MEAN WELL PWM-120 Series 120W Constant Voltage PWM Output LED Driver User Manual
Features
- Constant voltage PWM style output.
- Emergengcy lighting application is available according to IEC61347-2-13.
- Built-in active PFC function and class Il design
- No load power consumption <0.5W/ standby power consumption <0.5W(DA/DA2-type)
- Fully encapsulated with IP67 level
- Function options: 3 in 1 dimming (dim-to-off); DALI/DALI-2
- Minimum dimming level 0.2% for DALI type
- Typical lifetime>50000 hours and 5 years warranty
Applications
- LED strip lighting
- Indoor LED lighting
- LED decorative lighting
- LED architecture lighting
- Industrial lighting
- Type “HL” for use in class |, division 2 hazardous (classified) location.
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
PWM-120 series is a 120W AC/DC LED driver featuring the constant voltage mode with PWM style output,
which is able to maintain the color temperature and the brightness homogeneity when driving all kinds of LED strips. PWM-120 operates from 90~305VAC and offers models with different rated voltage ranging between 12V and 48V. Thanks to the high efficiency up to 90.5%, with the fanless design, the entire series is able to operate for -40°C ~ +90°C case temperature under free air convection. The entire series is rated with IP67 ingress protection level and is suitable to work for dry, damp or wet locations. PWM-120 is equipped with dimming function that varies the duty cycle of the output, providing great flexibility for LED strips applications.
Model Encoding
Type | IP Level | Function | Note |
Blank | IP67 | 3 in 1 dimming function (0~10Vdc, 10V PWM signal and resistance) | In stock |
DA | IP67 | DALI control technology.(for 12V/24V DA type only ) | In stock |
DA2 | IP67 | DALI-2 control technology.(for 12V/24V with DA2 Type only ) | In stock |
SPECIFICATION
MODEL | PWM-120-12 | PWM-120-24 | PWM-120-36 | PWM-120-48 | |
OUTPUT | DC VOLTAGE | 12V | 24V | 36V | 48V |
RATED CURRENT | 10A | 5A | 3.4A | 2.5A | |
RATED POWER | 120W | 120W | 122.4W | 120W | |
DIMMING RANGE | 0 ~ 100% | ||||
PWM FREQUENCY (Typ.) | 1.47kHz for Blank/DA-Type, 2.5kHz for DA2-Type | ||||
SETUP, RISE TIME Note.2Note.9 | 500ms, 80ms/ 230VAC or 115VAC | ||||
HOLD UP TIME (Typ.) | 16ms/230VAC or 115VAC | ||||
INPUT | VOLTAGE RANGE Note.3 | 90 ~ 305VAC 127 ~ 431VDC(Please refer to “STATIC CHARACTERISTIC” section) | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
POWER FACTOR (Typ.) | PF>0.97/115VAC, PF>0.96/230VAC, PF>0.93/277VAC @ full load(Please refer to “POWER FACTOR (PF) CHARACTERISTIC” section) | ||||
TOTAL HARMONIC DISTORTION | THD< 20%(@load≧60%/115VAC, 230VAC; @load≧75%/277VAC)(Please refer to “TOTAL HARMONIC DISTORTION” section) | ||||
EFFICIENCY (Typ.) | 88.5% | 90% | 90% | 90.5% | |
AC CURRENT (Typ.) | 1.3A / 115VAC 0.65A / 230VAC 0.55A / 277VAC | ||||
INRUSH CURRENT (Typ.) | COLD START 60A(twidth=520μs measured at 50% Ipeak) at 230VAC; Per NEMA 410 | ||||
MAX. NO. of PSUs on 16A CIRCUIT BREAKER | 4 units (circuit breaker of type B) / 6 units (circuit breaker of type C) at 230VAC | ||||
LEAKAGE CURRENT | <0.25mA / 277VAC | ||||
NO LOAD/STANDBY POWER CONSUMPTION | No load power consumption<0.5w for blank-type;standby power consumption<0.5W for DA-type/DA2-type | ||||
PROTECTION | OVERLOAD | 108 ~ 130% rated output power | |||
Hiccup mode, recovers automatically after fault condition is removed | |||||
SHORT CIRCUIT | 12V/24V hiccup mode and 36V/48V shut down mode(including DA-type/except for DA2-type) Hiccup mode,recovers automatically after fault condition is removed (only for DA2-type) | ||||
OVER VOLTAGE | 15 ~ 17V | 28 ~ 34V | 41 ~ 46V | 54 ~ 60V | |
Shut down o/p voltage, re-power on to recover | |||||
OVER TEMPERATURE | Shut down o/p voltage, re-power on to recover | ||||
ENVIRONMENT | WORKING TEMP. | Tcase=-40 ~ +90℃ (Please refer to “ OUTPUT LOAD vs TEMPERATURE” section) | |||
MAX. CASE TEMP. | Tcase=+90℃ | ||||
WORKING HUMIDITY | 20 ~ 95% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40 ~ +80℃, 10 ~ 95% RH | ||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 45℃,except 0 ~ 40℃ for 12V) | ||||
VIBRATION | 10 ~ 500Hz, 5G 12min./1cycle, period for 72min. each along X, Y, Z axes | ||||
SAFETY & EMC | SAFETY STANDARDS Note.5 | UL8750( type ”HL” )(except for 12DA type), CSA C22.2 No. 250.13-12; ENEC BS EN/EN61347-1, BS EN/EN61347-2-13, BS EN/EN62384 independent, IP67,BIS IS15885( for PWM-120-12,24 only), EAC TP TC 004,GB19510.1,GB19510.14approved; Design refer to BS EN/EN60335-1; According to BS EN/EN61347-2-13 appendix J suitable for emergency installations(EL)(AC Input: 100-240Vac)(for DA2-Type only) | |||
DALI STANDARDS | IEC62386-101, 102, 207,251 for DA/DA2-Type only, Device type 6(DT6) | ||||
WITHSTAND VOLTAGE | I/P-O/P:3.75KVAC; I/P-DA:1.5KVAC; O/P-DA:1.5KVAC | ||||
ISOLATION RESISTANCE | I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH | ||||
EMC EMISSION Note.6 | Compliance to BS EN/EN55015, BS EN/EN61000-3-2 Class C (@load≧60%) ; BS EN/EN61000-3-3,GB17743 and GB17625.1,EAC TP TC 020 | ||||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11; BS EN/EN61547, light industry level (surge immunity Line-Line 2KV), EAC TP TC 020 | ||||
OTHERS | MTBF | 2243.7K hrs min. Telcordia SR-332 (Bellcore) ; 228.7K hrs min. MIL-HDBK-217F (25℃) | |||
DIMENSION | 191*63*37.5mm (L*W*H) | ||||
PACKING | 0.97Kg; 15pcs/15.6Kg/0.87CUFT | ||||
NOTE |
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx |
DIMMING OPERATION
DIM+ for Blank-Type DA+ for DA/DA2-type * *DIM- for Blank-Type DA- for DA/DA2-type
Dimming principle for PWM style output
Dimming is achieved by varying the duty cycle of the output current.
3 in 1 dimming function (for Blank-Type)
- Apply one of the three methodologies between DIM+ and DIM-: 0 ~ 10VDC, or 10V PWM signal or resistance.
- Dimming source current from power supply: 100μA (typ.)
Note
- Min. duty cycle of output current is about 0.15%, and the dimming input is about 6KΩ or 0.6VDC, or 10V PWM signal with 6% duty cycle.
- The duty cycle of output current could drop down to 0% when dimming input is less than 6KΩ or less than 0.6VDC, or 10V PWM signal with duty cycle less than 6%.
DALI Interface (primary side; for DA/DA2-Type)
- Apply DALI signal between DA+ and DA-.
- DALI protocol comprises 16 groups and 64 addresses.
- First step is fixed at 0.2% of output
OUTPUT LOAD vs TEMPERATURE
STATIC CHARACTERISTIC
POWER FACTOR (PF) CHARACTERISTIC
De-rating is needed under low input voltage.
TOTAL HARMONIC DISTORTION (THD)
EFFICIENCY vs LOAD
PWM-120 series possess superior working efficiency that up to 90.5% can be reached in field applications.
48V Model, Tcase at 80℃
LIFE TIME
Block Diagram
Mechanical Specification
Blank-Type
DA/DA2-Type
Recommend Mounting Direction
Installation Manual
Connection for Blank-type
Cautions
- Before commencing any installation or maintenance work, please disconnect the power supply from the utility. Ensure that it cannot be re-connected inadvertently!
- Keep proper ventilation around the unit and do not stack any object on it. Also a 10-15 cm clearance must be kept whenthe adjacent device is a heat source.
- Mounting orientations other than standard orientation or operate under high ambient temperature may increase the internal component temperature and will require a de-rating in output current.
- Current rating of an approved primary /secondary cable should be greater than or equal to that of the unit. Please refer to its specification.
- For LED drivers with waterproof connectors, verify that the linkage between the unit and the lighting fixture is tight so that water cannot intrude into the system.
- For dimmable LED drivers, make sure that your dimming controller is capable of driving these units.PWM series require 0.15mA each unit.
- Tc max. is identified on the product label. Please make sure that temperature of Tc point will not exceed limit.
- DO NOT connect “DIM- to -V”.
- Suitable for indoor use or outdoor use without direct sunlight exposure. Please avoid immerse in the water over 30 minutes.
- The power supply is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the complete installation, the final equipment manufacturers must re qualify EMC
- Directive on the complete installation again.
Documents / Resources
![]() |
MEAN WELL PWM-120 Series 120W Constant Voltage PWM Output LED Driver [pdf] User Manual PWM-120-12, PWM-120-24, PWM-120-36, PWM-120 Series, 120W Constant Voltage PWM Output LED Driver, PWM-120 Series 120W Constant Voltage PWM Output LED Driver, Constant Voltage PWM Output LED Driver, Voltage PWM Output LED Driver, PWM Output LED Driver, Output LED Driver, LED Driver, Driver |