masibus 1008S Flow Indicator Totaliser
1008S Flow Indicator Totaliser
Input Type | Range |
to 20 mA | to 30000 |
to 20 mA | |
to 5 V | |
to 5 V | |
*Pulse Input | |
Integrated/ Batch Total | to 999999 |
SPECIFICATIONS
- NUMBER OF INPUTS 1 with Optional 2 & 3
- ACCURACY ± 0.25% of full scale ± 1 Count , **0.45 % – for Integrated/ Batch Total
- BURN OUT DETECTION Available for 1 to 5VDC, 4 to 20 mA, 0 to 10 KHz.
- INPUT RESISTANCE
- 250 Ohms Internal for current Input
- 320K Ohms for Voltage Input
- ALLOWABE SIGNAL SOURCE RESISTANCE
- DC input voltage: 1KΩ or less. Effect from allowable signal source
- Resistance: 0.031 % / 100Ω or less
- ALLOWABLE INPUT VOLTAGE
- DC voltage: ±20V DC
- NOISE REJECTION RATIO
- Common Mode: > 100db
- Normal mode: > 40db
- RESPONSE TIME
- Input to relay o/p: < 1 second.
- Input to Analog o/p: < 1 second or less, 63 % (10 – 90%) (Time required for o/p to reach 63% of the maximum excursion when PV changes from 10% to 90%)
- RESOLUTION 16 bit POLARITY
- PROTECTION Not provided
- MEMORY BACKUP EEPROM
Loop Power Supply Specification
- LOOP POWER SUPPLY 24VDC ± 5% @ 50mA
Retransmission Output
NUMBER OF OUTPUTS | 1 |
OUTPUT SIGNALS | to 20 mA DC
|
LOAD RESISTANCE | 500Ω or less |
OUTPUT ACCURACY | ± 0.25% of full scale +1 count |
RESOLUTION | bits (5uA) |
Contact Input (Digital input)
NO OF INPUTS | 4 |
USAGE | Input 1 : Stop Batch Input 2 : Integration total zero(Therefore Batch total and roll count will be zero) Input 3 : Start Batch
Input 4 : Batch total zero |
INPUT TYPE | Non- voltage contact input or transistor open collector input |
INPUT CONTACT CAPACITY | 12VDC,10mA or more (for non – voltage contact input) |
ON/ OFF
DETERMINATION |
• For non-voltage contact input ON = contact resistance of 1KΩ or
less, OFF = contact resistance of 20KΩ or more • For transistor contact input ON = 2V or less OFF = leak current of 100µA or less |
MINIMUM
RETENTION TIME FOR STATUS DETECTION |
About 1 Second |
Contact Outputs
- NUMBER OF OUTPUTS 4 (2 Flow alarm relays, 2 Batch relays)
- USAGE Flow alarm / Batch relay
- RELAY CONTACT TERMINAL 3(Common, NO, NC)
- RELAY CONTACT RATING 250VAC/5Amps
Communication Specification
PROTOCOL | Modbus RTU serial |
STANDARD | EIA RS-485 |
MAX.
COMMUNICATION DISTANCE |
mtrs. (For 9600 bps RS 485) |
COMMUNICATION METHOD | wire half duplex (RS
485) |
DATA FRAME | N, 8, 1 |
COMMUNICATION RATE | 9600, 19200 bps |
MAX. CONNECTABLE
CONTROLLERS/ INDICATOR |
32 |
ADDRESS RANGE | to 99 |
Display Unit Specification
PROCESS VALUE DISPLAY | 0.56” 5 digit 7- segment red display |
INTEGRATED TOTAL DISPLAY | 0.40” 8 digit 7- segment red display |
PARAMETER DISPLAY | Same integrated total display |
STATUS INDICATING LAMP | Red LED’s |
Power Supply Specification
- POWER SUPPLY 110 to 230 VAC, 50Hz ; 24VDC(optional)
- POWER CONSUMPTION <10Va
- WITHSTANDING VOLTAGE
- Between primary terminal and secondary terminal : 1500VAC(For 1 min)
- Between primary terminal and ground terminal : 500VDC(for 1 min)
- Between ground terminal and Secondary terminal: 500V AC (for 1 minute).
- (Primary terminal: Power supply, relay output) (Secondary terminal: Analog input/output signal terminals, contact input terminal)
Signal Isolation Specifications
ISOLATION
RESISTANCE |
Between power supply terminal and ground terminal: 500 VDC, 50MΩ |
MEASURED INPUT TERMINAL | Isolated from other input/output terminals. Not isolated from 24Vdc supply
(Transmitter power supply) and internal circuit. |
24V DC SUPPLY
FOR TRANSMITTER |
Not isolated from the measured input terminal & internal circuit, isolated from other input/output terminals. |
RETRANSMISSION
OUTPUT TERMINAL |
Isolated from other input/output terminals and internal circuit. |
CONTACT INPUT TERMINAL | Isolated from other input/output terminals and internal circuit. |
RELAY CONTACT
O/P TERMINAL (DIGITAL INPUT) |
Isolated from other input /output terminals and internal circuit. |
RS–485
COMMUNICATION TERMINAL |
Isolated from other input/output terminals and internal circuit. |
POWER SUPPLY TERMINAL | Isolated from other input / output terminals and internal circuit. |
GROUND TERMINAL | Isolated from other input/ output terminals and internal circuit. |
Environmental Specification
- OPERATING TEMPERATURE 0 to 55°C
- STORAGE TEMPERATURE 0 to 70°C
- HUMIDITY 30 to 90% RH (Noncondensing) WARM UP TIME >10 Minute
- EFFECT OF AMBIENT TEMPERATURE
- For Voltage Input: 0.005% of FS/ °C or less
- For analog output: 0.010% of FS/ °C or less
Alarm Specification
ALARM TYPES | Flow high limit, Flow low limit |
BATCHING ALARM | Pre warn and set point |
SETTING
RANGES FOR PROCESS VALUE ALARMS |
Flow (PV) Alarms:
Min = Zero of individual I/P type Max = Span of individual I/P type |
Display Specification
PV DISPLAY | 5 digit red 7 segment display for flow rate |
INTEGRATED TOTAL | 8 digit red 7 segment display for integrated total |
PARAMETER DISPLAY | Same 8 digit red 7 segment display integrated total |
STATUS
DISPLAY |
Red LEDs (for alarm & Batch) |
Other Specification
SQUARE ROOT EXTRACTION | Applicable |
DIGITAL FILTER | Applicable |
TIME BASE UNIT | Second, minute, hour, day |
CONVERSION FACTOR | 0.00 to 99.99 |
FIVE POINT
LINEARIZATION |
Applicable |
PULSE OUT PUT | Maximum pulse: 20 pulses/Sec.
Excitation Voltage: <24Vdc with maximum 10 mAdc |
LOW FLOW CUT OFF | Applicable |
MOUNTING DETAILS
- Structure: Front fascia IP54 complied(not certified), Enclosure GP (IP20)
- Body construction: Polycarbonate plastic.
- Case color: Dark grey
- Weight: 0.45Kg
- Instrument Dimension: 96 W* 96H*125D max behind panel with terminal (all in mm)
- Mounting Method: Panel mounting
- Panel cut-out: 92W* 92H (all in mm)
- Wiring: 2.5sq.mm
- Standard Accessories: 2 mounting clamp
FRONT PANEL DESCRIPTION
Name of Part | Function |
![]() |
1. It will allow user to enter in EDIT mode, when instrument is in RUN mode.
2. It will scroll menu and submenu When it is enabled. 3. It will save edited data. |
![]() |
1. It will enter into the submenu, when main menu is enabled and shows submenu’s value.
2. It will select the digit to modify, when value is edited. 3. It will start batch, if pressed, when IT & BT are being displayed |
INCREMENT |
1. It will increment value of digit selected or constant selected.
2. It will stop batch, if pressed, when BT/IT are being displayed. 3. For Pause batch press stop key for 1 second. 4. If we press stop key for 3 second then batch becomes zero. |
|
1. It will escape to previous status, with reference to its current status.
Sequence of status: IT MENU SUB-MENU Parameter’s Value Escape sequence When Esc key is pressed in Menu, the instrument will come in RUN Mode. If user wants to go in EDIT mode, he will have to enter the correct password again. 2. When Esc key is pressed in RUN Mode, it will directly enter in to the set point menu. This function is only applicable when type of instrument is totaliser. |
RL1, RL2 RL3,RL4 | When Respective Relay LED Lits (In
Red) OR When Channel is OPEN(Channel no. is corresponding to Relay no.) |
Rx/Tx | When Communication on, two LEDs (In Red) blink. |
BACK PLATE CONNECTION DETAIL
Rear Panel Diagram of 1008S Standard
Rear Panel Diagram Of 1008S With Mass Flow
Terminal Details of 1008S Standard
Terminal Details of 1008S with Mass Flow
Batch total:
This is an eight digit totalized value, displayed as Batch total. As per the selected time base, Zero and Full-scale settings, this total is updated continuously, proportional to input. When New Batch Starts or Integration total is reset this value also gets initialized to 0.
Integration total:
This is an eight digit totalized value, displayed as integrated total. As per the selected time base, Zero and Full-scale settings, this total is updated continuously, proportional to input.
Relay-mode:
In ‘Relay-mode’ (relay nod), if set to ‘normal ‘mode then alarm relays and LEDs will work according to alarm values.
i.e. Relays on, LEDs on
Relays off, LEDs off. But if set to ‘Failsafe’ modede then the alarm relays and LEDs will operate reversibly.
i.e. Relays on, LEDs off Relays off, LEDs on
Cut Off(Low Flow Cut Off):
Cut off could be set to 0000 to 0100. Cut off will display the % value.
Cutoff value = Cutoff parameter (in %)*Full scale value
If full scale value is 10000 and cut off is 5% Then cut off value will be calculated as = (5/100)*10000 = 500.
So, if the displayed flow rate (displayed at upper window) is less then 500, it will not be added to integration.
For operation manual please visit www.masibus.com
Specifications are subject to change without notice due to continuous improvements.
Masibus Automation And Instrumentation Pvt. Ltd.
B-30, GIDC Electronics Estate, Sector-25, Gandhinagar382044, Gujarat, India.
Tel: +91 79 23287275-79
Fax: +91 79 23287281
Web:www.masibus.com
Email:support@masibus.com
FAQs
Q: What are the alarm types supported by by the product?
A: The alarm types supported are Flow high limit and Flow low limit.
Q: What is the power supply specification of the product?
A: The power supply supports 110 to 230 VAC, 50Hz and has a power consumption of…