SAI140 Modbus RTU Over RS485
to Analogy Input Quick Start Guide

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input

JerryPeng 0975-365-352
www.maxlong.com.tw

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - Qr code MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - Qr code 2

http://www.maxlong.com.tw

http://www.maxlong.com.tw/product-detail/lora-converter

Introduction

SAI140 provides 4 analogy inputs selective from 4~20 mA and 0~10V by onboard jumper settings. It’s sample rate 5 times/second (4 inputs).
One RS485 Serial Port (Terminal Block interface) support Modbus RTU protocol.
Notes:
Word type : Unsigned Integer
Resolution : 16 bits
Wording order : High byte in the front, Low type in the back.
The correct value from analog input should be the obtained value divided by 1000.

1.1 Product Views 

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - Product Views

1.2 Wiring Architecture 

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - Wiring Architecture

Configuration

2.1 Analogy Type Settings

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - Analogy Type Settings

Note: Analog Inputs each selective of 4~20mA OR 0~10V by onboard jumper Settings.

2.2 Configuration Via Windows Utility
Step1➔ Open and configure SAI140 via the “SCAI4_TestTool”
Step2➔ Configure the test tool (as shown below)

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - SCAI4 test tool configuration

Step3➔ After configure COM port parameters then Click “Connect”
Step4➔One should get ‘Connected” from SAI140 And now you have successfully connected to SAI140.

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - SCAI4 test tool configuration 2

2.3 Function Test

  1. Voltage testMaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - Voltage test
  2. Current testMaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - Current test
  3. VO SettingsMaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - VO Settings

2.4 Modbus Command Set
A basic MODBUS command always takes two main parameters:

  1. ID Address: Designated to receive this Command ID address。
  2. Function Code: This Command function。

The reception to the Command element will return a Response inform the completion of action in response to the remote or the value returned by the read, Response Command format in the format is basically the same, but also have ID Address and Function code in order to master identification, the following table for common Function code order.

1. MODBUS RTU Protocol
The following MODBUS functions are supported.

Function code Description
0x03 Read Holding Registers
0x06 Write Single Register

MODBUS Protocol Address Map

MODBUS Register HEX Function Description Action
0000 0106 Read/Write Modbus device Address
And Baud Rate Setting
High byte: Modbus device Address
The rage is 1~247
Low byte: Baud Rate Setting
1: 2400
2: 4800
3: 9600
4: 14400
5: 19200
6: 38400
7: 115200
R/W
0001 0600 Data length , Parity, and stop bits Setting High byte: Data length , Parity, and stop bits. Valid values are :
SERIAL_7N1 0x04 SERIAL_8N1 0x06(default) SERIAL_7N2 0x0C SERIAL_8N2 0x0E SERIAL_7E1 0x24 SERIAL_8E1 0x26 SERIAL_7E2 0x2C SERIAL_8E2 0x2E SERIAL_7O1 0x34 SERIAL_8O1 0x36 SERIAL_7O2 0x3C SERIAL_8O2 0x3E
Low byte: Reserved
R/W
0004 0018 Read AI1 voltage Ex: 0x2710 = 10000 in decimal. It means 10.000V R
0005 0030 Read AI1 current Ex: 0x4E20 = 20000 in decimal. It means 20.000mA R
0008 0018 Read AI2 voltage Ex: 0x2710 = 10000 in decimal. It means 10.000V R
0009 0030 Read AI2 current Ex: 0x4E20 = 20000 in decimal. It means 20.000mA R
0014 2710 Read AO1 voltage Ex: 0x2710 = 10000 in decimal. It means 10.000V R/W
0018 1388 Read AO2 voltage Ex: 0x1388 = 5000 in decimal. It means 5.000V R/W

Example for read Modbus Address and Baud Rate :

Request Response
Field Name (Hex) Field Name (Hex)
MODBUS Address 01 MODBUS Address 01
Function 03 Function 03
Starting Address Hi 00 Byte Count 02
Starting Address Lo 00 High Byte Data 01
Quantity of Outputs Hi 00 Low Byte Data 06
Quantity of Outputs Lo 01 High Byte CRC 39
High Byte CRC 84 Low Byte CRC D6
Low Byte CRC 0A

Ex: High Byte Data 0x01 means Modbus Address = 01. The available rage is 1~247.
Low Byte Data 0x06 means Baud Rate = 38400
For
1 means baud rate is 2400
2 means baud rate is 4800
3 means baud rate is 9600
4 means baud rate is 14400
5 means baud rate is 19200
6 means baud rate is 38400
7 means baud rate is 115200

Example for read AI1 voltage input

Request Response
Field Name (Hex) Field Name (Hex)
MODBUS Address 01 MODBUS Address 01
Function 03 Function 03
Starting Address Hi 00 Byte Count 02
Starting Address Lo 04 High Byte Data 00
Quantity of Outputs Hi 00 Low Byte Data 18
Quantity of Outputs Lo 01 High Byte CRC B8
High Byte CRC C5 Low Byte CRC 4E
Low Byte CRC CB

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - voltage input

Ex: Data 0x0018 = 24 in decimal. It means 0.024V
Example for read AI1 current input

Request Response
Field Name (Hex) Field Name (Hex)
MODBUS Address 01 MODBUS Address 01
Function 03 Function 03
Starting Address Hi 00 Byte Count 02
Starting Address Lo 05 High Byte Data 00
Quantity of Outputs Hi 00 Low Byte Data 30
Quantity of Outputs Lo 01 High Byte CRC B8
High Byte CRC 94 Low Byte CRC 50
Low Byte CRC 0B

Ex: Data 0x0030 = 48 in decimal. It means 0.048mA
Example for read AI2 voltage input

Request Response
Field Name (Hex) Field Name (Hex)
MODBUS Address 01 MODBUS Address 01
Function 03 Function 03
Starting Address Hi 00 Byte Count 02
Starting Address Lo 08 High Byte Data 00
Quantity of Outputs Hi 00 Low Byte Data 18
Quantity of Outputs Lo 01 High Byte CRC B8
High Byte CRC 05 Low Byte CRC 4E
Low Byte CRC C8

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input - voltage input 2

Ex: Data 0x0018 = 24 in decimal. It means 0.024V
Example for read AI2 current input

Request Response
Field Name (Hex) Field Name (Hex)
MODBUS Address 01 MODBUS Address 01
Function 03 Function 03
Starting Address Hi 00 Byte Count 02
Starting Address Lo 09 High Byte Data 00
Quantity of Outputs Hi 00 Low Byte Data 30
Quantity of Outputs Lo 01 High Byte CRC B8
High Byte CRC 54 Low Byte CRC 50
Low Byte CRC 08

Ex: Data 0x0030 = 48 in decimal. It means 0.048mA
Example for set Modbus Address and Baud Rate :

Request Response
Field Name (Hex) Field Name (Hex)
MODBUS Address 01 MODBUS Address 01
Function 06 Function 06
Data Address Hi 00 Data Address Hi 00
Address Lo 00 Data Address Lo 00
High Byte Data 02 High Byte Data 02
Low Byte Data 06 Low Byte Data 06
High Byte CRC 08 High Byte CRC 08
Low Byte CRC A8 Low Byte CRC A8

Ex: High Byte Data 0x02 set Modbus Address as 02. The available rage is 1~247.
Low Byte Data 0x06 set Baud Rate as 38400
For 1 set baud rate as 2400
2 set baud rate as 4800
3 set baud rate as 9600
4 set baud rate as 14400
5 set baud rate as 19200
6 set baud rate as 38400
7 set baud rate as 115200

Example for set AO1 :

Request Response
Field Name (Hex) Field Name (Hex)
MODBUS Address 01 MODBUS Address 01
Function 06 Function 06
Data Address Hi 00 Data Address Hi 00
Address Lo 14 Data Address Lo 14
High Byte Data 27 High Byte Data 27
Low Byte Data 10 Low Byte Data 10
High Byte CRC D3 High Byte CRC D3
Low Byte CRC F2 Low Byte CRC F2

Ex: High Byte Data & Low Byte Data 0x2710 set AO1 10.000V output
Example for set AO2 :

Request Response
Field Name (Hex) Field Name (Hex)
MODBUS Address 01 MODBUS Address 01
Function 06 Function 06
Data Address Hi 00 Data Address Hi 00
Address Lo 18 Data Address Lo 18
High Byte Data 13 High Byte Data 13
Low Byte Data 88 Low Byte Data 88
High Byte CRC 04 High Byte CRC 04
Low Byte CRC 9B Low Byte CRC 9B

Ex: High Byte Data & Low Byte Data 0x1388 set AO2 5.000V output

2.5 Reset Button
If any chance you forgot the login password or have incorrect settings making this Device inoperable, upon the power is on and the “SYS” LED light on, use a point tip to press this button and hold it for more than 20 seconds the release the point tip. The Device will reboot and all the parameters will be reset to the factory default.

This document is proprietary to Max Long Corporation. Use or disclosure of the document, or the information contained therein, for any purposes other than Max Long purposes is NOT permitted without prior written authorization by Max Long

MaxLong logo

Documents / Resources

MaxLong SAI140 Modbus RTU Over RS485 to Analogy Input [pdf] User Guide
SAI140 Modbus RTU Over RS485 to Analogy Input, SAI140, Modbus RTU Over RS485 to Analogy Input, RS485 to Analogy Input, Analogy Input

References

Leave a comment

Your email address will not be published. Required fields are marked *