MEAN WELL DRA-60-12 Single Output Switching Power Supply 

MEAN WELL DRA-60-12 Single Output Switching Power Supply 

Feature

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Output Voltage adjustable through internal potentiometer
  • Output Current adjustable through external 1 ~1 0Vdc, PWM signal or resistance
  • Cooling by free air convection
  • Pass LPS
  • LED indicator for power on
  • 100% full load burn-in test
  • 3 years warranty
    Feature

Applications

  • Machine vision inspection system
  • Plant cultivation system

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

DRA-60 is one 60W AC/DC DIN rai l power supply, featuring the adjustable output current. Users are able to easi ly change the constant output current level, via 1 ~ 1 0Vdc, PWM signal or resistance. DRA-60 can be mounted on DIN rail TS-35/7.5 or 15; in addition, the width of the unit is only 40mm that it is well suited for the installation in a limited spacing. DRA-60 accepts the universal AC input between 90VAC and 264VAC; the efficiency is up to 87% that the entire series can operate, under free air convection , from -30°C through 70°C.

Model Encoding

Model Encoding

SPECIFICATION

MODEL DRA-60-12 DRA-60-24
OUTPUT DC VOLTAGE 12V 24V
CONSTANT CURRENT REGION 3 ~ 12V 3 ~ 24V
RATED CURRENT 5A 2.5A
CURRENT RANGE 0 ~ 5A 0 ~ 2.5A
RATED POWER 60W 60W
RIPPLE & NOISE (max.) Note.2 120mVp-p 150mVp-p
VOLTAGE ADJ. RANGE 12 ~ 15V 24 ~ 30V
VOLTAGE TOLERANCE Note.3 ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5%
LOAD REGULATION ±0.5% ±0.5%
SETUP, RISE TIME Note.4 400ms, 90ms/230VAC            800ms, 90ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC            10ms/115VAC at full load
 INPUT VOLTAGE RANGE 90 ~ 264VAC            127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 85% 87%
AC CURRENT (Typ.) 1.3A/115VAC            0.8A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC            60A/230VAC
PROTECTION OVERLOAD 95 ~ 108% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE 14.49 ~ 18.63V 28.98 ~ 37.26V
Protection type : Shut down o/p voltage, re-power on to recover
ENVIRONMENT WORKING TEMP. -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃) on output
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC (Note 5) SAFETY STANDARDS UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61204-3, light industry level, criteria A, EAC TP TC 020
OTHERS MTBF 2930.8K hrs min.       Telcordia SR-332 (Bellcore) ; 436.4K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION 40*90*100mm (W*H*D)
PACKING 0.3Kg; 42pcs/13.6Kg/0.82CUFT
NOTE
  1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
  3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
  5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
  6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
  7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Block Diagram

Derating Curve

  • AMBIENT TEMPERATURE (℃)
    Derating Curve

Static Characteristics

Static Characteristics

Output Current Adjustment Operation

  • Built-in 3 in 1 current adjustment function . Output constant current level can be adjusted by applying 1 ~ 10Vdc, 10V PWM signal or resistance between DIM+ and DIM-.
  • Please DO NOT connect “DIM-” to “-V”.
  • Reference resistance value for output current adjustment (Typical)
Resistance value Single Power supply 10KΩ 20KΩ 30KΩ 40KΩ 50KΩ 60KΩ 70KΩ 80KΩ 90KΩ 100KΩ OPEN
Multiple Power supplies (N=Power supply quantity for simultaneous current adjustment control) 10KΩ/N 20KΩ/N 30KΩ/N 40KΩ/N 50KΩ/N 60KΩ/N 70KΩ/N 80KΩ/N 90KΩ/N 100KΩ/N —–
Percentage of rated current 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

1 ~ 10Vdc for output current adjustment (Typical)

Applied Source 1V 2V 3V 4V 5V 6V 7V 8V 9V 10V OPEN
Percentage of rated current 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 102%~108%

10V PWM signal for output current adjustment (Typical): Frequency range :100Hz ~ 3KHz

Duty value 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% OPEN
Percentage of rated current 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 102%~108%

Using the current adjustment function can not adjust the output current to 0A. Please refer to the connection method below to adjust the output
current to 0A.

Output Current Adjustment Operation

Driving Methods Of Applications

The power supply may either work in “constant voltage mode or constant current mode”

Output Current Adjustment Operation In the constant current region, the highest voltage at the output of the driver
depends on the configuration of the end systems.
Should there be any compatibility issues, please contact MEAN WELL.

Mechanical Specification

Mechanical Specification

Installation Instruction

  • Back ViewInstallation Instruction

This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.

Installation Manual

Please refer to : http://www.meanwell.com/manual.html

User’s Manual

QR Code

Logo

Documents / Resources

MEAN WELL DRA-60-12 Single Output Switching Power Supply [pdf] Instruction Manual
DRA-60-12 Single Output Switching Power Supply, DRA-60-12, Single Output Switching Power Supply, Output Switching Power Supply, Switching Power Supply, Power Supply, Supply

References

Leave a comment

Your email address will not be published. Required fields are marked *