MEAN WELL LPV-150 Series 150W Single Output Switching Power Supply
Features
- Constant voltage design
- input for LPVL-150
- 1 input for LPV-150
- Fully encapsulated with IP67 level (Note. 7)
- Class 11 power unit, no FG
- Protections: Short circuit/Overload/Over voltage/Over temperature
- Fully isolated plastic case
- Fanless design, cooling by free air convection
- 100% full load burn-in test
- Low cost, high reliability
- Listed in UL Sign Component Manual (SAM)
- Type “HL” for use in Class l, Division 2 hazardous (Classified) location luminaires for LPVL-150
- 2-year warranty
Description
LPV-150 and LPVL-150 are 150W single-output power supplies that specifically and perfectly work for LED lighting and LED moving sign applications. As a class 11 power unit, these two series are housed with the UL 94V-O rated flame retardant plastic enclosure. The IP67 design allows every model to fit the use at dry, damp and wet locations. Both series are constant voltage mode designs that have various models with 12V, 15V, 24V, 36V, and 48V for LPV-150 where as 12V and 24V are provided for LPVL-150.
Model Encoding
Applications
- Suitable for LED-related fixtures or appliances (such as LED Decoration or Advertisement devices)(Note 1 0)
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTlN.aspx
SPECIFICATION
MODEL | LPV -150-12 | LPV-150-15 | LPV -150-24 | LPV-150-36 | LPV-150-48 | ||
OUTPUT | DC VOLTAGE | 12V | 15V | 24V | 36V | 48V | |
RATED CURRENT | 10A | 8A | 6.3A | 4.2A | 3.2A | ||
CURRENT RANGE | 0 ~ 10A | 0 ~ 8A | 0 ~ 6.3A | 0 ~ 4.2A | 0 ~ 3.2A | ||
RATED POWER | 120W | 120W | 151.2W | 151.2W | 153.6W | ||
RIPPLE & NOISE (max.) Note.2 | 200mVp-p | 200mVp-p | 200mVp-p | 200mVp-p | 200mVp-p | ||
VOLTAGE TOLERANCE Note 3 | ±5.0% | ||||||
LINE REGULATION | ±1.0% | ||||||
LOAD REGULATION | ±2.0% | ||||||
SETUP, RISE TIME Note 6 | LPV-150: 500ms, 50ms / 230VAC 500ms, 50ms / 277VAC; LPVL-150: 1500ms, 50ms / 115VAC | ||||||
HOLD UP TIME (Typ.) | LPV-150: 18ms/230VAC 20ms/277VAC at full load; LPVL-150: 10ms/115VAC at full load | ||||||
INPUT | VOLTAGE RANGE Note 4 | LPV-150: 180 ~ 305VAC 254 ~ 431VDC; LPVL-150: 90~132VAC | |||||
FREQUENCY RANGE | 47 ~ 63Hz | ||||||
EFFICIENCY (Typ.) | 87% | 88% | 89% | 89% | 90% | ||
AC CURRENT | LPV-150: 1.7A/230VAC 1.5A/277VAC; LPVL-150: 3.0A/115VAC | ||||||
INRUSH CURRENT
(Typ.) |
Blank type | COLD START 60A(twidth=900μs measured at 50% Ipeak) at 230VAC | |||||
L type | COLD START 75A(twidth=900μs measured at 50% Ipeak) at 115VAC | ||||||
MAX. No. of PSUs on 16A CIRCUIT
BREAKER |
Blank type | 2 units (circuit breaker of type B) / 3 units (circuit breaker of type C) at 230VAC | |||||
L type | 1 unit (circuit breaker of type B) / 2 units (circuit breaker of type C) at 115VAC | ||||||
LEAKAGE CURRENT | LPV-150: 0.25mA / 240VAC LPVL-150:0.25mA / 120VAC | ||||||
PROTECTION | OVERLOAD | 110 ~ 150% rated output power | |||||
Protection type: Hiccup mode, recovers automatically after the fault condition is removed | |||||||
OVER VOLTAGE | 13.5 ~ 18V | 17 ~ 25V | 27 ~ 35V | 40 ~ 49V | 52 ~ 63V | ||
Protection type: Shut down o/p voltage, re-power on to recover | |||||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after the temperature goes down | ||||||
ENVIRONMENT | WORKING TEMP. | -25 ~ +65℃ (Refer to “Derating Curve”) | |||||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||||
STORAGE TEMP., HUMIDITY | -40 ~ +80℃, 10 ~ 95% RH | ||||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 40℃ for LPV-150-12,15 and LPVL-150-12,24;0~50℃ for LPV-150-24,36,48) | ||||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes | ||||||
SAFETY &
EMC |
SAFETY
STANDARDS |
Blank type | UL8750,CSA C22.2 No 250.13-12,UL879,CSA C22.2 No.207-M89,BIS IS15885(for LPV-150-12,24 only),EAC TP TC 004, IP67, IEC62368-1, BS EN/EN62368-1 approved | ||||
L type | UL8750(type”HL”),CSA C22.2 No 250.13-12,UL879,CSA C22.2 No.207-M89,IP67 approved | ||||||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC | ||||||
ISOLATION RESISTANCE | I/P-O/P:>100M Ohms / 500VDC / 25℃/ 70% RH | ||||||
EMC EMISSION | Blank type | Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2 Class A(≤80% load), BS EN/EN61000-3-3, EAC TP TC 020 | |||||
L type | Compliance to FCC part 15 | ||||||
EMC IMMUNITY | Blank type | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11; BS EN/EN55035, light industry level, EAC TP TC 020 | |||||
L type | Design refers to IEC61000-4-2,3,4,5,6,8,11; light industry level | ||||||
OTHERS | MTBF | 3361.2K hrs min. Telcordia SR-332 (Bellcore) ; 391.9Khrs min. MIL-HDBK-217F (25℃) | |||||
DIMENSION | 191*63*37.5mm (L*W*H) | ||||||
PACKING | LPV-150: 0.79Kg;20pcs/17Kg/0.98CUFT; LPVL-150: 0.79Kg;20pcs/17Kg/0.98CUFT |
NOTE | All parameters NOT specially mentioned are measured at 230VAC(115VAC for LPVL) input, rated load, and 25℃ of ambient temperature.
Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. Tolerance: includes setup tolerance, line regulation and load regulation. Derating may be needed under low input voltage. Please check the static characteristics for more details. The power supply is considered a component that will be operated in combination with the final equipment. Since EMC performance will be affected by the complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again. (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf) The length of setup time is measured at first cold start. Turning ON/OFF the power supply may lead to an increase of the setup time. Suitable for indoor use or outdoor use without direct sunlight exposure. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft). For any application note and IP waterproof function installation caution, please refer our user manual before using. https://www.meanwell.com/Upload/PDF/LED_EN.pdf This product is not intended for LED lighting luminaire applications in the EU and China.(In the EU and China, the LPF/NPF/XLG/XLC/XLN series are recommended.) ※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx |
Mechanical Specification
Recommend Mounting Direction
Block Diagram
Derating Curve
Static Characteristics
Documents / Resources
![]() |
MEAN WELL LPV-150 Series 150W Single Output Switching Power Supply [pdf] Owner's Manual LPV-150-12, LPV-150-15, LPV-150-24, LPV-150-36, LPV-150-48, LPV-150 Series 150W Single Output Switching Power Supply, LPV-150 Series, 150W Single Output Switching Power Supply, Output Switching Power Supply, Switching Power Supply, Power Supply |