Specifications

  • Model: RSP-2000-12 / RSP-2000-24 / RSP-2000-48
  • DC Voltage: 12V / 24V / 48V
  • Rated Power: 1200W / 1920W / 2016W
  • Efficiency: 87% typical
  • Input Voltage Range: 90 ~ 264VAC
  • Output Ripple & Noise: 150mVp-p max.
  • Power Factor: 0.97 typical at full load
  • Dimensions: 295 x 127 x 41mm (L x W x H)

Product Usage Instructions

Installation

  1. Ensure input power is within the specified voltage range (90 ~ 264VAC).
  2. Connect the output terminals to your device following the correct polarity.
  3. Securely mount the power supply in a well-ventilated area using appropriate mounting hardware.

Operation

  1. Apply AC power to the unit within the specified voltage range.
  2. If required, program the output voltage within the adjustable range.
  3. Monitor the device for any abnormal behavior or alarm signals.

Maintenance

  1. Regularly inspect the power supply for dust and debris accumulation.
  2. Ensure proper airflow around the unit for efficient cooling.
  3. Refer to the user manual for troubleshooting steps in case of issues.

FAQ

  • Q: What are the main protections provided by the power supply?
    A: The power supply offers protections against short circuit, overload, over voltage, and over temperature conditions.
  • Q: What are the typical applications of the RSP-2000 series power supply?
    A: The power supply is commonly used in factory control, test and measurement instruments, laser machines, burn-in facilities,digital broadcasting, and RF applications.

2000W Power Supply with Single OutputMEAN-WELL-RSP-2000-series-Switching-Power-Supply- (1)

Features

  • Universal AC input / Full range
  • Built-in active PFC function
  • High efficiency up to 92%
  • Forced air cooling by built-in DC fan
  • Output voltage programmable
  • Active current sharing up to 8000W (3+1)
  • Built-in remote ON-OFF control / remote sense / auxiliary power / DC OK signal / OTP alarm signal
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Optional conformal coating
  • 5 years warranty

Applications

  • Factory control or automation apparatus
  • Test and measurement instrument
  • Laser related machine
  • Burn-in facility
  • Digital broadcasting
  • RF application
  • GTIN CODE MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description
RSP-2000 is a 2KW single output enclosed type AC/DC power supply with 1U low profile. This series operates for 90~264VAC input voltage and offers the models with the DC output mostly demanded from the industry. Each model is cooled by the built-in fan with fan speed control, working for the temperature up to 70°C. Moreover, RSP-2000 provides vast design flexibility by equipping various built-in functions such as the output programming, active current sharing, remote ON-OFF control, auxiliary power, etc.

Model Encoding / Order Information

MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (1)

SPECIFICATION

MODEL RSP-2000-12 RSP-2000-24 RSP-2000-48
 

 

 

 

 

 

 

OUTPUT

DC VOLTAGE 12V 24V 48V
RATED CURRENT 100A 80A 42A
CURRENT RANGE 0 ~ 100A 0 ~ 80A 0 ~ 42A
RATED POWER 1200W 1920W 2016W
RIPPLE & NOISE (max.) Note.2 150mVp-p 200mVp-p 300mVp-p
VOLTAGE ADJ. RANGE 10.5 ~ 14V 21 ~ 28V 42 ~ 56V
VOLTAGE TOLERANCE Note.3 ±2.0% ±1.0% ±1.0%
LINE REGULATION ±1.0% ±0.5% ±0.5%
LOAD REGULATION ±1.0% ±0.5% ±0.5%
SETUP, RISE TIME 1500ms, 60ms/230VAC at full load
HOLD UP TIME (Typ.) 16ms/230VAC at 75% load         10ms/230VAC at full load
 

 

 

 

INPUT

VOLTAGE RANGE                                      Note.4,5 90 ~ 264VAC         250 ~ 320VDC
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.) 0.97/230VAC at full load
EFFICIENCY (Typ.) 87% 90.5% 92%
AC CURRENT (Typ.)                                        Note.4 13A/115VAC         7A/230VAC 16A/115VAC         10A/230VAC 16A/115VAC         10A/230VAC
INRUSH CURRENT (Typ.) COLD START 50A
LEAKAGE CURRENT <2mA / 240VAC
 

 

 

PROTECTION

 OVERLOAD 105 ~ 125% rated output power
Protection type : Constant current limiting, unit will shut down o/p voltage after 5 sec. re-power on to recover
 

OVER VOLTAGE

14.7 ~ 17.5V 29.5 ~ 35V 57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE Shut down o/p voltage, recovers automatically after temperature goes down
 

 

 

FUNCTION

OUTPUT VOLTAGE PROGRAMMABLE(PV) Adjustment of output voltage is allowable to 40 ~ 115% of nominal output voltage. Please refer to the Function Manual.
CURRENT SHARING Up to 8000W or (3+1) units. Please refer to the Function Manual.
AUXILIARY POWER 5V @ 0.3A, 12V @ 0.8A
REMOTE ON-OFF CONTROL By electrical signal or dry contact Power ON:open Power OFF:short. Please refer to the Function Manual.
REMOTE SENSE Compensate voltage drop on the load wiring up to 0.5V. Please refer to the Function Manual.
DC OK SIGNAL The isolated TTL signal out. Please refer to the Function Manual.
 

 

 

ENVIRONMENT

WORKING TEMP. -35 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
 

 

 

 

 

 

 

 

 

 

SAFETY & EMC

(Note 6)

SAFETY STANDARDS UL62368-1, CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, BSMI CNS14336-1, AS/NZS62368.1, EAC TP TC 004 approved
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
  

EMC EMISSION

Parameter Standard Test Level / Note
Conducted BS EN/EN55032 (CISPR32) Class B
Radiated BS EN/EN55032 (CISPR32) Class A
Harmonic Current BS EN/EN61000-3-2 —–
Voltage Flicker BS EN/EN61000-3-3 —–
 

 

 

 

 

 

EMC IMMUNITY

BS EN/EN55035, BS EN/EN61000-6-2, BSMI CNS13438
Parameter Standard Test Level / Note
ESD BS EN/EN61000-4-2 Level 3, 8KV air ; Level 2, 4KV contact
Radiated BS EN/EN61000-4-3 Level 3
EFT / Burst BS EN/EN61000-4-4 Level 3
Surge BS EN/EN61000-4-5 Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
Conducted BS EN/EN61000-4-6 Level 3
Magnetic Field BS EN/EN61000-4-8 Level 4
Voltage Dips and Interruptions BS EN/EN61000-4-11 >95% dip 0.5 periods, 30% dip 25 periods,

>95% interruptions 250 periods

 

OTHERS

MTBF 487.7K hrs min.      Telcordia SR-332 (Bellcore) ; 42.9K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION 295*127*41mm (L*W*H)
PACKING 1.95Kg; 6pcs/12.7Kg/1.15CUFT
NOTE
  1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
  3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. Derating may be needed under low input voltages. Please check the derating curve for more details.
  5. Please contact MEANWELL for 320~370VDC application.
  6. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on     a 720mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf)
  7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block DiagramMEAN-WELL-RSP-2000-series-Switching-Power-Supply- (3) Static Characteristics

MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (4) MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (5)

Function Manual

  1. Remote Sense
    The Remote Sense compensates voltage drop on the load wiring up to 0.5VMEAN-WELL-RSP-2000-series-Switching-Power-Supply- (6)
  2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
    In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 40~115% of the nominal voltage by applying EXTERNAL VOLTAGE. MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (7)
  3. Remote ON-OFF Control
    The power supply can be turned ON/OFF individually or along with other units by using the “Remote ON-OFF” function. MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (8)
  4. Current Sharing with Remote Sense
    RSP-2000 has the built-in active current sharing function and can be connected in parallel, up to 4 units, to provide higher output power as exhibited below :
    • The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
    • Difference of output voltages among parallel units should be less than 0.2V.
    • The total output current must not exceed the value determined by the following equation:
      Maximum output current at parallel operation=(Rated current per unit) (Number of unit)××0.9
    • Under parallel operation, the minimum output load should be greater than 5% of total output load; otherwise, it is likely that only one unit operates whereas other units may enter standby mode or their LED status indicators may not turn on.
    • When the total output current is less than 5% of the total rated current, or say (5% of Rated current per unit)×(Number of unit) the current shared among units may not be fully balanced.
    • CN502/CN504 Function pin connection
 

Parallel

PSU1 PSU2 PSU3 PSU4
CN502 CN504 CN502 CN504 CN502 CN504 CN502 CN504
1 unit X V  

 

 

 

 

 

2 unit V V V V  

 

 

 

3 unit V V V X V V  

 

4 unit V V V X V X V V

V is CN502/CN504 connected to plug pin, X is CN502/CN504 not connected to plug pin.

MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (9)

Mechanical Specification

MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (10)

Hole No. Recommended Screw Size MAX. Penetration Depth L Recommended mounting torque
1 M4 6mm 7~10Kgf-cm
2 M4 4mm 7~10Kgf-cm

MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (11)

Control Pin No. Assignment (CN501) : HRS DF11-12DP-2DS or equivalent

Mating Housing HRS DF11-12DS or equivalent
Terminal HRS DF11-**SC or equivalent

MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (12)

Pin No. Function Description
1 +S Positive sensing for remote sense.
2 -S Negative sensing for remote sense.
3 PV Connection for output voltage programming. (Note.1)
4 GND This pin connect to the negative terminal(-V).
 

5

 

DC-OK

High (4.5 ~ 5.5V) : When the Vout ≦80%±6%. Low (0 ~ 0.5V) : When Vout ≧80%±6%.

The maximum sourcing current is 10mA and only for output. (Note.2)

 

6

 

T-ALARM

High (4.5 ~ 5.5V) : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.

Low (0 ~ 0.5V) : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. The maximum sourcing current is 10mA and only for output. (Note.2)

7 Remote ON-OFF The unit can turn the output on and off by electrical signal or dry contact between Remote ON-OFF and +5V-AUX. (Note.2) Short (4.5 ~ 5.5V) : Power OFF ; Open (0 ~ 0.5V) : Power ON ; The maximum input voltage is 5.5V.
8,9,10 GND-AUX Auxiliary voltage output GND.

The signal return is isolated from the output terminals (+V & -V).

11 +5V-AUX Auxiliary voltage output, 4.5~5.5V, referenced to GND-AUX.

The maximum load current is 0.3A. This output has the built-in “Oring diodes” and is not controlled by the Remote ON-OFF control.

12 +12V-AUX Auxiliary voltage output, 10.6~13.2V, referenced to GND-AUX.

The maximum load current is 0.8A. This output has the built-in “Oring diodes” and is not controlled by the Remote ON-OFF control.

Note1: Non-isolated signal, referenced to the output terminals (-V).
Note 2: Isolated signal, referenced to GND-AUX.

LED Indicators & Corresponding Signal at Function Pins

MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (13) Signal between function pin and “GND-AUX”.

Control Pin No. Assignment (CN502) : HRS DF11-6DP-2DSA or equivalentMEAN-WELL-RSP-2000-series-Switching-Power-Supply- (14)

Mating Housing HRS DF11-6DS or equivalent
Terminal HRS DF11-**SC or equivalent
Pin No. Function Description
1,2 DA Differential digital signal for parallel control.
3,4 DB Differential digital signal for parallel control.
5,6 GND These pins connect to the negative terminal (-V).

Control Pin No. Assignment (CN504):

Pin No. Function Description
1,2 Terminal resistance CN504 is the selector of terminal resistor that is designed for DA/DB signals and parallel control function.

AC Input Terminal Pin No. Assignment

MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (15)DC Output Terminal Pin No. Assignment

MEAN-WELL-RSP-2000-series-Switching-Power-Supply- (16)

Installation Manual
Please refer to : http://www.meanwell.com/manual.html

Downloaded from Arrow.com.

Documents / Resources

MEAN WELL RSP-2000 series Switching Power Supply [pdf] Owner's Manual
RSP-2000-12, RSP-2000-24, RSP-2000-48, RSP-2000 series Switching Power Supply, RSP-2000 series, Switching Power Supply, Power Supply, Supply

References

Leave a comment

Your email address will not be published. Required fields are marked *