each header P4 and P6. A frame is a measure of display capacity. Each display module has its own frame measure. See section 7.3 on page 10 for the list of available modules and their frames. There are five types of enclosures available (shown in Table 1). The RAXN-4000LCDGC may also be mounted in the BB-5008 and the BB-5014 backboxes as part of a central location or node, and it may be mounted in the inner deadfront chassis of all FleX-NetTM FX-4000 and MMXTM-4000 fire alarm enclosures as a main display.
2.0 Installation Instructions
Table 1 Dimensions of enclosures
Enclosure Model
Height of enclosure
H (in.)
BB-1001D/DR/DS (MMX-BB-1001D/DR) BB-1002D/DR/DS (MMX-BB-1002D/DR) BB-1003D/DR/DS (MMX-BB-1003D/DR) BB-1008D/DR/DS (MMX-BB-1008D/DR) BB-1012D/DR/DS (MMX-BB-1012D/DR)
9.0″ 18.0″ 26.5″ 33.0″ 45.0″
Width of enclosure
(in.)
12.75″ 12.75″ 12.75″ 22.5″ 22.5″
Horizontal Mounting Hole dim.
A (in.) 9.95″ 9.95″ 9.95″ 9.95″ 9.95″
Vertical Mounting Hole dim.
B (in.) 7.5″ 16.5″ 24.9″ 35.2″ 52.0″
Number of chassis it
holds
1 2 3 8 12
BACKBOX CAN BE MOUNTED WITH STANDARD 4″ X 4″ ELECTRICAL BOXES
BACKBOX
WALL
12.75″
B
DOOR
H A
1.85″
BB-1001D/DR/DS BACKBOX IS SHOWN
RAXN-4000LCDGC ANNUNCIATOR
GB-1002 GUARD BRACKET
Figure 1 Mounting RAXN-4000LCDGC in BB-1001D
4
#6-32 HEXNUTS
Inner deadfront chassis
4 HD-362 standoffs
CH-980B BRACKET
RAXN-4000LCDGC
(order part # RAXN-UB-BRACKET)
4 screws
Figure 2 Mounting RAXN-4000LCDGC in a fire alarm enclosure
i
Note: If the RAXN-4000LCDGC installed as a main display, close JW1 on the front to silence the buzzer. See section 3.1.
5
3.0
3.1
Connectors, Jumpers, and Switches
Front
Table 2 Connectors, jumpers, and switches on the front
Jumper or switch
JW1
JW2 and JW3
JW4
JW5 JW6 SW1
Function
CLOSE to silence the buzzer. By default it is OPEN (OFF). Close if the RAXN4000LCDGC is installed in the FACU as a main display. If there are problems with RS-485 communication, CLOSE both JW2 and JW3 on only one RAXN-4000LCDGC connected by RS-485. By default these jumpers are OPEN (OFF). If the RAXN-4000LCDGC is the last controller connected by RS-485, CLOSE JW4 if an external end-of-line 120 resistor is not available. By default this jumper is OPEN (OFF). Leave CLOSED (shorted) (for watchdog timer). Leave CLOSED (shorted). Leave OFF.
P5 connects to the first set of display modules, up to a total of 13 frames. P4 is an expansion connector for the next 14 frames, and P6 for the next 14 frames beyond that for a maximum of 41 frames.
RS-485 terminals Not used 24V power terminals
P4
Buzzer
JW1
P5
P6
TS1
JP1 ON TS3
JW4
JW2
JW3
OFF
SW1 JW6 JW5
Figure 3 Front of RAXN-4000LCDGC
6
3.2
4.0
Back
Table 3 Connectors, jumpers, and switches on the back
Jumper or switch
JW1 JW2 JW3 JW4 SW1 SW2 SW3 SW4 SW5
Leave OPEN (OFF). Leave OPEN (OFF). Leave OPEN (OFF). Leave OPEN (OFF). Reset button. Leave OFF. Leave OFF. ONES dial for setting the address. TENS dial for setting the address.
Function
TS1-TS4 and JP1 are not used
TS3
TS4
SW1
JW1
JP1
ON SW2
TS1
JW2
JW4JW3 TS2
SW4 SW5
ON
SW3
OFF
CN1
Not used
Figure 4 Back of RAXN-4000LCDGC
Address Settings
Each RAXN-4000LCDGC must be assigned a unique address on the 2 dials SW4 and SW5 located on the back of the unit.
SW4
ONES
SW5
TENS
Figure 5 Address dials For example, to set the address 34, turn SW4 to 4 and SW5 to 3. The valid range of addresses is 33 to 39.
7
5.0
i
Cable Connections
On the RAX-1048TZDS Adder
Annunciator Chassis:
P2
P1: Connects to the RAXN4000LCDGC main annunciator chassis, or to the previous display modules RAX-1048TZDS, IPS2424DS or other display adder.
P2: Connects to the next RAX1048TZDS, IPS-2424DS or other display adder.
Adder Display Module, for example RAX-1048TZDS Adder Annunciator or IPS-2424DS Programmable Input Switches Module
P1
RS-485 TERMINALS
POWER TERMINALS
On the IPS-2424DS Programmable Input Switches Module (shown here as an example):
P1: Connects to the RAXN4000LCDGC, or to the previous display module.
P2: Connects to the next display module.
RAXN-4000LCDGC GRAPHIC ANNUNCIATOR BOARD
On the RAXN-4000LCDGC Chassis:
P5: Connects to the first display module. This connector can support up to 13 frames.
P4: Connects to next 14 frames of display modules.
P6: Connects to next 14 frames of display modules.
If all headers are used, the RAXN-4000LCDGC can support up to a maximum of 41 frames.
Terminals: See section 6 on page 9 for details.
Note: If the RAXN-4000LCDGC is the last controller connected by RS-485, close JW4 if an external end-of-line 120 resistor is not available. See section 3.1 on page 6.
8
6.0
Wiring Instructions
MGC recommends 18-22 AWG unshielded twisted pair for the RS-485 wiring, as shown in Figure 6. The maximum RS-485 wiring run between each device is 1000 feet (305 m). The maximum RS-485 wiring run between the first and last node is 4000 feet (1219 m). The maximum capacitance conductor to conductor is 13 pF/foot.
The RS-485 wiring from the fire alarm control panel to the annunciators must be point-to-point from the fire alarm panel to the first annunciator, then to the next annunciator, and so on. No star wiring or T-tapping is allowed. If the RAXN-4000LCDGC is the last controller connected by RS-485, close JW4 if an external end-of-line 120 resistor is not available. See section 3.1 on page 6.
RS-485 FROM FIRE ALARM MAIN BOARD OR PREVIOUS ANNUNCIATOR (UNSHIELDED TWISTED PAIR)
24 VDC POWER TO NEXT ANNUNCIATOR
RS-485 TO NEXT ANNUNCIATOR (UNSHIELDED TWISTED PAIR)
24 VDC POWER FROM FIRE ALARM MAIN BOARD OR PREVIOUS ANNUNCIATOR
íC+ í C+
+í í+
Figure 6
RS-485 INPUT
RS-485 OUTPUT
24 VDC 24 VDC OUTPUT INPUT
RS-485 and power wiring
The 24 VDC field wiring needs to be of an appropriate gauge for the number of annunciators and the total wiring run length.
i
Note: All circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.
!
Attention: Accidentally connecting any of the 24 VDC wires to the RS-485 wiring will result in damage to the annunciator and the fire alarm control panel to which
it is connected.
Table 4 Power Wiring length and size
Total Maximum Current for all Annunciators
Amperes 0.12 0.30 0.60 0.90 1.20 1.50 1.70
18 AWG
ft 1180 470 235 156 118 94 78
m 360 143 71 47 36 29 24
Maximum Wiring Run to Last Annunciator
16 AWG
14 AWG
12 AWG
ft 1850 750 375 250 185 150 125
m 567 229 114 76 56 46 38
ft 3000 1200 600 400 300 240 200
m 915 366 183 122 91 73 61
ft 4250 1900 850 570 425 343 285
m 1296 579 259 174 129 105 87
Max. Loop Resistance
ohms 15 6 3 2 1.5 1.2 1.0
9
7.0
7.1
i
7.2 7.3
10
Specifications and Features
Enclosure Models
BB-1001D/DR/DB/DS (MMX-BB-1001D/DR): Backbox for one annunciator chassis with keylock door.
BB-1002D/DR/DB/DS (MMX-BB-1002D/DR): Backbox for up to two annunciator chassis with keylock door.
BB-1003D/DR/DB/DS (MMX-BB-1003D/DR): Backbox for up to three annunciator chassis with keylock door.
BB-1008D/DR/DB/DS (MMX-BB-1008D/DR): Backbox for up to eight annunciator chassis with keylock door.
BB-1012D/DR/DB/DS (MMX-BB-1012D/DR): Backbox for up to twelve annunciator chassis with keylock door.
Note:
Finish: Backbox painted black, white painted door (standard), suffix “R” for red painted door, suffix “B” for black painted door and suffix “S” for stainless steel finish. Material: BB-1001D/DR/DB/DS (MMX-BB-1001D/DR), BB-1002D/DR/DB/DS (MMXBB-1002D/DR) 18 G.A. cold rolled steel (CRS), doors are 18 G.A. BB-1003D/DR/DB/DS (MMX-BB-1003D/DR) 16 G.A. CRS, door is 18 G.A. BB-1008D/DR/DB/DS (MMX-BB-1008D/DR), BB-1012D/DR/DB/DS (MMX-BB1012D/DR) 16 G.A cold rolled steel (CRS), doors are 14 GA.
See section 2 on page 4 for enclosure dimensions.
RAXN-4000LCDGC Specifications
· 24VDC nominal. · Interconnects via wiring to the Network Fire Alarm Panel or to previous annunciators
(see section 6 on page 9). · Provides exact functions as the Network Fire Alarm main display. · Standby: 225 mA Max., All LEDs ON: 235 mA Max.
Adder Display Modules
RAX-1048TZDS Adder Annunciator (3 frames)
· Interconnects via one ribbon cable from RAXN-4000LCDGC or previous display module and to the next display module.
· Annunciation of up to 48 additional points. · Standby: 22 mA Max., All LEDs ON: 262 mA Max.
IPS-2424DS 24 Programmable Input Switches Module (2 frames)
· Interconnects via one ribbon cable from RAXN-4000LCDGC or from previous display module and to the next display module.
· Annunciation of up to 48 additional points. · Standby: 5 mA Max., All LEDs ON: 22 mA Max.
IPS-4848DS 48 Programmable Input Switches Module (4 frames)
· Interconnects via one ribbon cable from RAXN-4000LCDGC or from previous display module and to the next display module.
· Annunciation of up to 96 additional points. · Standby: 10 mA Max., All LEDs ON: 22 mA Max.
FDX-008W(KI) Smoke Control Fan Damper Module (1 frame)
· Interconnects via one ribbon cable from RAXN-4000LCDGC or from previous display module and to the next display module.
· Provides switch operation of 8 fan damper zones or operation of 7 fan damper zones and one keyswitch operation.
· Standby: 15 mA Max., All LEDs ON: 35 mA Max.
AGD-048 Adder Graphic Module (1 frame)
· Interconnects via one ribbon cable from RAXN-4000LCDGC or from previous display module and to the next display module.
· Annunciation of up to 48 Points. · Standby: 25 mA, Alarm: 2.4 A Max.
QAZT-5302DS 24 Zone Paging and Telephone Selector Panel (2 frames)
· Interconnects via one ribbon cable from RAXN-4000LCDGC or from previous display module and to the next display module.
· Annunciation of up to 24 audio zones. · Standby: 5 mA, Alarm: 22 A Max.
QAZT-5348DS 48 Zone Paging and Telephone Selector Panel (4 frames)
· Interconnects via one ribbon cable from RAXN-4000LCDGC or from previous display module and to the next display module.
· Annunciation of up to 48 audio zones. · Standby: 10 mA, Alarm: 22 A Max.
QMP-5101N(V) Network Master Paging Control Panel (1 frame)
· Interconnects via one ribbon cable from RAXN-4000LCDGC or from previous display module and to the next display module.
· Standby: 3 mA, Alarm: 7 A Max.
QMT-5302N(V) Network Master Telephone Control Panel (1 frame)
· Interconnects via one ribbon cable from RAXN-4000LCDGC or from previous display module and to the next display module.
· Standby: 1 mA, Alarm: 13 A Max.
11
8.0
8.1
Applications
Operation of RAXN-4000LCDGC as a Main Display and Remote Display
When RAXN-4000LCDGC functions as the main display and a second RAXN-4000LCDGC functions as a remote display, then only the main RAXN-4000LCDGC must be connected to the FACU’s auxiliary power. All remote displays must be powered by a different power source, such as the 4-wire power supply.
FACU
RAXN-4000LCDGC installed as main display powered by AUX power
All remote displays powered by 4-wire power supply or a di erent power source
RS-485
RAXN-4000LCDGC installed as remote display
Remote enclosure
Figure 7 RAXN-4000LCDGC as both main display and remote display
8.2
Operation of RAXN-4000LCDGC as a Main Display in a
Separate Enclosure
When RAXN-4000LCDGC is installed in a separate enclosure but functions as the main display, then the connections between the FACU and the RAXN-4000LCDGC must be in the same room within 20 feet (6.1 m) in the USA or 18 m in Canada, and enclosed in conduit or equivalently protected against mechanical injury.
FACU with no display
Wiring max. length 20 ft (6.1 m) in USA or 18 m in Canada and enclosed in conduit
AUX power RS-485
RAXN-4000LCDGC installed as main display
Remote enclosure
Figure 8 Operation of RAXN-4000LCDGC as a main display in a separate enclosure
12
8.3
Operation of RAXN-4000LCDGC as an Ancillary Device as
required by ULC S527
For use of RAXN-4000LCDGC as an ancillary device as required by ULC S527, the following manual controls must be disabled:
· Signal Silence · Total Evacuation (General Alarm) · Acknowledge · Fire Drill · System Reset Only the Lamp Test button will remain active. · In the MGC Configurator, the Type column for Signal Silence, Total Evacuation,
Acknowledge, Fire Drill and System Reset is Common Ctrl by default.
Figure 9 Default control assignments
1. Change the Type to <unassigned> for Signal Silence, Total Evacuation, Acknowledge, Fire Drill and System Reset.
Figure 10 All controls unassigned except for Lamp Test 2. Leave Lamp Test as Common Ctrl. 3. In addition, select the Buzzer is Local checkbox for the RAXN-4000LCDGC. When this checkbox is selected, Buzzer Silence will silence only the local buzzer on the RAXN4000LCDGC, and not any other buzzers.
Figure 11 Buzzer is Local
13
9.0 Warranty and Warning Information
WARNING!
Please read this document CAREFULLY, as it contains important warnings, life-safety, and practical information about all products manufactured by the Mircom Group of Companies, including Mircom and Secutron branded products, which shall include without limitation all fire alarm, nurse call, building automation and access control and card access products (hereinafter individually or collectively, as applicable, referred to as “Mircom System”).
NOTE TO ALL READERS:
1. Nature of Warnings. The within warnings are communicated to the reader out of an abundance of caution and create no legal obligation for Mircom Group of Companies, whatsoever. Without limiting the generality of the foregoing, this document shall NOT be construed as in any way altering the rights and obligations of the parties, governed by the legal documents that apply in any given circumstance.
2. Application. The warnings contained in this document apply to all Mircom System and shall be read in conjunction with:
a. the product manual for the specific Mircom System that applies in given circumstances;
b. legal documents that apply to the purchase and sale of a Mircom System, which may include the company’s standard terms and conditions and warranty statements;
c. other information about the Mircom System or the parties’ rights and obligations as may be application to a given circumstance.
3. Security and Insurance. Regardless of its capabilities, no Mircom System is a substitute for property or life insurance. Nor is the system a substitute for property owners, renters, or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation. Building automation systems produced by the Mircom Group of Companies are not to be used as a fire, alarm, or life-safety system.
NOTE TO INSTALLERS:
All Mircom Systems have been carefully designed to be as effective as possible. However, there are circumstances where they may not provide protection. Some reasons for system failure include the following. As the only individual in contact with system users, please bring each item in this warning to the attention of the users of this Mircom System. Failure to properly inform system end-users of the circumstances in which the system might fail may result in over-reliance upon the system. As a result, it is imperative that you properly inform each customer for whom you install the system of the possible forms of failure:
4. Inadequate Installation. All Mircom Systems must be installed in accordance with all the applicable codes and standards in order to provide adequate protection. National standards require an inspection and approval to be conducted by the local authority having jurisdiction following the initial installation of the system and following any changes to the system. Such inspections ensure installation has been carried out properly.
5. Inadequate Testing. Most problems that would prevent an alarm a Mircom System from operating as intended can be discovered by regular testing and maintenance. The complete system should be tested by the local authority having jurisdiction immediately after a fire, storm, earthquake, accident, or any kind of construction activity inside or outside the premises.
14
The testing should include all sensing devices, keypads, consoles, alarm indicating devices and any other operational devices that are part of the system.
NOTE TO USERS:
All Mircom Systems have been carefully designed to be as effective as possible. However, there are circumstances where they may not provide protection. Some reasons for system failure include the following. The end user can minimize the occurrence of any of the following by proper training, testing and maintenance of the Mircom Systems:
6. Inadequate Testing and Maintenance. It is imperative that the systems be periodically tested and subjected to preventative maintenance. Best practices and local authority having jurisdiction determine the frequency and type of testing that is required at a minimum. Mircom System may not function properly, and the occurrence of other system failures identified below may not be minimized, if the periodic testing and maintenance of Mircom Systems is not completed with diligence and as required.
7. Improper Operation. It is important that all system users be trained in the correct operation of the alarm system and that they know how to respond when the system indicates an alarm. A Mircom System may not function as intended during an emergency situation where the user is unable to operate a panic or emergency switch by reason of permanent or temporary physical disability, inability to reach the device in time, unfamiliarity with the correct operation, or related circumstances.
8. Insufficient Time. There may be circumstances when a Mircom System will operate as intended, yet the occupants will not be protected from the emergency due to their inability to respond to the warnings in a timely manner. If the system is monitored, the response may not occur in time enough to protect the occupants or their belongings.
9. Carelessness or Safety Hazards. Moreover, smoke detectors may not provide timely warning of fires caused by carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits or children playing with matches or arson.
10. Power Failure. Some Mircom System components require adequate electrical power supply to operate. Examples include: smoke detectors, beacons, HVAC, and lighting controllers. If a device operates only by AC power, any interruption, however brief, will render that device inoperative while it does not have power. Power interruptions of any length are often accompanied by voltage fluctuations which may damage Mircom Systems or other electronic equipment. After a power interruption has occurred, immediately conduct a complete system test to ensure that the system operates as intended.
11. Battery Failure. If the Mircom System or any device connected to the system operates from batteries it is possible for the batteries to fail. Even if the batteries have not failed, they must be fully charged, in good condition, and installed correctly. Some Mircom Systems use replaceable batteries, which have a limited life-span. The expected battery life is variable and in part dependent on the device environment, usage and type. Ambient conditions such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the expected battery life. Moreover, some Mircom Systems do not have a battery monitor that would alert the user in the event that the battery is nearing its end of life. Regular testing and replacements are vital for ensuring that the batteries function as expected, whether or not a device has a low-battery monitor.
12. Physical Obstructions. Motion sensors that are part of a Mircom System must be kept clear of any obstacles which impede the sensors’ ability to detect movement. Signals being communicated by a Mircom System may not reach the receiver if an item (such as metal, water, or concrete) is placed on or near the radio path. Deliberate jamming or other inadvertent radio signal interference can also negatively affect system operation.
15
13. Wireless Devices Placement Proximity. Moreover all wireless devices must be a minimum and maximum distance away from large metal objects, such as refrigerators. You are required to consult the specific Mircom System manual and application guide for any maximum distances required between devices and suggested placement of wireless devices for optimal functioning.
14. Failure to Trigger Sensors. Moreover, Mircom Systems may fail to operate as intended if motion, heat, or smoke sensors are not triggered.
a. Sensors in a fire system may fail to be triggered when the fire is in a chimney, walls, roof, or on the other side of closed doors. Smoke and heat detectors may not detect smoke or heat from fires on another level of the residence or building. In this situation the control panel may not alert occupants of a fire.
b. Sensors in a nurse call system may fail to be triggered when movement is occurring outside of the motion sensors’ range. For example, if movement is occurring on the other side of closed doors or on another level of the residence or building the motion detector may not be triggered. In this situation the central controller may not register an alarm signal.
15. Interference with Audible Notification Appliances. Audible notification appliances may be interfered with by other noise sources such as stereos, radios, televisions, air conditioners, appliances, or passing traffic. Audible notification appliances, however loud, may not be heard by a hearing-impaired person.
16. Other Impairments. Alarm notification appliances such as sirens, bells, horns, or strobes may not warn or waken a sleeping occupant if there is an intervening wall or door. It is less likely that the occupants will be alerted or awakened when notification appliances are located on a different level of the residence or premise.
17. Software Malfunction. Most Mircom Systems contain software. No warranties are provided as to the software components of any products or stand-alone software products within a Mircom System. For a full statement of the warranties and exclusions and limitations of liability please refer to the company’s standard Terms and Conditions and Warranties.
18. Telephone Lines Malfunction. Telephone service can cause system failure where telephone lines are relied upon by a Mircom System. Alarms and information coming from a Mircom System may not be transmitted if a phone line is out of service or busy for a certain period of time. Alarms and information may not be transmitted where telephone lines have been compromised by criminal tampering, local construction, storms or earthquakes.
19. Component Failure. Although every effort has been made to make this Mircom System as reliable as possible, the system may fail to function as intended due to the failure of a component.
20. Integrated Products. Mircom System might not function as intended if it is connected to a non-Mircom product or to a Mircom product that is deemed non-compatible with a particular Mircom System. A list of compatible products can be requested and obtained.
Warranty
Purchase of all Mircom products is governed by:
https://www.mircom.com/product-warranty
https://www.mircom.com/purchase-terms-and-conditions
https://www.mircom.com/software-license-terms-and-conditions
16
17
© Mircom 2025 Printed in Canada Subject to change without prior notice
www.mircom.com
CANADA – Main Office 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 888-660-4655 Fax: 905-660-4113
U.S.A 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Tel: 905-660-4655 888-660-4655 Fax: 905-660-4113
Documents / Resources
![]() |
MGC RAXN-4000LCDGC Network Remote Graphic Color Annunciator and Main Display [pdf] Installation Guide LT-6738MP, RAXN-4000LCDGC, RAXN-4000LCDGC Network Remote Graphic Color Annunciator and Main Display, Network Remote Graphic Color Annunciator and Main Display, Color Annunciator and Main Display, Annunciator and Main Display, Main Display |