ADT Security System User Manual

System Reference

The control station features several indicators and keys for system operation:

  • READY Indicator: Green light indicating the system is ready to be armed. If off, one or more zones are faulted.
  • ARMED Indicator: Red light indicating the system is armed. If blinking, it signifies the exit delay period.
  • TROUBLE Indicator: Lighted when a trouble condition exists. Contact your security representative.
  • ALARM Indicator: Lighted when an alarm has occurred.
  • ZONE Indicators (1-6): Indicate the status of individual zones. If lighted, the zone is not secure. If not lighted, the zone is secure. If blinking, the zone is bypassed.
  • Emergency Panic Keys (A, B, C): Used to activate specific emergency alarms (Fire, Hold-up, etc.) as programmed by the installer.

Zone Identification Card: A pull-out card that lists the areas of protection assigned to each zone.

Individual Zone Status:

  • If lighted: Zone is not secure (e.g., door/window open). Check doors, windows, etc.
  • If not lighted: Zone is secure.
  • If blinking: Zone is bypassed.

Ready Status: If lighted, the system is ready to arm. If not lighted, one or more zones are faulted, and the corresponding zone indicator(s) will be lit.

Armed Status: If lighted, the system is armed. If not lighted, the system is disarmed. If blinking, the exit delay is active.

Important Phone Numbers: Fields for Alarm Company, Police, and Fire contact information.

Operating Your System

ARMING

To arm the system prior to leaving:

  1. Ensure the READY indicator is on.
  2. Enter your User Code.
  3. The control station will beep, and the ARMED indicator will blink, signaling the start of the exit delay. The ARMED indicator will become steady when the system is fully armed.
  4. Leave the building immediately. The exit delay allows time to leave through a defined intrusion detection zone without triggering an alarm.

The security system divides protection into two areas:

  • PERIMETER: The first line of defense, typically using door/window contacts.
  • INTERIOR: The second line of defense, using motion detectors or other interior sensors.

You can choose to turn off interior protection before arming to allow free movement within the building.

Turning Off Interior Zones and Entrance Delay

Press and hold key [4] for three seconds to turn interior zones off before arming. Corresponding ZONE indicators will flash. The system automatically re-enables interior zones upon disarming, unless programmed otherwise.

Automatic Interior Off/Delay Off

This feature may be programmed to automatically turn interior zones off if you arm and do not leave before the exit delay expires. The entrance delay may also be turned off automatically.

Two Digit Arming

An abbreviated arming feature may be enabled, requiring only the first two digits of your User Code to arm the system.

System Will Not Arm (READY Light Off)

If the READY indicator is off, one or more detection devices (door, window) are open. The system cannot be armed. The corresponding ZONE indicator(s) will be lit, indicating the faulted area. An attempt to arm with the READY light off will result in a three-second error tone.

DISARMING

To disarm the system upon entering:

  1. After entering through a delay zone, the control station will sound a continuous tone.
  2. CAUTION: If the ALARM indicator is lit, an alarm has occurred. Leave immediately and contact authorities. Do not re-enter the premises.
  3. Enter your User Code.
  4. The ARMED light will turn off, indicating the system is disarmed.

Note on Interior Follower: If enabled, interior zones automatically become delay zones when entering through a delay zone, allowing movement past interior detectors.

Testing the Burglar and Fire Alarm Audibles

Weekly testing is recommended. Notify the Central Station or authorities before and after testing.

  • Burglar Alarm Test: Arm the system, then open a non-delayed door, window, or motion detector to activate the sounding device. Reset by disarming.
  • Fire Alarm Test: Follow procedures for activating auxiliary alarms (refer to page 7 of the manual for specific details, though this reference is internal to the original document and not directly actionable here).

ALARM CONDITIONS

What To Do If An Alarm Occurs

When an alarm occurs, the ALARM indicator lights, the audible alarm sounds (if applicable), and the control may communicate with the central station.

NOTE: If you discover an alarm has occurred upon returning to the premises, DO NOT ENTER. Leave immediately and contact the appropriate authorities.

To reset the alarm:

  1. Enter your User Code.
  2. The ALARM indicator will remain lit.

If the alarm was activated by a hardwire zone, the corresponding ZONE indicator(s) will also light, showing the violated area. Use the zone I.D. card to identify the area. If activated by an emergency key, no zone indicators will light.

Press the "[*]" key to extinguish the ALARM indicator after identifying the alarm type and area.

A history of alarm conditions is stored in memory and can be recalled.

False Alarms

If a false alarm occurs:

  1. Enter your User Code.
  2. The ARMED light should turn off.
  3. Notify the appropriate authorities immediately.
  4. Press the "[*]" key to extinguish the ALARM light. Use the zone I.D. card to identify the area.

THE EMERGENCY KEYPAD PANIC ALARMS

Your system may include up to three emergency panic alarms for activating alarms during Fire, Hold-up, or other emergencies. Each is activated by pressing an appropriate panic key (A, B, or C). Alarms can be audible or silent and may report to a central monitoring station.

Emergency Alarm Activation: Press the relevant panic key (A, B, or C) to activate the alarm. Your installer may have programmed these keys to require a press-and-hold or multiple presses for activation.

Resetting the Emergency Alarm: Enter your User Code. Pressing the "[*]" key will extinguish the ALARM indicator if it is lit.

SPECIAL FEATURES

Chime Mode Operation

The CHIME mode allows audible monitoring of zones while the system is disarmed. When active, the control station beeps when a perimeter zone (door, window) is opened. For example, it might beep twice when the front door opens.

To Turn CHIME On: The system must be disarmed. Press and hold key [6] for three seconds. The control station will beep three times. It will then beep twice for any burglar zone opening. (Note: CHIME does not annunciate Interior zones).

To Turn CHIME Off: Press and hold key [6] for three seconds. The control station will beep two times.

Force Arming

(This feature may be disabled in U.L. Listed systems). Your system may be programmed for quick arming even with faulted zones. If an attempt is made to arm with faulted zones (READY light off), an error tone sounds. A second attempt within eight seconds will bypass faulted zones and force arm the system. Force-armed zones may be permanently bypassed or return to operation later.

Bypassing Zones

The bypass key ([#]) temporarily removes selected zones from the system, preventing them from activating an alarm. This is useful for allowing movement in an area while arming the rest of the system or for zones requiring service.

When zones are bypassed, their corresponding ZONE indicators will flash. This flashing stops 30 seconds after the exit delay expires when the system is armed.

Note: Bypassing zones compromises security. Do not instruct temporary users on this feature.

  • To Bypass A Zone: System must be disarmed. Press BYPASS key ([#]), then enter the zone number (1-6). The ZONE indicator will blink.
  • To Cancel A Zone Bypass: System must be disarmed. Press BYPASS key ([#]), then the zone number (1-6). The ZONE indicator will stop blinking.
  • To Cancel All Zone Bypasses: Press BYPASS key ([#]) followed by key [9]. All ZONE indicators stop flashing.
  • To Bypass All Faulted Zones Simultaneously: System must be disarmed. Press BYPASS key ([#]) then key [0]. All faulted zones will blink.

Key Switch Operation

Your system may use a key switch for arming and disarming.

  • Arming: Verify READY light is on. Insert key, turn, hold for one second, release. ARMED light blinks during exit delay, then becomes steady.
  • Disarming: Insert key, turn, hold for one second, release. ARMED light turns off.

Access

If equipped with the ACCESS feature, the control station can switch other devices on/off or act as a timed switch (e.g., electric door release, lights). Consult your security representative.

The Reset Key

The "[*]" key can be used to:

  • Silence control station sounder and audible output during Auxiliary "A" (Fire) and "C" (Emergency) alarms.
  • Silence control station sounder during Burglar alarms.
  • Exit the audible test mode.

NOTE: Pressing the "[*]" key does not reset alarms or cancel reporting to the central station.

Remote Programming

Your system may be serviced remotely by the alarm company if set up for Remote Programming. Consult your security representative for details.

Programming

Certain system features are programmable via the control station. Enter programming mode by pressing key [9] and holding for three seconds, then entering the Master User Code. Consult your security representative for a list of user-programmable features.

WARNING: Do not attempt to program the system unless properly trained and you fully understand the operation.

USER CODES

The system can accept up to five regular User Codes and one Master User Code. Each code is a four-digit sequence (avoid 1234 or 1111). Codes can be added, deleted, or changed.

The Master User Code (code 1) performs all User Code functions and grants access to programming mode.

User Code 6 can be programmed as a Temporary User Code with a limited number of uses, after which it becomes inoperable. It can be assigned to maintenance personnel or others for limited access.

Changing User Codes

If you make an error during programming, press the "[*]" key five times and restart.

WARNING: Pressing "[#]" or "[*]" while programming a code may cause improper operation. Return to step 1 if an error occurs.

  1. System must be disarmed.
  2. Press and hold key [9] for three seconds (control beeps three times).
  3. Enter the Master User Code (control beeps two times). READY and ARMED indicators blink alternately, other indicators blink repeatedly when programming mode is entered.
  4. Press the key corresponding to the User Code to program (e.g., [4] for User Code 4) or key [1] to change the Master User Code, then press [#]. The control beeps three times.
  5. Enter the new 4-digit code sequence. A short beep followed by a long beep indicates acceptance and exit from programming mode.

Deleting a Code

  1. System must be disarmed.
  2. Press and hold key [9] for three seconds (control beeps three times).
  3. Enter the Master User Code (control beeps two times). Indicators blink as described above.
  4. Press keys [1], then [0], then [#] to initiate code deletion. Control beeps three times.
  5. Enter the number of the code (1-6) to be deleted.
  6. The code is deleted, and the system exits programming mode.

Programming A Temporary Code (User Code 6)

Assign a limited number of uses to User Code 6. After uses expire, it becomes disabled. It can be re-enabled by reprogramming the number of uses.

  1. System must be disarmed.
  2. Press and hold key [9] for three seconds (control beeps three times).
  3. Enter the Master User Code (control beeps two times). Indicators blink as described above.
  4. Press key [6], then [#] to program the code sequence for User Code 6. Control beeps three times.
  5. Enter the desired four-digit code sequence. A short beep followed by a long beep indicates exit from programming mode.
  6. Repeat step 2 to re-enter programming mode.
  7. Press keys [7] plus [#] to program the number of valid uses for User Code 6. Control beeps two times.
  8. Enter the number of uses (1-255), then press "[*]". Control beeps two times.
  9. Press "[*]" twice to exit programming mode.

Note: Temporary codes perform all functions of regular User Codes. Only the Master User Code (Code 1) allows entry into programming mode. Remote Programming is not available in U.L. Listed Systems.

NOTE REGARDING REMOTE PROGRAMMING: If the ALARM indicator lights steadily after entering programming mode, your installer has enabled Remote Programming, allowing remote service and control by the installing company.

Audible Zone Testing

The TEST mode makes the control station beep continuously and light the zone indicator for each violated zone. Testing is only possible while the system is disarmed and should be done in both AC power and standby battery modes.

Inform neighbors about the system and ask them to notify authorities if they hear it sounding. Burglar alarms typically have a pulsing bell; fire alarms have a steady horn.

Note: A lighted zone indicator means at least one sensor in that zone was tested. Test your system weekly.

  1. System must be disarmed.
  2. Use the zone I.D. card to identify each zone.
  3. To simplify testing, secure all zones first (READY light ON). If not possible, the control will beep continuously for non-secure zones.
  4. Press and hold key [8] for three seconds. Control beeps three times to enter TEST mode.
  5. Violate a detection zone (e.g., open a door). The control beeps continuously, and the zone indicator lights.
  6. Secure the zone (close the door). The control station beeping ceases.
  7. Interior detection devices may also cause beeping unless INTERIOR is turned OFF. You can also walk test motion detectors to check coverage.
  8. Begin at step 5 to test remaining sensors.
  9. Press "[*]" when finished testing.

Note: Test your system at least once per week. If the wall transformer is removed, test the system to ensure the standby battery is adequate. Reconnect the transformer and test again.

FIRE DETECTION

Your system may include fire detection based on purchased options and local regulations. Fire alarm systems are active 24/7 and require regular testing and maintenance. Dust can cause smoke detectors to false alarm.

What To Do If The Fire Alarm Sounds

  1. The ALARM indicator lights, and the alarm sounder sounds steadily. ZONE indicators for violated Fire Zones light up. No zone indicators light if activated by an emergency panic zone.
  2. Press "[*]" to silence the control station and audible alarm.
  3. Notify the alarm monitoring service or authorities immediately if the alarm was unintentional.
  4. The ALARM light remains on.
  5. Enter a valid User Code to clear the alarm.
  6. If the TROUBLE indicator lights, a Fire Supervisory/Trouble condition may exist. Consult your Security Representative.

Fire Supervisory/Trouble (Resetting Smoke Detectors)

Smoke detectors may latch on and illuminate an indicator when triggered. If a detector remains latched after a fire alarm, the yellow TROUBLE indicator will light.

  1. Check all smoke detectors for a latched condition to identify the triggered detector. If all appear normal, a wire may be broken or shorted; call for service.
  2. Press and hold key [7] for three seconds. The system attempts to reset smoke detectors. If they do not reset, the TROUBLE condition persists; call your security representative.

Emergency Evacuation Plan

Preparation and education are crucial for fire prevention. Establish an emergency evacuation plan BEFORE an emergency arises. Ensure your installer explains your system's fire detection and notification capabilities.

Steps for establishing an evacuation plan:

  1. Evaluate all possible escape routes and draw a floor plan.
  2. Select two exit escape routes from each room.
  3. Provide emergency escape ladders for rooms above the first floor, ensuring they reach the ground.
  4. Draw a rough sketch of the plan for everyone to understand.
  5. Practice the plan to ensure everyone knows their role.
  6. Establish an outside meeting place for family members.
  7. Advise the local fire authority if a fire alarm system is installed.

Discuss the following with all residents:

  1. Familiarity with alarm signals.
  2. Status of bedroom doors (check for heat).
  3. Testing doors during a fire and using alternate escape routes if a door is hot.
  4. Crawling and holding breath techniques during a fire.
  5. Escape FAST; DO NOT STOP for packing.
  6. Emphasize that no one is to return to a burning building.

Fire Prevention and Escape

Heat and smoke detectors detect fires early, allowing occupants more time to exit before smoke becomes dangerous.

KNOW FIRE HAZARDS

No detection device is foolproof. Take safeguards against hazards like smoking in bed, leaving children unattended, and using flammable liquids. Minimize fire hazards through proper storage and housekeeping. Careless use of combustibles and overloading electrical outlets are common fire causes. Eliminate explosive and fast-burning materials.

IN CASE OF FIRE

Leave immediately! Do not pack or search for valuables. In heavy smoke, stay low and crawl. The clearest air is usually near the floor. When passing through a closed door, feel it and the doorknob for heat. If cool, brace your foot against the bottom, push with your hip and hand on the top edge, and open slightly. If hot air rushes in, slam it shut. Unvented fires build pressure.

Use a neighbor's phone or a street fire alarm box. Extinguishing fires should be left to professionals.

BE PREPARED

Conduct fire drills regularly to practice recognizing alarm signals. Simulate different scenarios. Draw floor plans showing two exits per room. Instruct children carefully, as they may hide during a crisis.

Establish an outside meeting place. This prevents people from re-entering a burning building for missing family members who may be safe.

Consider placing decals on bedroom windows if small children or invalids reside in the household.

Become familiar with the sounds of your Fire and Burglar alarm signals.

FIRE PROTECTION

Smoke Detector Location

Smoke detectors should be installed per National Fire Protection Association (NFPA) Standard 74.

Detectors should be installed outside each sleeping area, near bedrooms, and on each additional story of a family living unit, including basements, excluding crawl spaces and unfinished attics. For split-level units, a detector on an upper level may suffice for the adjacent lower level.

EXCEPTION: If there is an intervening door between levels, a detector must be on the lower level.

Ceiling-mounted alarms should be in the center of the room/hall, at least 4 inches from any wall. Wall-mounted detectors should have the top 4 to 12 inches from the ceiling.

Do not install alarms where ambient temperatures are above 100°F (37.8°C) or below 40°F (4°C).

Avoid locations in front of air conditioners, heating registers, or areas with strong air circulation that could prevent smoke from reaching the detector.

Heat rises to the ceiling and spreads. The corner where the ceiling and wall meet has a 'dead' air space (approx. 4 inches along the ceiling and 4 inches down the wall) that heat may not penetrate easily. Detectors should not be placed in this space.

Smoke Detector Placement Diagram Description

The diagram illustrates acceptable and unacceptable placement of smoke detectors relative to the ceiling and walls. It shows a 'dead' air space in the corner that should be avoided. Measurements indicate acceptable ranges from the ceiling and wall.

Additional diagrams show typical floor plans for single-story and multi-story homes, indicating required smoke detector locations (black dots) and optional locations (circles with crosses) if doors are not provided between living and recreational rooms.

  • A smoke detector should be located on each story.
  • A smoke detector should be located between the sleeping area and the rest of the family living unit.
  • A black dot indicates a required smoke detector.
  • A circle with a cross indicates an optional smoke detector if a door is not provided between living and recreational rooms.

Glossary

  • Alarm Memory: A history of the last alarm that occurred.
  • Arm: To turn the intrusion detection system on.
  • Bypass: To temporarily remove a zone from operation; also called shunting.
  • Control Panel: The main system electronics housed in a metal enclosure.
  • Control Station: The remote station used to enter instructions to the control panel (e.g., arm, disarm, bypass). Also called a keypad.
  • Delay Zone: A zone allowing programmable time to enter and disarm without alarm, and providing an exit time.
  • Disarm: To turn the intrusion detection system off.
  • Entrance Delay: Time permitted to enter armed premises through a delay-defined zone.
  • Faulted: A detection area that is not secure (e.g., open door/window), causing the control to lose its "Ready" status.
  • Force Arm: To override and force the system to arm when one or more zones are not ready.
  • Hardwire Zones: The six areas of protection referred to as Zones 1-6 on the control station.
  • Indicator Lights: The ten lights (LEDs) on the control station.
  • Interior: The backup or second line of defense, typically using motion detectors or interior door contacts.
  • Interior Follower Feature: Converts interior zones to delay zones upon entry through a delay door, allowing passage through interior zones to disarm the system.
  • Keypad: A generic term for the control station.

FCC COMPLIANCE

This equipment generates and uses radio frequency energy. If not installed and used properly per manufacturer's instructions, it may cause interference to radio and television reception. It has been tested and found to comply with Class B limits for computing devices under FCC rules, designed to provide reasonable protection against interference in residential installations. However, interference is not guaranteed in all installations.

If interference occurs, the user is encouraged to try correcting it by:

  1. Reorienting the TV or radio antenna.
  2. Relocating the alarm control away from the receiver.
  3. Plugging the transformer into a different outlet so the receiver and alarm are on different circuits.
  4. Consulting an alarm dealer or experienced radio/television technician if necessary.

The booklet "How To Identify and Resolve Radio-TV Interference Problems" from the U.S. Government Printing Office may be helpful.

ALL RIGHTS RESERVED

No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form without written permission from Aritech Corp. Material is for informational purposes and subject to change without notice. Aritech Corp assumes no responsibility for errors. Printed in U.S.A.

The MOOSE logo is present, identifying it as a product of SENTROL, INC. Sentrol, Inc reserves the right to change specifications without notice. ©1991 Sentrol, Inc.

PDF preview unavailable. Download the PDF instead.

ADT37 Photoshop PDF Plug-in 1.0 Photoshop PDF Plug-in 1.0

Related Documents

Preview ADT Security System User Manual: Operation, Features, and Fire Safety
Comprehensive user manual for ADT and Moose security systems, covering arming, disarming, alarm conditions, special features, fire detection, and emergency evacuation. Learn how to operate and maintain your security system.
Preview ADT FOCUS 200 PLUS Commercial Fire & Burglary Alarm System User Guide
User guide for the ADT FOCUS 200 PLUS commercial security system. Learn about installation, operation, programming, and troubleshooting for fire and burglary alarms.
Preview BHS 4000A System Manual - ADT Security System Guide
Comprehensive system manual for the ADT BHS 4000A security system, covering operation, arming/disarming, panic alarms, troubleshooting, and system testing for home and business users.
Preview ADT Focus 200 Plus Security System User Guide
User guide for the ADT Focus 200 Plus Commercial Fire & Burglary Alarm System. This manual provides information on system overview, quick start, false alarm prevention, and system operation.
Preview ADT Unimode 10 Fire Control Communicator: Programming, Installation, Maintenance, and Operation Manual
Comprehensive manual for the ADT Unimode 10 Fire Control Communicator, covering programming, installation, maintenance, and operating instructions. Learn about its features, specifications, and how to ensure optimal performance.
Preview ADT 4520-810 Power Supply Unit: Technical Specifications and Operation
Detailed technical specifications, features, operation, installation, and testing procedures for the ADT 4520-810 Power Supply Unit, a component for Unimode fire alarm monitoring and control systems.
Preview ADT TSSC-BASE and TSSC-KP User Guide: Operation and Features
Comprehensive user guide for the ADT TSSC-BASE Base Control Unit and TSSC-KP Wireless Bidirectional Alpha Keypad. Learn about system features, key functions, operation, user codes, testing, battery replacement, and warranty information.
Preview Honeywell Lynx Touch Battery Replacement Guide | ADT
Step-by-step instructions for safely replacing the backup battery in your Honeywell Lynx Touch home security system. Learn how to put your system in test mode and properly dispose of old batteries.